Data sheet
PRO MAX 120W 24V 5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Creation date February 17, 2021 9:18:08 PM CET
Catalogue status 12.02.2021 / We reserve the right to make technical changes. 3
General data
AC failure bridging time @ Inom min. 20 ms Current limiting > 120% IN
Degree of efficiency 89% Derating > 60°C / 75% @ 70°C
Earth leakage current, max. 3.5 mA Housing version Metal, corrosion resistant
MTBF
>500.000h (25°C, IEC
61709 (SN29500))
Mounting position, installation notice Horizontal on TS35
mounting rail. 50 mm of
clearance at top &
bottom for air circ. Can
mount side by side with no
space in between.
Operating temperature -25 °C...70 °C Power factor (approx.) > 0.90 @ 230 V AC
Protection against reverse voltages from
the load 30…35 V DC
Short-circuit protection
Yes
Status indication LED red/green and relay
(≥21.6 V DC LED green,
relay on/ ≤20.6 LED red,
relay off)
Surge voltage category
III
EMC / shock / vibration
Interference immunity test acc. to EN 55024, EN 55032,
IEC61000-3-2,-3,
IEC61000-4-2,-3,-4,-5,-6,-8,-11
Noise emission in accordance with
EN55032
Class B
Shock resistance IEC 60068-2-27 30 g in all directions Vibration resistance IEC 60068-2-6 2.3 g
Insulation coordination
Humidity at operating temperature 5...95 %, no condensation Insulation voltage, input/output 4 kV
Pollution severity 2 Protection class I, with PE connection
Surge voltage category III
Electrical safety (applied standards)
Electrical machine equipment
Acc. to EN60204
For use with electronic equipment Acc. to EN50178 /
VDE0160
Protection against dangerous shock
currents Acc. to VDE0106-101
Protective separation / protection
against electrical shock
VDE0100-410 / acc. to
DIN57100-410
Safety transformers for switch-mode
power supplies
According to EN
61558-2-16
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max. 10
Conductor cross-section, AWG/kcmil ,
min. 26
Conductor cross-section, flexible , min. 0.22 mm² Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.18 mm² Connection system Screw connection
Wire connection cross section, flexible
(input), max. 4 mm²
Connection data (output)
Conductor cross-section, AWG/kcmil ,
max. 12
Conductor cross-section, AWG/kcmil ,
min. 26
Conductor cross-section, flexible , max. 4 mm² Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 6 mm² Conductor cross-section, rigid , min. 0.5 mm²
Connection system Screw connection Number of terminals 8 (++,---,11,13,14)