Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
Features
• Designed for the international market. UL Recognized (UL1077 and
UL1500), CSA Accepted and VDE approved.
Ratings to 50 amps.
• Heavy duty #10-32 stud connections. (W9)
Quick-connect or screw terminals. (W6)
Optional 10 amp auxiliary switch.
• Several delay curve options.
• Choice of toggle or rocker actuator per pole or per unit (W6).
Optional relay/remote trip pole available.
Trip-free operation.
Agency Approvals
UL: Recognized as Supplementary Protector under UL 1077. Available
models meet Ignition Protection requirements in accordance with
UL1500. File E69543.
CSA: Accepted as a Supplementary Protector. File LR15734.
VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
License No. 73782.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to confirm the product meets the
requirements for a given application.
Mechanical/Environmental Data
Operating Temperature: -40°C to +85°C.
Humidity: Meets requirements of Mil-STD-202 method 103.
Shock: Tested per Mil-STD-202, method 213, test condition C
(100g @ 6 ms).
Vibration:Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06"
(1.52mm) total excursion in 2 planes.
Fungus And Moisture Resistance: Special moisture resistant finish
applied to all ferrous parts.
Plastic parts are made of inherently
fungus resistant material.
Marking: International “1” and “0” symbols are marked on the toggle for
both W6 and W9. W9 units have “ON” and “OFF” molded into
the area at the base of the toggle. On a special order basis,
graphics can be imprinted on the rockers of rocker actuated W6
units. VDE approved versions of rocker actuated W6 breakers
have their rockers imprinted with “1” and “0.”
Mounting: Units are mounted with two #6-32 screws from the front of
the panel. Metric models for use with M3 x 0.5 screws are
available. To maintain published performance specifications,
units should not be mounted more than 90° from their normal
upright position.
Weight: Approximately 2.5 ounces per pole.
W6/W9 series
Magnetic Hydraulic
P&B Circuit Breakers
Electrical Data
Auxiliary Switch: See Auxiliary Switch Ratings Table 2 for details.
Calibration: Breakers will hold 100% of rated current.
Breakers may trip between 101% and 124% of rated load
(134% for AC/DC units).
Breakers must trip at 125% of rated load and above (135%
for AC/DC units).
Dielectric Strength: 50/60 Hz., 1500V: DC, 1100V.
Insulation Resistance: 100 Megohms at 500VDC.
Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Units tested at six cycles per minute, 1 second on and 9
seconds off at 25°C ambient.
Relay Trip Coil: (Ratings applicable to all W6 models with this option)
24 to 277VAC, 150mA minimum available current;
6 to 48VDC, 300mA minimum available current.
Approvals and Ratings Table 1
Typical Resistance and Impedance
DC 50/60 Hz.
Current Resistance Impedance
(Amps) (Ohms) (Ohms)
0.2 90 90
1.0 1.2 1.2
2.0 0.28 0.28
5.0 0.04 0.04
10.0 0.013 0.013
20.0 0.004 0.005
30.0 0.0027 0.004
40.0 0.002 0.002
50.0 0.0015 0.0015
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
W9 Series UL1077/CSA (All Circuit Functions) W6 or W9 Series UL1500 (Circuit Function X)
Current Interrupting Current Interrupting
Maximum Frequency Phase Rating Capacity Maximum Frequency Phase Rating Capacity
Voltage (Hz) (Amps) (Amps) Voltage (Hz) (Amps) (Amps)
65 DC - 0.2 - 50 2,000 48 DC - 0.2 - 50 3,000
277 50/60 1 0.2 - 50 5,000 125/250 50/60 1 0.2 - 50 1,000
277/480 50/60 3Ø-Wye 0.2 - 20 5,000 250 50/60 3Ø-Wye 0.2 - 50 1,000
W6 Series UL1077/CSA (All Circuit Functions) W6 or W9 Series VDE (Circuit Function X)
Current Interrupting Current Interrupting
Maximum Frequency Phase Rating Capacity Maximum Frequency Phase Rating Capacity
Voltage (Hz) (Amps) (Amps) Voltage (Hz) (Amps) (Amps)
65 DC - 0.2 - 50 2,000 65 DC - 0.2-50 2,000
277 50/60 1 0.2 - 20 5,000 250 50/60 1 0.2-30 5,000
277 50/60 1 21 - 50 2,500 250 50/60 1 31-50 2,000
277/480 50/60 3Ø-Wye 0.2 - 20 5,000 415/240 50/60 0.2-30 5,000
Auxiliary Switch Ratings Table 2
UL/CSA
Switch Voltage Current Terminals
Number 50/60 Hz. (Amps) WxTxL
A 125 10 .093 x .020 x .250
(2.36 x .51 x 6.40)
2
Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
Time vs. Current Trip Curves For W6 Series and W9 Series
Note:
For instantaneous curves for all voltages refer to Curve 0 Instantaneous under the AC 50/60 Hz. heading.
Pulse tolerance is defined as a single pulse of a half sine
wave (1/2 cycle or 8 milliseconds) that will not trip the
breaker. An inertia wheel for increased pulse tolerance is
available by specifying “P” after the time delay curve
number in the ordering information. The table at right lists
pulse tolerance values of standard and inertia delay models.
AC 50/60 Hz.
DC
AC/DC
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,000
1000
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 0 INSTANTANEOUS
OVERLOAD @ 50/60 Hz. & DC @ 400 Hz.
125% 100 ms max. May Trip
150% 55 ms max. 100 ms max.
200% 30 ms max. 30 ms max.
400% 15 ms max. 15 ms max.
600% 12 ms max. 12 ms max.
800% 12 ms max. 12 ms max.
TRIP TIMES
400 Hz.
DC & 50/60 Hz.
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,000
1000
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 2 STANDARD DELAY 50/60 Hz.
OVERLOAD TRIP TIMES
(SEC.)
125% 10 - 150
200% 2.2 - 20
400% .2 - 2
600% .03 - .75
800% .007 - .15
1000% .005 - .04
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,000
1000
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 2 STANDARD DELAY DC
OVERLOAD TRIP TIMES
(SEC.)
125% 2 - 55
200% .60 - 8
400% .1 - 1.5
600% .02 - .5
800% .004 - .05
1000% .004 - .025
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,000
1000
100
10
1
.1
.01
.001
0
TIME IN SECONDS
MOTOR START / LONG DELAY
CURVE 10 HIGH INRUSH 50/60 Hz. AC
OVERLOAD TRIP TIMES
(SEC.)
125% 40 - 500
200% 9 - 100
400% 2 - 20
600% .8 - 10
800% .1 - 4.5
1000% .009 - 2
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,000
100 0
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 12 HIGH INRUSH 50/60 Hz.
125% 10 - 150
200% 3 - 25
400% .5 - 2.5
600% .15 - 1
800% .015 - .7
1000% .009 - .35
OVERLOAD TRIP TIMES
(SEC.)
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,000
1000
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 3 SHORT DELAY DC
OVERLOAD TRIP TIMES
(SEC.)
125% .6 - 7
200% .16 - 1.5
400% .03 - .25
600% .01 - .13
800% .004 - .05
1000% .003 - .015
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,0 0 0
100 0
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 34 DC, 50/60 Hz. STANDARD DELAY
OVERLOAD TRIP TIMES
(SEC.)
135% 1 - 90
200% .60 - 20
400% .095 - 2
600% .02 - .95
800% .002 - .45
1000% .002 - .09
135
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,0 0 0
100 0
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 13 HIGH INRUSH 50/60 Hz.
OVERLOAD TRIP TIMES
(SEC.)
125% .8 - 30
200% .15 - 2.5
400% .03 - .3
600% .02 - .15
800% .009 - .12
1000% .009 - .09
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,000
1000
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 3 SHORT DELAY 50/60 Hz.
OVERLOAD TRIP TIMES
(SEC.)
125% 1 - 15
200% .15 - 1.5
400% .03 - .25
600% .007 - .15
800% .003 - .08
1000% .003 - .04
100 200 300 400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125 150
10,0 0 0
1000
100
10
1
.1
.01
.001
0
TIME IN SECONDS
CURVE 53 DC HIGH INRUSH
OVERLOAD TRIP TIMES
(SEC.)
125% 80 - 700
200% 15 - 150
400% 2 - 20
600% .70 - 10
800% .10 - 3
1000% .01 - .1
Pulse Tolerance Specifications
Pulse Tolerance Value
Time
Delay Inertia
Voltage Curve Standard Delay
2 7.5 18
AC 36 18
50/60 Hz. 10 18 30
12 18 30
13 18 30
To determine pulse tolerance multiply breaker rating by value in table. For
example, a 2A breaker with time delay curve 3 has a standard pulse tolerance
of 12A (2A x 6). The same breaker with an inertia delay has a pulse tolerance
of 36A (2A x 18).
3
Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
Ordering Information
W 67- X2 Q 1 2- 20
Typical Part No. >
W6 Series
1. Circuit Breaker Mounting:
W = #6-32 mounting threads.
M = M3.0 x 0.5 mounting threads.
2. Number of Poles:
67 = Single pole 68 = Two pole 69 = Three pole 70 = Four pole
3. Circuit Function: (Only X is VDE approved)
A = Series trip with auxiliary switch (.093” QC)
X = Series trip
D = Series trip with auxiliary relay trip pole (requires extra pole package, 3 pole (4 pole package) max., must
specify #10-32 screw terminals below, but relay trip pole will be equipped with .250” QC term. only, not UL),
relay trip pole will be on the right side of the breaker when viewed from the front.
4. Actuator:
One actuator per pole
1 = Black toggle 3 = Black rocker 5 = Red rocker 9 = Red toggle
2 = White toggle 4 = White rocker 6 = Grey rocker
One actuator per unit
7 = Black toggle 8 = White toggle J = Black rocker
5. Termination:
Q = .250” QC (DIN 46 244) [30A Max. UL/CSA; 25A Max. VDE]
S = #8-32 screw [30A Max.]
T = #10-32 screw [50A Max.]
U = #8-32 screw, nickel plated, bent inward 30° [30A Max.]
V = #10-32 screw, nickel plated, bent inward 30° [50A Max.]
Notes: #10-32 termination must be used for all ratings of greater than 30 amps.
#10-32 termination must be specified for circuit function D, but relay trip pole will be equipped with .250” QC.
6. Maximum Line Voltage: (See Table 1 for current ranges)
UL/CSA 1 = 277VAC, 50/60 Hz.
TYPES 2 = 277/480VAC, 50/60 Hz. [20A Max.] (Requires insulating barriers, see outline dimension drawing)
5 = 65VDC
7 = AC/DC 277VAC, 50/60 Hz. or 65VDC
(Time delay curve 34 must be specified.)
8 = AC/DC 120VAC, 120/240VAC, 48VDC
(Agency Approval M [UL1500] and time delay curve 34 must be specified.)
VDE 1 = 250VAC, 415/240VAC
TYPES 5 = 65VDC
7 = AC/DC 250VAC, 415/240VAC, 65VDC
(Time delay curve 34 must be specified.)
7. Time Delay Curve:
0 = Instantaneous 10 = AC high inrush motor start / long delay
2 = Standard delay 12 = AC high inrush version of #2
3 = Short delay 13 = AC high inrush version of #3
53 = DC high inrush 34 = Combination AC/DC standard delay
Notes: Curves may be specified with increased pulse tolerance for 1/2 cycle by adding "P" after curve.
See delay curve section for availability and details.
8. Amp Rating:
0.20 0.50 1.0 2.0 3.0 4.0 6.0 7.5 9.0 11.0 15.0 25.0 35.0 45.0 Consult factory for
0.25 0.75 1.5 2.5 3.5 5.0 7.0 8.0 10.0 12.0 20.0 30.0 40.0 50.0 other values.
9. Agency Approval:
Blank = UL1077/CSA breaker
V = VDE approved breaker without auxiliary switch
M = UL1077/UL1500 ignition protected breaker
W67-A2Q12-5
W67-A2Q12-10
W67-X2Q10-3
W67-X2Q10-5
W67-X2Q12-2
W67-X2Q12-3
W67-X2Q12-5
W67-X2Q12-7
W67-X2Q12-10
W67-X2Q12-15
W67-X2Q12-20
W67-X2Q12-30
W67-X2Q13-1
W67-X2Q13-2
W67-X2Q13-3
W67-X2Q13-10
W67-X2Q13-15
W67-X2Q13-20
W67-X2Q13-25
W67-X2Q13-30
W67-X2Q50-5
W67-X2Q50-10
W67-X2Q52-5
W67-X2Q52-10
W67-X2Q52-15
W67-X2Q52-20
W67-X2Q52-30
W67-X2Q110-15
W67-X2Q110-20
W68-X2Q12-3
W68-X2Q12-5
W68-X2Q12-7
W68-X2Q12-10
W68-X2Q12-15
W68-X2Q12-20
W68-X2Q12-25
W68-X2Q12-30
W68-X2Q13-15
W68-X2Q110-10
W68-X2Q110-20
W69-X2Q12-5
W69-X2Q12-10
W69-X2Q12-15
W69-X2Q12-20
W69-X2Q12-25
W69-X2Q12-30
W69-X2Q110-20
W69-X2Q110-30
Authorized distributors are more likely to stock the following items.
4
Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
W91- X112- 20
Typical Part No. >
1. Circuit Breaker Mounting:
W = #6-32 mounting threads.
M = M3.0 x 0.5 mounting threads.
2. Number of Poles:
91 = Single pole 92 = Two pole 93 = Three pole 94 = Four pole
3. Circuit Function: (Only X is VDE approved)
A = Series trip with auxiliary switch (.093” QC)
X = Series trip
D = Series trip with auxiliary relay trip pole (requires extra pole package, 3 pole max., not UL)
4. Actuator:
One actuator per pole:
1 = Black toggle 2 = White toggle
5. Maximum Line Voltage: (See Table 1 for current ranges)
UL/CSA 1 = 277VAC, 50/60 Hz.
TYPES 2 = 277/480VAC, 50/60 Hz. [20A Max.]
5 = 65VDC
7 = AC/DC 277VAC, 50/60 Hz. or 65VDC
(Time delay curve 34 must be specified.)
8 = AC/DC 120VAC, 120/240VAC, 48VDC
(Agency Approval M [UL1500] and time delay curve 34 must be specified.)
VDE 1 = 250VAC, 415/240VAC
TYPES 5 = 65VDC
7 = AC/DC 250VAC, 415/240VAC, 65VDC
(Time delay curve 34 must be specified.)
6. Time Delay Curve:
0 = Instantaneous 10 = AC high inrush motor start / long delay
2 = Standard delay 12 = AC high inrush version of #2
3 = Short delay 13 = AC high inrush version of #3
53 = DC high inrush 34 = Combination AC/DC standard delay
Notes: Curves may be specified with increased pulse tolerance for 1/2 cycle by adding "P" after curve.
See delay curve section for availability and details.
7. Amp Rating:
0.20 0.75 2.0 3.5 6.0 8.0 11.0 20.0 35.0 50.0
0.25 1.0 2.5 4.0 7.0 9.0 12.0 25.0 40.0 Consult factory for other values
0.50 1.5 3.0 5.0 7.5 10.0 15.0 30.0 45.0
8. Agency Approval:
Blank = UL1077/CSA approved breaker
V = VDE approved breaker without auxiliary switch
M = UL1077/UL1500 ignition protected breaker
W9 Series
W91-X112-1
W91-X112-2
W91-X112-3
W91-X112-5
W91-X112-7
W91-X112-10
W91-X112-15
W91-X112-20
W91-X112-40
W91-X112-50
W91-X113-5
W91-X113-10
W91-X113-15
W91-X150-5
W91-X152-10
W91-X152-15
W91-X152-20
W91-X152-30
W91-X152-40
W91-X152-50
W91-X1110-20
W92-X112-1
W92-X112-2
W92-X112-3
W92-X112-5
W92-X112-7
W92-X112-10
W92-X112-15
W92-X112-20
W92-X112-25
W92-X112-30
W92-X112-40
W92-X112-50
W92-X113-15
W92-X113-20
W92-X1110-20
W92-X1110-30
W93-X112-5
W93-X112-10
W93-X112-15
W93-X112-20
W93-X112-25
W93-X112-30
W93-X112-40
W93-X112-50
W93-X1110-20
W93-X1110-30
Authorized distributors are more likely to stock the following items.
Ordering Information
5
Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
1.520
(38.61)
.235
(5.97)
2.043
(51.89) 1.640
(41.66) .245
(6.22)
.66
(16.8)
ON
OFF
2
3
A
B
LINE
LOAD
2.000
(50.80)
6.32 TH'D. .14 (3.56) DP. TYP.
M3 X 0.5 OPTIONAL
1.22
(31.00)
1.05
(26.67)
1.660
(42.16)
.750
(19.05)
Ø .590
(15.00)
Note: Multi-pole models furnished with separate handle tie hardware.
W6 Series
Outline Dimensions - Toggle Actuator Models
W6 Series – One Actuator Per Pole
1 Pole 2 Pole 3 Pole 4 Pole
2.250
(57.15)
.750
(19.05)
1.660
(42.16)
Ø .625 +.010
-.000
(15.88 +0.25)
-0.00
1 PER POLE
Ø .156
(3.96) [2 PLACES PER POLE]
1.048
(26.62)
Notes:
1. Terminal protrusion dimensions are
referenced from back of mounting panel.
2. Main terminals are male quick connect
type .250 (6.35) wide x .031 (.79) thick x
.377 (9.58) long. Optional 8-32 x .250
(6.35) or 10-32 x .250 (6.35) screw type.
3. Panel mounting cutout detail mtg. detail
tol.: ± .005 (.13) unless noted. Add
additional cutouts to correspond to
number of poles. Outline drawing
tolerance ± .015 (.38) unless noted.
Panel Mounting Cutout
1.058
(26.97)
2.380
(60.45)
LINE
LOAD
A
B
LINE
LOAD
1.520
(38.61)
.235
(5.97)
2.032
(51.61)
A
B
A
B
LINE
LOAD
LINE
LOAD
C
NO
NC
.416
(10.56)
.827
(21.00)
UL/CSA Models
W/Screw Terminals
UL/CSA/VDE Models
W/Aux. Switch
3.000
(76.20)
VDE Models
W/Screw Terminals
2.000
(50.80)
6.32 TH'D. .14 (3.56) DP. TYP.
M3 X 0.5 OPTIONAL
1.22
(31.00)
1.05
(26.67)
1.660
(42.16)
.750
(19.05)
Ø .590
(15.00)
Note: 4-pole models furnished with separate
handle tie hardware.
W6 Series – One Actuator Per Unit
1 Pole 2 Pole 3 Pole 4 Pole
2.250
(57.15)
3.000
(76.20)
UL/CSA Models
W/Terminals Bent 30°
480V Model with Barriers
2.250
(57.15)
2.778
(70.56)
.269
(6.83)
.266
(6.76)
2.530
(64.26)
Note: 3-pole model shown.
Model with Aux. Relay Trip Pole
Note: W68 -D model shown. Note that the
auxiliary relay trip pole is on the right.
#10-32 screw terminals must be
specified with this option; however,
the terminals on the relay trip pole
are 0.250” quick connects.
The relay pole is self-opening, so the
trip current can remain energized
indefinitely.
Termination Options
6
Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
Outline Dimensions - Optional Toggle Guards
.78
(19.8)
.20
(5.08)
.44
(11.18)
.2 x
R1.0
(25.4)
.17 REF.
(4.32)
6 x .16 DIA.
(4.06)
.75
(19.05)
.75
(19.05)
1.093
(27.76)
2.185 INSIDE
(55.50)
4 x .16 DIA.
(4.06)
.75
(19.05)
.313
(7.95)
.313
(7.95)
1.375 INSIDE
(34.92)
.625 INSIDE
(15.88)
.47
(11.94)
.625
(15.88)
2 x .16 DIA.
(4.06)
.17
(4.32)
1.66
(42.16)
2.00
(50.8)
2 x
.27 DIA.
(6.86)
.95
(24.1)
.53
(13.46)
.08
(2.03)
.03
(.76)
W6 Series
3.000
(76.20)
2.250
(57.15)
1
.500
(38.10)
2 POLE
.375
(9.53) .750
(19.05) .750
(19.05)
.750
(19.05)
3
POLE
4
POLE
ON
OFF
.750
(19.05)
.375
(9.53)
2.000
(50.80)
.388
(9.86)
2.600
(66.04)
TAPPED FOR #6-32
M3 X 0.5 OPTIONAL
Outline Dimensions - Rocker Actuator Models
.750
(19.05) .750
(19.05)
.750
(19.05)
.375
(9.53)
.205
(5.21)
1.250
(31.75)
1.660
(42.16)
Ø .156
(3.96)
TYP. 2
PER POLE
.750
(19.05) 1.500
(38.10) 2.250
(57.15) 3.000
(76.20)
1 POLE
2 POLE
3 POLE
4 POLE
Panel Mounting Cutout
1Pole
(Shown with optional “ON”
and “OFF” graphics)
2, 3 & 4 Pole, One Actuator Per Pole
LOAD
LINE
.240
(6.10)
1.520
(38.61)
2.435
(61.85)
1.769
(44.93)
.774
(19.65)
.392
(9.96) .180
(4.57)
1.30
(33.0)
1.660
(42.16)
A
D
W6 Series
VDE Rocker Marking
I
O
Notes:
1. Outline drawing tolerance ± .015 (.38) unless
noted. Dimensions in brackets ( ) are in
millimeters.
2. Mounting Detail Tol.: ± .005 (.13) unless noted
Optional toggle guards may be ordered separately for use on W6 toggle actuator models. These guards help to prevent accidental operation and allow the breaker to be
locked in the “off” position.
84-004
(For 1 Pole
Breaker)
84-005
(For 2 Pole
Breaker)
84-006
(For 3 Pole
Breaker)
1.500
(38.10)
.375
(9.53) .750
(19.05)
.388
(9.86)
TAPPED FOR #6-32
M3 X 0.5 OPTIONAL
2.250
(57.15)
.375
(9.53)
.750
(19.05)
.750
(19.05)
3.000
(76.20)
.375
(9.53) .750
(19.05) .750
(19.05)
.750
(19.05)
1.660
(42.16)
1.660
(42.16)
2.000
(50.80)
2.600
(66.04)
2, 3 & 4 Pole, One Actuator Per Unit
84-004 toggle guard shown
with W67 series circuit
breaker mounted in a panel.
7
Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
.750
(19.05)
.750
(19.05)
.750
(19.05)
.385
(9.78)
1.450
(36.83)
.732
(18.59)
2X Ø .156
(3.96)
PER POLE
.76
(19.3)
1
.52
(38.6)
2.28
(57.9)
3.04
(77.2)
1 POLE
2 POLE
3 POLE
4 POLE
.907
(23.04)
2.065
(52.45)
Notes:
1. Terminal protrusion
dimensions are referenced
from the back of the
mounting panel.
2. Mounting detail tolerance
±.005 (13) unless noted.
3. Outline drawing tolerance ±
.015 (.38) unless noted.
Dimensions in brackets ( )
are in millimeters.
ON
29°
30°
OFF
.74
(18.8)
2.10
(53.34)
1.940
(49.28)
.281
(7.14)
1
.845
(46.86) .313
(7.95)
.14
(3.56)
2.50
(64.00)
LINE
LOAD
#10-32
STUD
TERMINATION
.375
(9.52) 1.15
(29.21)
.060
(1.52)
Outline Dimensions
OFF OFF
ON ON
.750
(19.05)
OFF OFF
ON ON
OFF OFF
ON ON
OFF OFF
ON ON
OFF OFF
ON ON
.750
(19.05)
.750
(19.05)
.750
(19.05)
.375
(9.53)
2 POLE
1. 5 0 0
(38.10) 2.250
(57.15)
3 POLE
4 POLE
3.000
(76.20)
.218
(5.54)
2.065
(52.45)
.398
(10.11)
1. 4 3 8
(36.53)
2.50
(63.5)
TAPPED #6-32 X .16 (4.06)
DEEP
M3 X 0.5 OPTIONAL
.375
(9.53)
1 POLE
.060
(1.52)
1.940
(49.28)
.281
(7.14) 2.46
(62.48)
2.50
(64.00)
LINE
LOAD
C
NO
N
C
'A' STYLE
Series Trip Model Series Trip Model
Series Trip Model
With Common Enclosed Auxiliary Switch
Panel Mounting Cutout Detail
W9 Series
Note:
1. Top mounted plate
(shown with broken
line) is present only on
UL1500 models.
© 2010 by Tyco Electronics Corporation. All Rights Reserved.
P&B, Potter & Brumfield, TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors.
Disclaimer:
While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this
document, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any
guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any
time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied
warranties of merchantability or fitness for a particular purpose. Tyco Electronics‘ only obligations are those stated in Tyco Electronics’ Standard Terms and
Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including,
but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgment to evaluate the suitability of a product for a certain
purpose and test each product for its intended application.
In case of any potential ambiguities or questions, please don’t hesitate to contact us for clarification.