F-Series
Circuit Breaker
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062-1177
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: sales@carlingtech.com • www.carlingtech.com
The F-Series hydraulic/magnetic high amperage circuit
breakers are designed to handle high current applications
in extremely hot and/or cold locations. Due to its time-
proven hydraulic/magnetic design, the F-Series load
sensing mechanism is insensitive to changes in ambient
or enclosure temperature, providing a consistent trip
point over temperatures ranging from -40°C to +85°C.
Additionally, the F-Series circuit breakers come with a
choice of overload time delays, making them ideal for
critical applications having inductive loads.
Further, the F-Series breakers are available up to 700A
and an optional 25 millivolt metering shunt construction
provides a safe method for monitoring current flowing
through the breaker by simply connecting a meter with
light gauge wire to the appropriate terminals located on the
shunt housing at the rear of the breaker. Applications can
be customized by measuring and displaying percentage of
current, watts or safe/danger zones.
Features:
AC ratings to UL 489
DC voltage ratings up to 700A with metering
shunt section
Consistent trip point over temperatures ranging
from -40°C to +85°C
Optional 25 millivolt metering shunt construction
Applications:
Ideal for applications under extreme temperatures
Higher Amperage Applications
Battery Disconnect Systems
Solar Power Systems
Military
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
2 |
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
F-Series Circuit Breaker - General Specications
Mechanical
Physical
Environmental
Electrical
Maximum Voltage
Current Rating
Auxiliary Switch Rating
Insulation Resistance
Dielectric Strength
Resistance, Impedance
Endurance
Trip Free
Trip Indication
Number of Poles
Internal Circuit Cong.
Available Accessories
Weight
Standard Colors
Shock
Vibration
Moisture Resistance
Salt Spray
Thermal Shock
Operating Temperature
Designed and tested in accordance with requirements of
specication MIL-PRF-55629 & MIL-STD-202 as follows:
125VDC, 277 VAC
Standard current coils: 100, 125,
150, 175, 225, 250 amps. 300, 350,
400, 500, 600, 700 amps available as
parallel pole construction.
SPDT; 10.1 Amps @ 250VAC, 1.0
Amps @ 65VDC, 0.5 Amps @ 80VDC
0.1 Amps @ 125VAC (with gold
contacts).
Minimum: 100 Megohms at 500 VDC
1960 VAC, 50/60 Hz for one minute
between all electrically isolated
terminals, except 2500 VAC for one
minute between alarm/aux. switch
and main terminals with contacts in
open and closed position. F-Series
circuit breakers comply with the
8mm spacing & 3750VAC 50/60
Hz dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main circuits
to auxilary circuits per Publications EN
60950 and VDE 0805.
Values from Line to Load Terminal -
based on Series Trip Circuit Breaker.
4000 ON-OFF operations with rated
Current & Voltage & 4000 operations
with no load (8000 operations
total) @ 5 per minute. Parallel Pole
construction: 1000 operations with
rated Current and Voltage @ 5 per
minute.
All F-Series Circuit Breakers will trip on
overload, even when the actuator is
forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when
an overload causes the circuit breaker
to trip.
1 - 3 Poles Note: Ratings over 250
Amps only available with parallel pole.
Series (with or without auxiliary
switch), Switch Only (with or without
auxiliary switch).
Factory installed: DC Current Metering
Shunt (25 mV @lr)
Varies depending on construction.
Consult factory.
Housing - Black; Actuator- Black
or White with contrasting ON-OFF
legend.
Withstands 100 Gs, 6ms, sawtooth while
carrying rated current per Method 213,
Test Condition “I”. Instantaneous and
ultra-short curves tested @ 90% of rated
current.
Withstands 0.060” excursion from 10-
55 Hz, and 10 Gs 55-500 Hz, at rated
current per Method 204C, Test Condition
A. Instantaneous and ultrashort curves
tested at 90% of rated current.
Method 106D; ten 24-hour cycles @ +
25°C to +65°C, 80-98% RH.56 days @
+85°C, 85% RH.
Method 101, Condition A (90-95% RH @
5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five cycles
@ -55°C to +25°C to +85°C to +25°C).
-40°C to +85°C.
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 3
Table A: Lists UL Listed (489)and CSA Certified (C22.2 N0. 5.1-M) configurations and performance
capabilities as a Molded Case Circuit Brekaer
CURRENT
RATING
CIRCUIT MAX FULL LOAD UL / CSA
TUV
2
CONFIGURATION RATING FREQUENCY PHASE AMPS 1 - 3 POLES 1 or 2 POLES
125 DC --- 50 - 250 50,000 25,000
120 / 240 150 / 60 1 100 - 250 10,000 ---
277 50 / 60 1 100 - 250 10,000 ---
208Y / 120 50 / 60 3 100 - 250 10,000 ---
NOTES:
1. 120/240V rating available in 2 or 3 poles. In a 3 pole construction the center pole is Neutral.
2. TUV constructions are not available with AC ratings.
SERIES
F SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
VOLTAGE
INTERRUPTING
CAPACITY (AMPS)
F-Series Circuit Breaker - General Specications
Electrical Tables
Table A: Lists UL Listed (489)and CSA Certified (C22.2 N0. 5.1-M) configurations and performance capabilities as a Molded Case Circuit Breaker
Table B: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A
Agency Certifications
UL Listed
UL 489
UL 489A
TUV Certied
Circuit Breakers , Molded Case
(Guide DIVQ, File E129899)
Complies with the requirements
of the CSA Standard for Molded
Case Circuit Breakers,
CANCSA- C22.2 No. 5.1 –M
Circuit Breakers for Use in
Communications Equipment
(Guide DITT, File E189195)
IEC 60947-2
Low Voltage Switchgear and Control
Gear under TUV License No.
R72031058
Notes:
1 120/240V rating available in 2 or 3 poles. In a 3 pole construction the center pole is Neutral.
2 TUV constructions are not available with AC ratings.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
4 |F-Series Handle – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting
11
Max. App.
Rating
12
Agency
Approval
4
Circuit
F A B 1 A2 0 2 B G14 820
1 SERIES
F
2 ACTUATOR
A Handle, one per pole
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
8 TERMINAL
Back Connected (Front Mounted Only) Max Rating
19 3/8-16 Stud 250A
214 3/8-16 Screw, Line & Load 700A
514 3/8-16 Short Stud 250A
Front Connected (Back Mounted Only)11 Max Rating
3 Box Wire Connector, Line & Load 700A
414 3/8-16 Screw, Line & Load 700A
10 MOUNTING
Front Mounting Inserts
A 10-32
B ISO M5
Back Mounting Inserts
10-32 screw clearance holes
10-32 screw clearance holes
3 POLES
1 One 2 Two 3 Three
5 AUXILIARY/ALARM SWITCH5
0 w/o Aux Switch
2 S.P.D.T., 0.110 Q.C. Term.
3 S.P.D.T., 0.139 Solder Lug
4 S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
5 S.P.S.T., 0.093 Q.C. Term.
(Gold Contacts)
6 S.P.S.T., 0.139 Solder Lug
7 S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
8 S.P.S.T., 0.187 Q.C.
Terminals
9 S.P.D.T., 0.187 Q.C.
Terminals.
A6 S.P.S.T., 0.093 Round QC
Terminals.
B6 S.P.D.T., 0.093 Round Q.C.
Terminals.
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
107 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
22 AC Short
24 AC Medium
26 AC Long
7 CURRENT RATING (AMPERES)
OR VOLTAGE COIL (VOLTS, MIN. TRIP RATING)7
810 100.00
912 125.00
815 150.00
917 175.00
820 200.00
922 225.00
825 250.00
8308 300.00
8358 350.00
8408 400.00
8458 450.00
8508 500.00
8608 600.00
8708 700.00
CODE AMPERES
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
CODE AMPERES
11 MAXIMUM APPLICATION RATING
VOLTAGE CURRENT
B 125 VDC 700A
C15 120/240 250A
F 277 VAC 250A
716 120/208 VAC 250A
12 AGENCY APPROVAL
A No approvals
G UL 489 Listed & CUL Certied
J UL 489 Listed, CUL Certied & TUV Certied
T UL489A (Telecom) Listed
9 ACTUATOR COLOR & LEGEND12,13
Acuator Color I-O ON-OFF Dual Marking Color
White A B 1 Black
Black C D 2 White
Notes:
1 For 100 to 250 amps, select Current Code 825. For 300-400 amps, select Current
Code 840. For 450-700 amps, select Current Code 870.
2 Available with Frequency and Delay code 10 or 20 only, and are not rated for continuous
duty. Delay 10 and 20 are only available with voltage coils.
3 3 Codes M, N, P & Q (Parallel Poles) are supplied with factory installed Bus Bar on
Line and Load.
4 4 Metering terminals are female pin type, ref. Molex part number 02-09-1101, model
1189-T.
5 Auxiliary Switch breakers are only available with Series Trip and Switch Only circuits.
On multi-pole breakers, one Auxiliary Switch is supplied, mounted in the extreme right
pole per gure A. Back-Mounted breakers require special mounting provisions when
an Auxiliary Switch is specied.
6 Available with parallel pole construction (circuit codes P and Q, and breakers with
circuit codes M and N).
7 Frequency and delay code 10 is only available with Voltage Coils. Voltage Coils are not
rated for continuous duty.
8 Ratings over 250 amps are only available with Agency Approval code T (UL489A) and
are Parallel Pole conguration (circuit codes M, N, P and Q.) 300-450 amp ratings are
available on two pole breakers. 500-700 amp ratings are available on three pole breakers.
9 Per UL requirement, an “Anti-Flash Over Barrier” is supplied between poles on multipole
breakers with 3/8 - 16 stud terminals (Terminal Code 1)
10 Front connected breakers can also be front mounted by utilizing the supplied front panel
mounting inserts.Terminal connections must be made before mounting.
11 Box Wire connector will accept #6 through 250 MCM copper wire.
12 Agency codes G & T must have ON-OFF or dual legends. Agency code J must have dual
legend.
13 Other colors available. Consult factory.
14 Terminals 2,4 & 5 are shipped without terminal hardware.
15 2 or 3 Pole Circuit Breaker Required for 120/240 VAC Rating.
16 3 Pole Circuit Breaker Required for 120/208 VAC Rating.
4 CIRCUIT
A1 Switch Only (no coil)
B Series Trip (current)
C2 Series Trip (voltage)
Parallel Pole Construction:
M3,4 Series Trip (Current) with
Metering Shunt
N3,4 Switch Only with
Metering Shunt
P3 Series Trip (Current)
Q3 Switch Only
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 5 F-Series Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
6 |F-Series Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 7 F-Series Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
8 |F-Series Handle – Form & Fit Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 9 F-Series Handle – Form & Fit Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
10 |F-Series Handle – Form & Fit Diagrams
F-Series breakers are available up to 700A, and are also available with a 25 millivolt metering shunt
construction. This optional construction provides a safe method for monitoring current owing through
the breaker by simply connecting a meter with light gauge wire to the appropriate terminals located
on the shunt housing at the rear of the breaker. You can customize the application by measuring and
displaying percentage of current, watts or safe/danger zones.
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 11 F-Series Handle – Form & Fit Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
12 |F-Series Circuit Breaker - Time Delay Curves
Long - AC 26
F SERIES
50/60 HZ LONG
CURVE NO. 26
F SERIES
50/60 HZ SHORT
CURVE NO. 22
F SERIES
50/60 HZ MEDIUM
CURVE NO. 24
22
16
14
12
11
No Trip
No Trip
No Trip
No Trip
No Trip
.700 - 12.0
110 - 1000
10.0 - 110
.475 - 10.0
.013 - .125
10.0 - 160
50.0 - 700
.350 - 4.00
60.0 - 400
6.00 - 40.0
.275 - 2.80
.010 - .070
6.00 - 60.0
32.0 - 350
.130 - 1.30
22.0 - 150
2.50 - 15.0
.140 - .850
.008 - .032
.220 - 20.0
10.0 - 90.0
.027 - .220
4.00 - 25.0
.500 - 3.00
.030 - .190
.006 - .020
.300 - 3.00
1.50 - 15.0
.008 - .130
1.00 - 5.50
.180 - 1.00
.015 - .125
.005 - .020
.050 - 1.30
.500 - 7.00
.004 - .090
.010 - 1.80
.010 - .280
.010 - .050
.004 - .020
.007 - .500
.020 - 3.00
.004 - .045
.004 - .020
.008 - .390
.008 - .080
.008 - .038
.005 - .060
.006 - 2.00
No Trip
No Trip
24
26
Short - AC 22 Ultrashort - DC
Short - DC
Medium - DC
Long - DC
Medium - AC 24
DCAC
REV_CB_F_0612