ET 200eco Distributed I/O Device ___________________ Preface 1 ___________________ Product overview SIMATIC Distributed I/O ET 200eco Distributed I/O Device Operating Instructions 2 ___________________ Installing 3 ___________________ Connecting 4 ___________________ Configuration ___________________ 5 Commissioning Alarm, error and system ___________________ 6 messages ___________________ 7 General specifications ___________________ 8 Technical specifications ___________________ A Appendix 08/2014 A5E00158716-AD Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NURNBERG GERMANY A5E00158716-AD 09/2014 Subject to change Copyright (c) Siemens AG 2002 - 2014. All rights reserved Preface Purpose of this manual The information in this manual enables you to run the ET 200eco distributed I/O device on PROFIBUS DP in DP slave mode. Basic knowledge requirements This manual presumes a general knowledge in the field of automation engineering. The manual describes the components based on the data valid at the time of its release. SIEMENS reserves the right of including a product information for each new component, and for each component of a later version. Scope of this manual This manual applies to the ET 200eco distributed I/O device. Conventions Note A note contains important information about the product described in the documentation, about the handling of the product, and about the section in this documentation demanding your particular attention. Position in the information landscape In addition to this manual you require the manual of the DP master system of your configuration. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 3 Preface Guide This manual describes the hardware of the ET 200eco distributed I/O device. It consists of instructive sections and reference sections (specifications). Topics covered in this manual: Installation and wiring Commissioning and diagnostics Components Article numbers Important terms are explained in the glossary. The index helps you to quickly find all texts relevant to your keyword. Recycling and disposal The ET 200eco distributed I/O device can be recycled due to its low-pollutant equipment. For environmentally sustainable recycling and disposal of your old device, contact a certificated disposal service for electronic scrap. Additional support Please contact your local Siemens representative if you have any questions about the products described in this manual. You will find your contact person on the Internet (http://www.automation.siemens.com/partner/). A guide to the technical documentation for the various SIMATIC products and systems is available on the Internet (http://www.siemens.com/automation/support-request). The online catalog and online ordering system are available on the Internet (http://mall.industry.siemens.com). Training center Siemens offers corresponding courses to get you started with your ET 200eco distributed I/O device and the SIMATIC S7 automation system. Please contact your local training center or the central training center in Nuremberg, D-90327 Germany. Additional information about Siemens Technical Support is available on the Internet (http://www.sitrain.com/index_en.html). Technical Support You can reach Technical Support for all Industry Automation products via the support request Web form on the Internet (http://www.siemens.com/automation/support-request). Additional information about Siemens Technical Support is available on the Internet (http://www.siemens.com/automation/service). ET 200eco Distributed I/O Device 4 Operating Instructions, 08/2014, A5E00158716-AD Preface Service & Support on the Internet In addition to our documentation, we offer a comprehensive knowledge base on the Internet (http://www.siemens.de/automation/csi_en_WW). There, you will find the following information: Our newsletter, providing the latest information on your products The right documents for you, using the Service & Support search engine Worldwide forum in which users and experts exchange ideas Your local Automation & Drives partner in our partner database Information about on-site services, repairs, spare parts and more. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens' products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. You can find more information about industrial security on the Internet (http://www.siemens.com/industrialsecurity). To stay informed about product updates as they occur, sign up for a product-specific newsletter. You can find more information on the Internet (http://support.automation.siemens.com). ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 5 Table of contents Preface ...................................................................................................................................................... 3 1 2 3 Product overview ....................................................................................................................................... 8 1.1 Distributed I/O systems - overview .......................................................................................... 8 1.2 ET 200eco Distributed I/O Device.......................................................................................... 10 Installing .................................................................................................................................................. 12 2.1 Mounting position, mounting dimensions ............................................................................... 12 2.2 Installing the I/O module ........................................................................................................ 13 2.3 Installing the terminal block.................................................................................................... 15 2.4 Replacing labels ..................................................................................................................... 16 2.5 Removing the ET 200eco ...................................................................................................... 17 2.6 Setting the PROFIBUS address............................................................................................. 17 Connecting .............................................................................................................................................. 20 3.1 General operating rules and regulations ................................................................................ 20 3.2 Operating the ET 200eco on grounded mains ....................................................................... 21 3.3 Electrical configuration of ET 200eco .................................................................................... 23 3.4 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 3.4.7 Wiring the ET 200eco ............................................................................................................ 27 Wiring procedures (steps) ...................................................................................................... 27 Connecting ET 200eco to protective earth (PE) .................................................................... 27 Wiring I/O modules with M12 connectors .............................................................................. 28 Wiring I/O modules with Y-connector and Y-cable ................................................................ 33 Wiring the ECOFAST terminal block ..................................................................................... 37 Wiring the M12, 7/8" terminal block ....................................................................................... 41 Looping PROFIBUS DP and the supply voltage.................................................................... 45 4 Configuration ........................................................................................................................................... 47 5 Commissioning ........................................................................................................................................ 48 5.1 6 Commissioning ET 200eco .................................................................................................... 48 Alarm, error and system messages ......................................................................................................... 50 6.1 Diagnostics by LED Display ................................................................................................... 50 6.2 6.2.1 6.2.2 6.2.3 6.2.4 6.2.5 6.2.6 6.2.7 ET 200eco diagnostics ........................................................................................................... 53 Reading diagnostics data....................................................................................................... 53 Example: Reading slave diagnostics data using SFC 13 "DP NRM_DG" ............................. 54 Configuration of ET 200eco slave diagnostics....................................................................... 55 Station states 1 to 3 ............................................................................................................... 56 Master PROFIBUS address ................................................................................................... 57 Manufacturer ID ..................................................................................................................... 58 Device-specific diagnostics .................................................................................................... 59 ET 200eco Distributed I/O Device 6 Operating Instructions, 08/2014, A5E00158716-AD Table of contents 7 8 A General specifications ............................................................................................................................. 60 7.1 Standards and Approvals .......................................................................................................60 7.2 EMC compatibility, shipping and storage conditions ..............................................................61 7.3 Mechanical and climatic environmental conditions.................................................................63 7.4 Specifications for insulation tests, protection class, degree of protection, and rated voltage ....................................................................................................................................65 Technical specifications ........................................................................................................................... 67 8.1 Overview .................................................................................................................................67 8.2 ECOFAST terminal block (6ES7194-3AA00-0AA0) ...............................................................67 8.3 M12, 7/8" terminal block (6ES7194-3AA00-0BA0) .................................................................69 8.4 I/O module 8 DI (6ES7141-3BF00-0XA0) ..............................................................................71 8.5 I/O module 16 DI (6ES7141-3BH00-0XA0) ............................................................................75 8.6 I/O module 8 DO 2A (6ES7142-3BF00-0XA0) .......................................................................79 8.7 I/O module 16 DO 0.5A (6ES7142-3BH00-0XA0) ..................................................................83 8.8 I/O module 8 DI / 8 DO 2A (6ES7143-3BH00-0XA0) .............................................................87 8.9 I/O module 8 DI / 8 DO 1.3A (6ES7143-3BH10-0XA0) ..........................................................91 Appendix.................................................................................................................................................. 95 A.1 Article numbers .......................................................................................................................95 A.2 Dimensional drawings ...........................................................................................................102 A.3 I/O address space .................................................................................................................104 Glossary ................................................................................................................................................ 110 Index ...................................................................................................................................................... 112 ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 7 1 Product overview 1.1 Distributed I/O systems - overview Field of application A plant configuration quite often features a process I/O configuration in a central automation system. The wiring of process I/O components installed at a grated distance away from an automation system may soon may soon become highly complex and susceptible for electromagnetic interference. Distributed I/O systems are the perfect solution for such configurations. The controller CPU is located in a central rack. The I/O systems (inputs and outputs) are operated locally in a distributed configuration. The high data transmission rates of the high-performance PROFIBUS DP ensures smooth communication between the PLC and its I/O systems. PROFIBUS DP PROFIBUS DP is an open bus system, based on IEC 61784-1 with the "DP" transmission protocol (DP stands for distributed peripherals). Physically, PROFIBUS DP is either an electrical network based on a shielded two-wire line, or an optical network based on a fiber-optic cable. The "DP" transmission protocol facilitates high-speed cyclic data exchange between the PLC and its distributed I/O systems. DP masters and DP slaves The DP master links the controller CPU with the distributed I/O systems. It exchanges data with its distributed I/O systems via PROFIBUS DP, and monitors the PROFIBUS DP. The distributed I/O systems (= DP slaves) prepare the data of the sensors and actuator for the transfer to the CPU via PROFIBUS DP. ET 200eco Distributed I/O Device 8 Operating Instructions, 08/2014, A5E00158716-AD Product overview 1.1 Distributed I/O systems - overview Connectable devices PROFIBUS DP supports the operation of a wide range of devices in DP master or DP slave mode, provided their properties are compliant with IEC 61784-1. This includes devices of the following product families: SIMATIC S5 SIMATIC S7/M7/C7 SIMATIC PG/PC SIMATIC HMIs (operating and monitoring devices OP, OS, and TD) Devices from other manufacturers Configuration of a PROFIBUS DP network The figure below illustrates the typical configuration of a PROFIBUS DP network. The DP masters are integrated into the relevant device, for example, the S7-400 or S7-300 PLC is equipped with a PROFIBUS DP interface. The DP slaves formed by the distributed I/O systems are connected to the DP masters via PROFIBUS DP. Figure 1-1 Typical configuration of a PROFIBUS DP network ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 9 Product overview 1.2 ET 200eco Distributed I/O Device 1.2 ET 200eco Distributed I/O Device Definition The ET 200eco distributed I/O device is a compact DP slave with degree of protection IP 65, IP 66 or IP 67. Field of application The fields of application of the ET 200eco are derived from its special properties. A robust design and degree of protection IP65, IP66 or IP67 make the ET 200eco distributed I/O device particularly suitable for use in harsh industrial environments. The compact design of ET 200eco is particularly favorable for applications in confined spaces. The easy handling of ET 200eco ensures quick commissioning and maintenance. View The ET 200eco consists of an I/O module and a terminal block. These are available in various versions. Figure 1-2 View of the ET 200eco Distributed I/O Device ET 200eco Distributed I/O Device 10 Operating Instructions, 08/2014, A5E00158716-AD Product overview 1.2 ET 200eco Distributed I/O Device ET 200eco components The table below provides an overview of the most important components of the ET 200eco distributed I/O system: Table 1- 1 ET 200eco components Component Function I/O module You connect the sensors and actuators of your system to the I/O module. The I/O module is available in the following versions: Terminal block * 8 DI * 16 DI * 8 DO 2A * 16 DO 0.5A * 8 DI / 8 DO 2A * 8 DI / 8 DO 1.3A Diagram You connect the power supply for the ET 200eco and PROFIBUS DP to the terminal block. The terminal block is available in the following versions: * ECOFAST * M12, 7/8" DP master The ET 200eco supports communication with all DP masters that conform to the IEC 61784-1 standard. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 11 2 Installing 2.1 Mounting position, mounting dimensions Mounting position An ET 200eco can be mounted in any position. Mounting and clearance dimensions The following table shows the mounting and clearance dimensions. Table 2- 1 Mounting dimensions Dimensions Mounting width * 60 mm Mounting height * 210 mm Mounting depth * with ECOFAST terminal block: 60 mm (without connector) * with terminal block M12, 7/8": 54 mm (without connector) ET 200eco Distributed I/O Device 12 Operating Instructions, 08/2014, A5E00158716-AD Installing 2.2 Installing the I/O module 2.2 Installing the I/O module Simple installation The ET 200eco Distributed I/O Device is designed for easy installation. Properties The I/O module should be mounted on a solid surface. The I/O module can be prewired (without installed terminal block). Requirements The following table shows the screws that are permitted for the installation of the I/O modules: Table 2- 2 Screw types Screw type Description Cylinder head screw M5 according to ISO 1207/ISO 1580 (DIN 84/DIN 85) Minimum screw length: 20 mm. M5 hex socket cylinder head screw according to DIN 912 You also need a set of DIN 125 washers. Tools required Medium-sized recessed head screwdriver or 8 mm socket wrench. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 13 Installing 2.2 Installing the I/O module Procedure Screw-mount the I/O module on a plane surface. Screw the I/O module onto the panel at both mounting fixtures at the front top and bottom. Tightening torque: 3 Nm. Figure 2-1 Mounting the I/O module onto the panel ET 200eco Distributed I/O Device 14 Operating Instructions, 08/2014, A5E00158716-AD Installing 2.3 Installing the terminal block 2.3 Installing the terminal block Properties The terminal block is used to connect the ET 200eco with the PROFIBUS DP and supplies the I/O module with voltage. Requirements The I/O module is installed. Tools required Recessed head screwdriver, medium size Installing the terminal block 1. Plug the terminal block into the I/O module. 2. Screw the terminal block onto the I/O module (torque = 1 Nm to 1.3 Nm). Tighten the screws in the terminal block working crosswise. Figure 2-2 Plug the terminal block into the I/O module, then screw-tighten it Note The degree of protection IP 65, IP 66 or IP 67 is only ensured if the terminal block is screwed firmly onto the I/O module! ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 15 Installing 2.4 Replacing labels 2.4 Replacing labels Properties You can label each channel of the I/O module and the terminal block. The labels are already installed in the I/O module in the delivery state: 8 labels on the I/O module 1 label on the terminal block Requirements You can order replacement labels. The article numbers are listed in the Appendix (Page 95). Tools required 2.5 to 4 mm screwdriver Replacing labels 1. Push the screwdriver into the small opening of the label at an angle, then lever it out. Figure 2-3 Removing labels 2. Push the label into the module using your fingers. ET 200eco Distributed I/O Device 16 Operating Instructions, 08/2014, A5E00158716-AD Installing 2.5 Removing the ET 200eco 2.5 Removing the ET 200eco Procedure The ET 200eco is wired and in operation. To remove the ET 200eco distributed I/O system, follow these steps: 1. Shut off the supply voltage to ET 200eco. 2. Disconnect the wiring from the terminal module. 3. Loosen the four fixing screws on the terminal block. 4. Disconnect the terminal block from the I/O module. 5. Disconnect the wiring from the I/O module. 6. Disconnect the fixing screws from the I/O module. Note When replacing the I/O module, refer to the chapter Looping of PROFIBUS DP and supply voltage (Page 45). 2.6 Setting the PROFIBUS address Properties The PROFIBUS address specifies the address of the ET 200eco Distributed I/O Device on the PROFIBUS DP. The PROFIBUS DP address of the ET 200eco is set at the terminal block. Requirements Each address can be assigned only once on PROFIBUS DP. The set PROFIBUS address must match the PROFIBUS address set for this ET 200eco in your configuration software. A change of the PROFIBUS DP address is only accepted at the ET 200eco after POWER ON. Tools required 14 mm socket wrench 2.5 mm screwdriver ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 17 Installing 2.6 Setting the PROFIBUS address Setting the PROFIBUS DP address with M12, 7/8" terminal block Permissible PROFIBUS DP addresses: 1 to 99. 1. Remove the two sealing caps from the rotary switches (use a 14 mm wrench). 2. Set the required PROFIBUS addresses on the rotary switches using a screwdriver. - Bottom rotary switch: Units digit - Top rotary switch: Tens place 3. Reinstall both caps on the rotary switches (torque: 0.5 Nm to 0.8 Nm). Rotary switch for setting the PROFIBUS address Figure 2-4 Setting the PROFIBUS DP address with M12, 7/8" terminal block Example of an address setting: PROFIBUS address 92 Position 9 Position 2 ET 200eco Distributed I/O Device 18 Operating Instructions, 08/2014, A5E00158716-AD Installing 2.6 Setting the PROFIBUS address Setting the PROFIBUS DP address at an ECOFAST terminal block The permissible range of PROFIBUS DP address is 1 to 99. If you set a higher address, the red bus error LED of the I/O module will indicate a fault. 1. Loosen the screws of the configuration connector with the ECOFAST terminal block and strip it off the connector. Figure 2-5 Loosen the screws of the configuration connector 2. Remove the cap from the configuration connector. Figure 2-6 Removing the cap 3. Set the PROFIBUS address at the DIL switches. Figure 2-7 Setting the PROFIBUS address at the configuration connector, sample address: 92 4. Screw on the cap again. 5. Place the configuration connector onto the terminal block and then secure it with the screws. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 19 3 Connecting 3.1 General operating rules and regulations Introduction Special rules and regulations have to be followed when operating an ET 200eco Distributed I/O Device as part of a plant or system, depending on the field of application. This section provides an overview of the most important rules you have to observe when integrating the ET 200eco Distributed I/O Device in a plant or system. EMERGENCY OFF equipment EMERGENCY OFF equipment to IEC 204 (corresponds to DIN VDE 113) must remain effective in all operating modes of the plant or system. Startup of the system after certain events The table below identifies situations you must pay attention to when the system starts up after the occurrence of certain events. If ... then ... Startup follows a power dip / failure Startup of the ET 200eco follows an interruption of bus communication Dangerous operating states must be avoided at all times. If necessary, force an "EMERGENCY OFF"! Startup after releasing the EMERGENCY OFF equipment Any uncontrolled or undefined startup must be avoided. 24 V DC supply The table shows what you have to observe for the 24 V DC supply. At ... Requirements ... Buildings external lightning protection take lightning protection measures 24 V DC power supply cables, signal cables internal lightning protection (for example, lightning protection elements) 24 V DC supply safe (electrical) isolation of the extra-low voltage Looping the power supply Voltage drop with looping (see chapter Looping of PROFIBUS DP and supply voltage (Page 45)) ET 200eco Distributed I/O Device 20 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.2 Operating the ET 200eco on grounded mains Protection against external electrical interference The table below shows what to observe in order to protect the system against electrical interference or faults. 3.2 At ... ensure that ... all plants or systems in which the ET 200eco is integrated the plant or system is connected to a protective conductor in order to discharge electromagnetic interference to ground. supply, signal, and bus lines the wiring arrangement and installation is correct. signal and bus lines a wire break or conductor break does not result in undefined states of the plant or system. Operating the ET 200eco on grounded mains Introduction This section provides information about the overall configuration of an ET 200eco Distributed I/O Device on grounded mains (TN-S network). The specific subjects discussed are: Disconnecting devices, short-circuit protection and overload protection to DIN VDE 0100 and DIN EN 60204-1. Definition: Grounded mains The neutral conductor of a TN-S system is always bonded to ground. A simple short-circuit to ground of a live conductor, or of a grounded component of the plant will trip the disconnecting devices. Components and protective measures Various components and protective measures are stipulated for plant installation. The nature of the components and of the degree to which protective measures are binding depends on the DIN VDE regulation applicable to your plant configuration. The next table refers to the diagram below. Table 3- 1 Comparison of the protective measures Compare ... Reference to the diagram DIN VDE 0100 DIN EN 60204 Disconnecting device for controllers, signal sensors and actuators ... Part 460: ... Part 1: Main switch Disconnect switch Short-circuit and overload protection ... Part 725: ... Part 1: Single-pole protec- with grounded secondary power tion of circuits circuit: single-pole protection ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 21 Connecting 3.2 Operating the ET 200eco on grounded mains Safety isolation Safety isolation is required for: Modules which must be supplied with 60 V DC or 25 V AC 24 V DC load circuits Installing an ET 200eco with grounded reference potential In an ET 200eco configuration with grounded reference potential, any interference currents will be discharged to protective earth. The connections must be interconnected either externally or in the connector (see the figure below): Connection between 1M and PE). Installing an ET 200eco with ungrounded reference potential In an ET 200eco configuration with ungrounded reference potential, any disturbance will be discharged to protective earth via an internal RC circuit (see the figure below: No connection between 1M and PE). Isolation monitoring Isolation monitoring must be provided if: The ET 200eco is operated with ungrounded potential A repetitive error is liable to cause dangerous plant states ET 200eco Distributed I/O Device 22 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.3 Electrical configuration of ET 200eco ET 200eco in the overall configuration The figure below shows the overall configuration of the ET 200eco Distributed I/O Device (load voltage supply and grounding concept) supplied with power from TN-S mains. Disconnecting device for controllers, signal sensors and actuators Short-circuit and overload protection Figure 3-1 3.3 Operating the ET 200eco on grounded reference potential Electrical configuration of ET 200eco Electrical isolation Electrically isolated components in the ET 200eco configuration: 1L+ (electronics / sensor supply): Electrical isolation from PROFIBUS DP and 2L+ (load voltage supply), except at I/O module 8 DI / 8DO 2A. 2L+ (load voltage supply): Electrical isolation from all other circuitry, except for I/O module 8 DI / 8DO 2A. 1M and 2M of I/O module 8 DI / 8DO 2A are internally interconnected. PROFIBUS DP interface: Electrical isolation from all other circuitry. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 23 Connecting 3.3 Electrical configuration of ET 200eco ET 200eco configuration The diagrams below show the potentials of an ET 200eco configuration with M12, 7/8" terminal block and with ECOFAST terminal block. Figure 3-2 Potentials of an ET 200eco configuration with M12, 7/8" terminal block ET 200eco Distributed I/O Device 24 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.3 Electrical configuration of ET 200eco Figure 3-3 Potentials of an ET 200eco configuration with ECOFAST terminal block Note * The ground potentials of the 1L+ electronics / sensor supply and 2L+ load voltage supply of the ET 200eco Distributed I/O Device with I/O module 8DI / 8DO 2A are interconnected. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 25 Connecting 3.3 Electrical configuration of ET 200eco Note Applicable to ET 200eco with terminal block: - Sensors are supplied with power from the 1L+ electronics / sensor supply - The outputs are supplied with power from the 2L+ load voltage supply. Protective measures against the destruction of components In order to prevent the destruction of ET 200eco or of any of its components, you should always protect the feed lines of the electronics / sensor supply and of the load voltage supply by means of over-current release: Protection of the electronics / sensor/ supply 1L+: 24 V DC / 10 A: tripping characteristics (type) B or C Protection of load voltage 2L+: 24 V DC / 16 A: tripping characteristics (type) B or C ET 200eco Distributed I/O Device 26 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco 3.4 Wiring the ET 200eco 3.4.1 Wiring procedures (steps) Wiring procedures You wire an ET 200eco Distributed I/O Device in several steps. To wire the ET 200eco Distributed I/O System, follow these steps: 1. Connect the ET 200eco to protective earth. 2. Wire the I/O module. 3. Wire the terminal block. 3.4.2 Connecting ET 200eco to protective earth (PE) Properties Always connect the ET 200eco to protective earth. The I/O module is equipped with a grounding screw. The module also requires this connection to protective earth in order to discharge any interference currents to ground, and for EMC compatibility. Requirements Always make sure you have a low-impedance connection to protective earth. Tools required Stripping tool Crimp tool Screwdriver Accessories required M5 x 10 fixing screw and washers Grounding cable (copper braid), conductor cross-section min. 4 mm2 Cable lugs ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 27 Connecting 3.4 Wiring the ET 200eco Connecting ET 200eco to protective earth 1. Strip the grounding conductor and crimp on the cable lug. 2. Screw the cable lug onto the I/O module (M5 fixing screw). The torque is 3 Nm. Figure 3-4 3.4.3 Connecting the I/O module to protective earth Wiring I/O modules with M12 connectors Properties Connect the digital I/O to the 5-pin M12 circular socket connectors on the front panel of the I/O module. You may also use 5-pin M12 circular connectors or Y connectors. The article numbers are listed in the Appendix (Page 95). Requirements Always wire the I/O module after you switched off the power supply or removed the terminal block. Tools required Stripping tool and screwdriver for wiring the M12 circular connector, if you do not use patch cables. ET 200eco Distributed I/O Device 28 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco Accessories required Pre-assembled cable with 5-pin M12 circular connector or 3, 4 or 5-wire Cu cable, flexible (conductor cross-section must be 0.75 mm2), and 5-pin M12 circular connector (see tables below) M12 sealing caps For article numbers, refer to the Appendix (Page 95) Connecting the M12 connector To connect the M12 connector, follow these steps: 1. Plug the connector into the relevant circular socket connector on the I/O block. Make sure the connectors and sockets are properly interlocked (matched joint). 2. Secure the connector by tightening the knurled ring nut. Figure 3-5 Connecting the M12 connector Terminal assignment of the M12 circular connector on I/O module 8 DI Table 3- 2 M12 circular connector on I/O module 8 DI Pin Pin-out X1 to X8 View of the circular connector (wiring side) 1 1 24 V sensor supply 1 (1L+) 2 n.c. 3 Sensor supply ground (1M) 4 Input signal 5 PE supplied internally to the connected sensor by ET 200eco ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 29 Connecting 3.4 Wiring the ET 200eco Terminal assignment of the M12 circular connector on I/O module 16 DI Table 3- 3 M12 circular connector on I/O module 16 DI Pin Pin-out X1 to X8 View of the circular connector (wiring side) 1 24 V sensor supply (1L+) 2 Input signal2 (n + 8) 3 Sensor supply ground (1M) 4 Input signal3 (n) 5 PE 1 1 supplied internally to the connected sensor by ET 200eco 2 In the process image of inputs (PII): Input byte x+1 3 In the process image of inputs (PII): Input byte x M12 circular connector on I/O module 8 DO 2A Table 3- 4 M12 circular connector on I/O module 8 DO 2A Pin Pin-out X1 to X8 View of the circular connector (wiring side) 1 n.c. 2 n.c. 3 Load voltage ground (2M) 4 Output signal 5 PE ET 200eco Distributed I/O Device 30 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco Terminal assignment of the M12 circular connector on I/O module 16 DO 0.5A Table 3- 5 M12 circular connector on I/O module 16 DO 0.5A Pin Pin-out X1 to X8 View of the circular connector (wiring side) 1 n.c. 2 Output signal1 (n + 8) 3 Load voltage ground (2M) 4 Output signal2 (n) 5 PE 1 In the process image of outputs (PIO): Output byte x+1 2 In the process image of outputs (PIO): Output byte x Terminal assignment of the M12 circular connector on I/O module 8 DI / 8 DO 2A Table 3- 6 M12 circular connector on I/O module 8 DI / 8 DO 2A Pin Assignment View of the circular connector (wiring side) 1 24 V sensor supply 1 (1L+) 2 Input signal 3 Sensor / load voltage supply ground 2 (1M/2M) 4 Output signal 5 PE 1 supplied internally to the connected sensor by ET 200eco 2 common ground for sensor and load voltage supply (1M and 2M internally interconnected) ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 31 Connecting 3.4 Wiring the ET 200eco Terminal assignment of the M12 circular connector on I/O module 8 DI / 8 DO 1.3A Table 3- 7 M12 circular connector on I/O module 8 DI / 8 DO 1.3A, pin-out X1, X3, X5, X7 Pin Pin-out X1, X3, X5, X7 View of the circular connector (wiring side) 1 24 V sensor supply (1L+) 2 Input signal2 (n + 1) 3 Sensor supply ground (1M) 4 Input signal2 (n) 5 PE 1 1 supplied internally to the connected sensor by ET 200eco 2 In the process image of inputs (PII): Input byte x Table 3- 8 M12 circular connector on I/O module 8 DI / 8 DO 1.3A, pin-out X2, X4, X6, X8 Pin Pin-out X2, X4, X6, X8 View of the circular connector (wiring side) 1 1 n.c. 2 Output signal1 (n + 1) 3 Load voltage ground (2M) 4 Output signal1 (n) 5 PE In the process image of outputs (PIO): Output byte x Closing unused circular socket connectors Close all unused circular socket connectors using M12 caps to achieve the degree of protection IP 65, IP 66 or IP 67. The article numbers are listed in the Appendix (Page 95). Reference For more information on the input/output byte see the Appendix (Page 104). ET 200eco Distributed I/O Device 32 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco 3.4.4 Wiring I/O modules with Y-connector and Y-cable Introduction Alternatively, you can replace the M12 connector with a Y-connector or Y-cable. The Y-connector or Y-cable allows you to connect two actuators or sensors to the ET 200eco inputs or outputs. The use of a Y-connector or Y-cable is particularly recommended when each socket of the module is occupied by two channels: I/O module 16 DI I/O module 16 DO 0.5A I/O module 8 DI / 8 DO 2A I/O module 8 DI / 8 DO 1.3A The Y-connector or Y-cable distributes the two channels to 2 circular connectors (the tables below show the terminal assignments). Note The Y-connector cannot be used in combination with the M12, 5-pin angular connector, order no. 3RX1668. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 33 Connecting 3.4 Wiring the ET 200eco Connecting Y-connector or Y-cable 1. Plug the Y-connector or Y-cable into the relevant circular socket connector on the I/O module. Make sure the connectors and sockets are properly interlocked (matched joint). 2. Secure the connector by tightening the knurled ring nut. Figure 3-6 Y-connector Figure 3-7 Y-cable Figure 3-8 Wiring the Y-cable ET 200eco Distributed I/O Device 34 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco Terminal assignment of the Y-connector or Y-cable on I/O module 16 DI Table 3- 9 Pin Y-connector or Y-cable on I/O module 16 DI Pin-out circular connectors X1 to X8 A (top) B (bottom) 1 24 V sensor supply 1 (1L+) 2 n.c. 3 Sensor supply ground (1M) 4 Input signal from pin 42 5 PE View Y-connector or Y-cable Input signal from pin 22 1 supplied internally to the connected sensor by ET 200eco 2 specified pins refer to the connection socket on the I/O module Terminal assignment of the Y-connector or Y-cable on I/O module 16 DO 0.5A Table 3- 10 Pin Y-connector or Y-cable on I/O module 16 DO 0.5A Pin-out circular connectors X1 to X8 A (top) 1 B (bottom) 1 n.c. 2 n.c. 3 Load voltage ground (2M) 4 Output signal from pin 41 5 PE View Y-connector or Y-cable Output signal from pin 21 specified pins refer to the connection socket on the I/O module ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 35 Connecting 3.4 Wiring the ET 200eco Terminal assignment of the Y-connector or Y-cable on I/O module 8 DI / 8 DO 2A Table 3- 11 Pin Y-connector or Y-cable on I/O module 8 DI / 8 DO 2A Pin-out circular connectors X1 to X8 A (top) View Y-connector or Y-cable B (bottom) 1 24 V sensor supply 1 (1L+) 2 n.c. 3 Sensor / load voltage supply ground 2 (1M/2M) 4 Output signal at pin 43 5 PE Input signal at pin 23 1 supplied internally to the connected sensor by ET 200eco 2 common ground for sensor supply and load voltage supply (1M and 2M internally interconnected) 3 specified pins refer to the connection socket on the I/O module Terminal assignment of the Y-connector or Y-cable on I/O module 8 DI / 8 DO 1.3A Table 3- 12 Pin Y-connector or Y-cable on I/O module 8 DI / 8 DO 1.3A, pin-out X1, X3, X5, X7 Pin-out circular connectors X1, X3, X5, X7 A (top) View Y-connector or Y-cable B (bottom) 1 24 V sensor supply (1L+) 2 n.c. 3 Sensor supply ground (1M) 4 Input signal from pin 42 5 PE 1 Input signal from pin 22 1 supplied internally to the connected sensor by ET 200eco 2 specified pins refer to the connection socket on the I/O module ET 200eco Distributed I/O Device 36 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco Table 3- 13 Pin Y-connector or Y-cable on I/O module 8 DI / 8 DO 1.3A, pin-out X2, X4, X6, X8 Pin-out circular connectors X2, X4, X6, X8 A (top) 1 B (bottom) 1 n.c. 2 n.c. 3 Load voltage ground (2M) 4 Output signal from pin 41 5 PE View Y-connector or Y-cable Output signal from pin 21 specified pins refer to the connection socket on the I/O module See also Article numbers (Page 95) 3.4.5 Wiring the ECOFAST terminal block Properties You connect the power supplies and PROFIBUS DP to the ECOFAST terminal block using an ECOFAST connector. An additional ECOFAST connector can be used to loop the power supplies and PROFIBUS DP. Terminate the first and last ET 200eco (node) on PROFIBUS DP with a terminating resistor. Requirements The PROFIBUS address is set according to your configuration. Tools required Screwdriver, stripping tool and crimp tool for wiring the ECOFAST connector, if you do not use a ready-to-use ECOFAST connector. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 37 Connecting 3.4 Wiring the ET 200eco Accessories required ECOFAST hybrid patch cable with ECOFAST connector. The cable is available in various lengths. If you do not use the ECOFAST hybrid patch cable (see the table below): - Han Brid Cu cable connector or Han Brid Cu cable plug - ECOFAST hybrid cable PROFIBUS DP terminating resistor (ECOFAST) For article numbers, refer to the Appendix (Page 95) Wiring ECOFAST connectors The table below shows the terminal assignment of the ECOFAST connector Table 3- 14 Terminal assignment of the ECOFAST connector Pin Assignment View of the ECOFAST connector Infeed X01 A PROFIBUS DP signal A B PROFIBUS DP signal B 1 1L+ electronics / sensor supply 2 Electronics/sensor supply ground (1M) 3 Load voltage ground (2M) 4 2L+ load voltage supply Loop-through X02 A PROFIBUS DP signal A B PROFIBUS DP signal B 1 1L+ electronics / sensor supply 2 Electronics/sensor supply ground (1M) 3 Load voltage ground (2M) 4 2L+ load voltage supply * Installation instructions are included in the packaging of the Han Brid Cu cable connector or cable plug. ET 200eco Distributed I/O Device 38 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco Connecting the ECOFAST connectors 1. At the terminal block, push the ECOFAST connector interlock downward. 2. Plug the ECOFAST connectors (for 1L+, 2L+ and PROFIBUS DP) into the sockets of the terminal block. Observe the mechanical coding of the connectors for the power supply and the loop through. 3. Push the ECOFAST connector interlock upward. Figure 3-9 Connecting the ECOFAST connectors CAUTION Removing ECOFAST connector It is not permitted to remove the ECOFAST connector while ET 200eco is in operation! Always switch off the load voltage supply 2L+ before you remove the ECOFAST connector. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 39 Connecting 3.4 Wiring the ET 200eco Connecting the PROFIBUS DP terminating resistor Each PROFIBUS DP segment must be terminated at both ends with a wave impedance, i.e. at the first and last node of the segment. At the last bus node, connect the terminating resistor to the right hand connector of the relevant ECOFAST connection module. The procedure is the same as for the connection of the ECOFAST connector. The article numbers are listed in the Appendix (Page 95). Figure 3-10 Connecting the ECOFAST terminating resistor Note The terminating resistor is supplied with power by the electronics / sensor supply 1L+. Proper functioning of the terminating resistor can only be ensured if the electronics / sensor supply 1L+ does not exceed a tolerance of 10 %. Closing unused sockets Close all unused ECOFAST sockets using caps to achieve the degree of protection IP 65, IP 66 or IP 67. The article numbers are listed in the Appendix (Page 95). ET 200eco Distributed I/O Device 40 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco 3.4.6 Wiring the M12, 7/8" terminal block Properties Connect the power supplies and PROFIBUS DP to the M12, 7/8" terminal block. - M12 connection: PROFIBUS DP - 7/8" connection: Supply voltages You can use M12 or 7/8" circular socket connectors to loop the supply voltages and PROFIBUS DP. Terminate the first and last ET 200eco (node) on PROFIBUS DP with a terminating resistor. Requirements Always switch off the power supply before you wire the M12, 7/8" terminal block. The PROFIBUS address is set according to your configuration, and the terminating resistor is switched on as required. Tools required Stripping tool and screwdriver for wiring the M12 or 7/8" connector if you are not going to use ready-to-use connectors. Accessories required Patch cables with connector If you are not going to use ready-to-use connectors: - M12: 2-wire cable, shielded (bus cable) and M12 connector (see the table below) - 7/8": 5-wire cable and 7/8" connector (see the table below) M12 terminating resistor for PROFIBUS DP For article numbers, refer to the Appendix (Page 95) ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 41 Connecting 3.4 Wiring the ET 200eco Terminal assignment of the M12, 7/8" connector The tables below show the terminal assignment of the M12, 7/8" connector. Table 3- 15 M12 connector (PROFIBUS DP) Pin Assignment View of the M12 connector (wiring side) 1 Supply + (P5V2) 2 Data channel A (RxD/TxD-N) 3 Data reference potential 1 (M5V2) 4 Data channel B (RxD/TxD-P) 5 Shielding Thread Shielding 1 Can only be used for the M12 terminating resistor. It is not permitted to loop-through the voltage to the next connector using a 5-wire cable. 1 Table 3- 16 7/8" connector (supply voltages) Pin Assignment View of the 7/8" connector (wiring side) 1 Load voltage ground (2M) 2 Electronics/sensor supply ground (1M) 3 PE 4 1L+ electronics / sensor supply 5 2L+ load voltage supply ET 200eco Distributed I/O Device 42 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco Note To connect the supply voltage, we recommend the use of the cables specified in the Appendix (Page 95) (cable 5x1.5 mm2 with 7/8" connectors). If you want to prepare the cable yourself, you should use a cable with a conductor crosssection of 1.5 mm2. Connecting M12, 7/8" connectors 1. Plug the connector (M12 or 7/8") into the relevant circular socket connector on the terminal block. Make sure the connectors and sockets are properly interlocked (matched joint). 2. Secure the connector by tightening the knurled ring nut. Figure 3-11 Connecting M12, 7/8" connectors NOTICE Removing the 7/8" connector It is not permitted to remove the 7/8" connector while ET 200eco is in operation! Always switch off the load voltage supply 2L+ before you remove the 7/8" connector. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 43 Connecting 3.4 Wiring the ET 200eco Connecting the M12 terminating resistor for PROFIBUS DP Each PROFIBUS DP segment must be terminated at both ends with a wave impedance, i.e. at the first and last node of the segment. If the ET 200eco is the last PROFIBUS node, terminate PROFIBUS DP using the M12 terminating resistor. The article numbers are listed in the Appendix (Page 95). 1. Plug the M12 terminating resistor into the right M12 circular socket connector loopthrough on the terminal block. Make sure the interlock has properly engaged. 2. Secure the M12 connector by tightening the knurled ring nut. Figure 3-12 Connecting the M12 terminating resistor Closing unused sockets Always close all unused sockets using M12 or 7/8" caps to achieve degree of protection IP65, IP66 or IP67. The article numbers are listed in the Appendix (Page 95). ET 200eco Distributed I/O Device 44 Operating Instructions, 08/2014, A5E00158716-AD Connecting 3.4 Wiring the ET 200eco 3.4.7 Looping PROFIBUS DP and the supply voltage Properties The terminal block is equipped with connectors for the power supplies, and with a socket for looping the supply voltage and PROFIBUS DP. The feed connector and the loop socket are interconnected internally. Result: The removal of a terminal block while the system is in operation does not influence any downstream PROFIBUS nodes. Figure 3-13 Looping PROFIBUS DP and the supply voltage NOTICE Removing the terminal block While ET 200eco is in operation, you may only remove the terminal block if all the outputs are disconnected from the supply. Always switch off the load voltage supply 2L+ before you remove the terminal block. Degree of protection IP 65, IP 66 or IP 67 is no longer guaranteed after removal of the terminal block. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 45 Connecting 3.4 Wiring the ET 200eco Information on wiring Always make allowances for the influence of the cable length on the supply voltage at your ET 200eco (permitted tolerance) when you wire your configuration. Example with ECOFAST terminal block: When using a 10m cable with O 1.5 mm2, the voltage will drop by 2.5 V at a load of 10 A; this is equivalent to 0.25 V at a load of 1 A. The maximum feed current - of the ECOFAST terminal block: 8 A with 1L+ and 10 A with 2L+ - at the M12, 7/8" terminal block: 6 A with 1L+ and 8 A with 2L+ Those values may not be exceeded. CAUTION Maximum feed currents If you do not maintain the maximum feed current and the appropriate cable crosssections, you will risk overheating of the cable insulation and contacts, and damage to the device. ET 200eco Distributed I/O Device 46 Operating Instructions, 08/2014, A5E00158716-AD Configuration 4 GSD file You configure the ET 200eco Distributed I/O Device using the GSD file. The GSD file is used to integrate the ET 200eco into your system as a standard slave. You can download the GSD file on the Internet, at: http://www.ad.siemens.com/csi_e/gsd The GSD files for ET 200eco: I/O module 8 DI: Siem80db.gs* I/O module 16 DI: Siem80da.gs* I/O module 8 DO 2A: Siem80dd.gs* I/O module 16 DO 0.5A: Siem80fb.gs* I/O module 8 DI / 8 DO 2A: Siem80dc.gs* I/O module 8 DI / 8 DO 1.3A: Siem80fc.gs* The "*" character represents a wildcard for the relevant language (German, for example: Siem80db.gsg) Integrating the GSD file in your configuration software The procedures depend on whether you integrate the GSD file into a SIMATIC S7 system (with different configuration software: See the corresponding documentation. To integrate the GSD file in your configuration software using STEP 7 V4.02 or higher: 1. Runt STEP 7, then select "Options > Install New GSD File" in HW Config. 2. On the next dialog box, select the GSD file to install, and confirm with "OK". Result: The field device appears in the hardware catalog of the PROFIBUS DP folder. 3. Configure the ET 200eco using STEP 7 (refer to the STEP 7 online help). To integrate the GSD file in your configuration software using COM PROFIBUS V3.0 or higher: 1. Copy the GSD file for ET 200eco to the COM PROFIBUS folder: ...COMPB3\GSD (default). 2. Copy the bitmap file to: ...COMPB3\BITMAPS. 3. Run COM PROFIBUS, then select "File > Load GSD File." Result: ET 200eco appears in the hardware catalog at the slave configuration. 4. Configure the ET 200eco using COM PROFIBUS (refer to the STEP 7 online help). ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 47 5 Commissioning 5.1 Commissioning ET 200eco Software requirements Table 5- 1 Software requirements for commissioning Configuration software used Version Explanations STEP 7 V4.02 or higher You have integrated the GSD file for ET 200eco in STEP 7. V5.1 or higher + Service Pack 4 The GSD file is supplied with the module. Configuration software for the DP master used You need the GSD file of ET 200eco. Commissioning requirements Check whether the following requirements for commissioning the ET 200eco distributed I/O system are met: the DP slave is installed the PROFIBUS address is set at the DP slave the DP slave is wired the DP slave is configured supply voltage for DP master is switched on (refer to DP master manual) DP master is in RUN mode (refer to DP master manual) Commissioning ET 200eco Steps in commissioning the DP slave 1. Switch on the electronics / sensor supply to the DP slave. 2. Switch on the load voltage supply as required. ET 200eco Distributed I/O Device 48 Operating Instructions, 08/2014, A5E00158716-AD Commissioning 5.1 Commissioning ET 200eco Startup of ET 200eco Figure 5-1 Startup of ET 200eco ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 49 6 Alarm, error and system messages 6.1 Diagnostics by LED Display I/O module Status display per channel (green) Group error (red) Bus fault (red) Electronic/sensor power supply 1L+ (green) Load voltage supply 2L+ (green) (I/O module 8 DI, 16 DI not equipped with this LED) Figure 6-1 LED display on ET 200eco ET 200eco Distributed I/O Device 50 Operating Instructions, 08/2014, A5E00158716-AD Alarm, error and system messages 6.1 Diagnostics by LED Display Status and error displays SF, BF, ON Table 6- 1 Status and error display by LEDs LEDs Meaning SF BF ON off off off Remedy * Electronics / sensor supply voltage too low * or missing at all at the DP slave. Switch on the electronics / sensor supply (1L+) for the DP slave. * Hardware fault. * Replace the I/O module. * * on * Voltage (electronics / sensor supply) present at the DP slave. - * on on * DP slave is in STARTUP. - * Communication to the DP master is down. * Check the PROFIBUS DP connection. * The DP slave is unable to detect any transmission rate. * Check the DP master. * Bus interruption * * DP master is out of service Check all cables of your PROFIBUS DP network. * Verify the firm seating of the PROFIBUS DP on the terminal block. The PROFIBUS address set at the configuration connector is wrong or > 99. * Select a PROFIBUS address from the range 1 to 991 * Evaluate diagnostics data off on on * on off on * Received diagnostics message * Hardware fault in DP slave off on on * The configuration data sent by the DP master to the DP slave do not match the configuration of the DP slave. * Check the DP slave configuration (I/O address, PROFIBUS address). off on on * The DP slave has detected the transmission rate, but s not addressed by the DP master. * Check the PROFIBUS address at the DP slave or in the configuration software. * * The DP slave is not configured. Check the DP slave configuration (station type). * Overload at the ET 200eco sensor supply. * Check the sensors / actuators connected to the module. Remove the sensors / actuators one after the other. Result: The BF LED stops flashing, and the ON LED will be lit after you have removed the field device causing the overload. * Your hardware is faulty if the BF LED continues flashing even though you have removed all sensors / actuators from the I/O module. off flashes off * Not relevant Switch POWER OFF / POWER ON after you edited the PROFIBUS address. With POWER ON, the PROFIBUS address is applied. 1 ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 51 Alarm, error and system messages 6.1 Diagnostics by LED Display 24 V DC status indicator The 24 V DC LED is lit in green color to indicate the presence of the 2L+ load voltage supply. Only the I/O modules 8 DO 2A, 8 DI / 8 DO 2A, 8 DI / 8 DO 1.3A and 16 DO 0.5A are equipped with this LED. Channel status display ET 200eco indicates the status at each input / output on separate LEDs. The LED is lit in green color to indicate the active input / output. I/O module 8 DI: 8 input status LEDs I/O module 16 DI: 16 input status LEDs I/O module 8 DO 2A: 8 output status LEDs I/O module 16 DO 0.5A: 16 output status LEDs I/O module 8 DI / 8 DO 2A and 8 DI / 8 DO 1.3A: 8 input status LEDs, and 8 output status LEDs ET 200eco Distributed I/O Device 52 Operating Instructions, 08/2014, A5E00158716-AD Alarm, error and system messages 6.2 ET 200eco diagnostics 6.2 ET 200eco diagnostics Note Disabling diagnostics Use the following hexadecimal parameter assignment to disable the diagnostics for ET 200eco: 08 00 00 00 00 6.2.1 Reading diagnostics data Slave diagnostics The slave diagnostics function is compliant with IEC 61784-1. Depending on the DP master, the diagnostics data of all DP slaves which conform to this standard can be read out using STEP 7. Options of reading diagnostics data Table 6- 2 Reading ET 200eco diagnostics data in STEP 7 Automation system with DP master Block or tab in STEP 7 Application See ... SIMATIC S7/M7 "DP Slave Diagnostics" tab Display slave diagnostics data in plain text on STEP 7 user interface "Hardware diagnostics" in STEP 7 online help SFC 13 "DP NRM_DG" Reading slave diagnostics data (saving these to the data area of the user program) Configuration see chapter Example: Reading slave diagnostics data using SFC 13 "DP NRM_DG" (Page 54), SFC see reference manual system and standard functions FB 125/FC 125 Evaluating slave diagnostics data Download of FB/FC 125 from the Internet (http://support.automatio n.siemens.com/CN/view/ en/26996747) FB 230 "S_DIAG" Reading slave diagnostics data (saving these to the data area of the user program) Configuration see the chapter in this manual SIMATIC S5 with the S5-95U as DP master Download of FB 192 from the Internet (http://support.automatio n.siemens.com/WW/view /en/113141) ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 53 Alarm, error and system messages 6.2 ET 200eco diagnostics 6.2.2 Example: Reading slave diagnostics data using SFC 13 "DP NRM_DG" Application example Here is an example of how to use SFC 13 to read DP slave diagnostics data in the STEP 7 user program. Assumptions For this STEP 7 user program it is assumed that: ET 200eco diagnostic address 1022 (3FEH). Slave diagnostics data should be saved to DB 82: starting at address 0.0, length 13 bytes. Slave diagnostics data consist of 13 bytes. STEP 7 user program STL Description CALL SFC 13 REQ:=TRUE Read request LADDR:=W#16#3FE ET 200eco diagnostics address RET_VAL:=MW 0 RET_VAL of SFC 13 RECORD:=P#DB82.DBX 0.0 BYTE 13 Diagnostics data mailbox in DB 82 BUSY:=M2.0 Read operation covers several OB1 cycles ET 200eco Distributed I/O Device 54 Operating Instructions, 08/2014, A5E00158716-AD Alarm, error and system messages 6.2 ET 200eco diagnostics 6.2.3 Configuration of ET 200eco slave diagnostics Configuration of ET 200eco slave diagnostics Figure 6-2 Configuration of ET 200eco slave diagnostics ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 55 Alarm, error and system messages 6.2 ET 200eco diagnostics 6.2.4 Station states 1 to 3 Definition Station states 1 to 3 provide an overview of the status of a DP slave. Station status 1 Table 6- 3 Bit 0 Configuration of ET 200eco station status 1 (byte 0) Meaning Cause / remedy 1: The DP master ca not address the DP slave. The bit is always 0 at the DP slave. * Check the correct setting of the PROFIBUS address at the DP slave * Check the bus connectors * Check the power supply of the DP slave * Verify the RS 485 Repeater settings * Check whether the DP slave was reset (POWER OFF / POWER ON) 1 1: The DP slave is not yet ready to exchange data. * Wait for the DP slave to complete its startup. 2 1: The configuration data sent by the DP master to the DP slave do not match the configuration of the DP slave. * Verify the station type or DP slave configuration in the configuration software 3 0: The bit is always 0. --- 4 1: The DP slave does not support the requested function (SYNC/FREEZE, for example). * Check the configuration. 5 1: The bit is "1" when reading the station status from the DP master * DP master is unable to interpret the response of the DP slave. 6 1: The DP slave type does not match the software configuration. * Compare your online and offline configuration. 7 1: Parameters have been assigned to the DP slave by a DP master other than the one currently accessing the DP slave. * The bit is always set to "1", for example, when you access the DP slave with the programming device or another DP master. The "master PROFIBUS address" diagnostic byte contains the PROFIBUS address of the DP master that assigned parameters to the DP slave. ET 200eco Distributed I/O Device 56 Operating Instructions, 08/2014, A5E00158716-AD Alarm, error and system messages 6.2 ET 200eco diagnostics Station status 2 Table 6- 4 Bit Configuration of ET 200eco station status 2 (byte 1) Meaning 0 1: The DP slave must be assigned new parameters. 1 1: Received a diagnostic message. The DP slave freezes its functions until the fault has been corrected (static diagnostic message). 2 1: The bit is always "1" at the DP slave. 3 1: Response monitoring is enabled for this DP slave. 4 1: The DP slave has received a "FREEZE" control command.* 5 1: The DP slave has received a "SYNC" control command.* 6 1: The bit is always "0." 7 1: When reading the station status from the DP master the bit is "1" if the DP slave is disabled at the DP master. The DP is disabled, which means it is isolated from the current processing. * The "FREEZE" control command also freezes the diagnostic messages. Station status 3 Table 6- 5 6.2.5 Configuration of ET 200eco station status 3 (byte 2) Bit Meaning 0 to 7 0: The bits are always "0." Master PROFIBUS address Definition Diagnostics byte 3 is used to store the PROFIBUS address of the DP master: which has assigned parameters to the DP slave, and has read / write access to the DP slave FFH in byte 3 If byte 3 of the master's PROFIBUS address contains the value FFH, the DP master has not assigned any parameters to the DP slave. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 57 Alarm, error and system messages 6.2 ET 200eco diagnostics 6.2.6 Manufacturer ID Definition The manufacturer ID contains a code that describes the DP slave type. Manufacturer ID Table 6- 6 Configuration of the ET 200eco manufacturer ID (bytes 4 and 5) Byte 4 Byte 5 Manufacturer ID for 80H DBH ET 200eco 8 DI 80H DAH ET 200eco 16 DI 80H DDH ET 200eco 8 DO 2A 80H FBH ET 200eco 16 DO 0.5A 80H DCH ET 200eco 8 DI / 8 DO 2A 80H FCH ET 200eco 8 DI / 8 DO 1.3A ET 200eco Distributed I/O Device 58 Operating Instructions, 08/2014, A5E00158716-AD Alarm, error and system messages 6.2 ET 200eco diagnostics 6.2.7 Device-specific diagnostics Definition Based on device-specific diagnostics data, you can identify a short-circuit at the electronics / sensor supply 1L+ or a missing load voltage supply 2L+. The length of device-specific diagnostics data is defined in the header. Device-specific diagnostics Configuration of device-specific diagnostics for ET 200eco: Figure 6-3 Configuration of device-specific diagnostics for ET 200eco ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 59 7 General specifications 7.1 Standards and Approvals PROFIBUS standard The ET 200eco distributed I/O system is based on the IEC 61784-1 standard. IEC 61131-2 The ET 200eco Distributed I/O System meets the requirements and criteria of the IEC 61131-2 standard. CE Label Our products fulfill the requirements and safety objectives of the following EC Directives and comply with the harmonized European standards (EN) published for programmable logic controllers in the official journals of the European Communities: 2004/108/EC "Electromagnetic Compatibility" (EMC Directive) The EC Declarations of Conformity are kept available for the responsible authorities at: Siemens Aktiengesellschaft Automation and Drives A & D AS RD 4 PO Box 1963 D-92209 Amberg Tick mark for Australia Our products are compliant with requirements to AS/NZS 2064 Class A. cULus approval Underwriters Laboratories Inc., in accordance with UL 508 (Industrial Control Equipment) CSA C22.2 No. 142 (Process Control Equipment) NEMA classification (for the US market) The ET 200eco distributed I/O device meets the NEMA classification: Enclusore rating Type: 4X-indoor use only. ET 200eco Distributed I/O Device 60 Operating Instructions, 08/2014, A5E00158716-AD General specifications 7.2 EMC compatibility, shipping and storage conditions 7.2 EMC compatibility, shipping and storage conditions Definition Electromagnetic compatibility is the ability of an electrical device to function in its electromagnetic environment in a satisfactory manner without affecting this environment. The ET 200eco Distributed I/O Device also meets the requirements of the EMC law of the EEC. Prerequisite is that the electrical configuration of the ET 200eco Distributed I/O Device complies with current regulations and directives. Pulse-shaped disturbance The table below shows the EMC compatibility of the ET 200eco Distributed I/O Device with respect to pulse-shaped disturbances. Table 7- 1 Pulse-shaped disturbance Pulse-shaped disturbance Test voltage corresponds with degree of severity 8 kV 3 (air discharge) Electrostatic discharge according to IEC 61000-4-2. Burst pulses (high-speed transient disturbance) to IEC 61000-4-4. 6 kV 2 (contact discharge) 2 kV (power supply line) 3 2 kV (signal line) 3 High-energy surge to IEC 61000-4-5 Only with lightning protection elements (see DP master manual and description of SIMATIC NET PROFIBUS networks) * * Asymmetric coupling 2 kV (power supply line) Symmetric coupling 1 kV (power supply line) 3 2 kV (signal / data line) 1 kV (signal / data line) Sinusoidal disturbance The table below shows the EMC compatibility of the ET 200eco Distributed I/O Device with respect to sinusoidal disturbance. Table 7- 2 Sinusoidal disturbance RF radiation to IEC 61000-4-3 Electromagnetic RF field Amplitude modulated 80 MHz to 1000 MHz Pulse modulated 900 MHz 5 MHz 10 V/m 80 % AM (1 kHz) HF coupling according to IEC 61000-4-6 0.15 MHz to 80 MHz 10 Vrms unmodulated 50 % ED 80 % AM (1 kHz) 200 Hz repetition rate 150 source impedance ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 61 General specifications 7.2 EMC compatibility, shipping and storage conditions Emission of radio interference The table below shows the emitted interference of electromagnetic fields according to EN 55011: Limit class A, group 1 (measured at a distance of 10 m). Table 7- 3 Emission of radio interference Frequency Noise emission 30 MHz to 230 MHz < 40 dB (V/m) Q 230 MHz to 1000 MHz < 47 dB (V/m) Q Shipping and storage conditions The ET 200eco Distributed I/O Device surpasses shipping and storage requirements to IEC 61131-2. The table below contains information on transportation and storage conditions that apply to modules in original packaging. Table 7- 4 Shipping and storage conditions Type of condition Permissible range Free fall 1m Temperature from -40 C to +70 C Temperature change 20 K/h Air pressure 1080 hPa to 660 hPa (corresponds to an altitude of -1000 m to 3500 m) Relative humidity 5% to 95%, without condensation ET 200eco Distributed I/O Device 62 Operating Instructions, 08/2014, A5E00158716-AD General specifications 7.3 Mechanical and climatic environmental conditions 7.3 Mechanical and climatic environmental conditions Climatic environmental conditions The table below shows the climatic environmental conditions. Table 7- 5 Climatic environmental conditions Environmental conditions Fields of application Remarks Temperature 0 C to 55 C All mounting positions Temperature change 10 K/h --- Relative humidity from 5% to max. 100% With condensation Air pressure 1080 hPa to 795 hPa Corresponds to an altitude of 1000 m to 2000 m Pollutant concentration SO2: < 0.5 ppm; --- relative humidity < 60 %, no dewing H2S: < 0.1 ppm; relative humidity < 60 %, no dewing Mechanical environmental conditions The table below shows the mechanical environmental conditions in the form of sinusoidal oscillations. Table 7- 6 Mechanical environmental conditions Frequency band Continuous Tested at ... 10 f 58 Hz 0.35 mm amplitude 0.75 mm amplitude 58 f 150 Hz 5 g constant acceleration 10 g constant acceleration ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 63 General specifications 7.3 Mechanical and climatic environmental conditions Tests of mechanical environmental conditions The table below provides information about the type and scope of the tests of mechanical environmental conditions. Table 7- 7 Tests of mechanical environmental conditions Test ... Test standard Terminal / electronic modules Vibration Vibration test according to IEC 60068-2-6 Type of vibration: Frequency sweeps at a rate of change of 1 octave/minute. 10 Hz f 58 Hz, constant amplitude 0.75 mm 58 Hz f 150 Hz, constant acceleration 10 g Duration of vibration: 10 frequency sweeps per axis in each of three perpendicular axes Shock Shock, tested to Shock method: half-sine IEC 60068-2-27 Strength of shock: 30 g peak value, 18 ms duration Direction of shock: 3 shocks in each +/- direction at each of the three vertically aligned axes Continuous shock Shock, tested to Shock method: half-sine IEC 60068-29 Strength of shock: 25 g peak value, 6 ms duration Direction of shock: 1000 shocks in each +/- direction at each of the three vertically aligned axes ET 200eco Distributed I/O Device 64 Operating Instructions, 08/2014, A5E00158716-AD General specifications 7.4 Specifications for insulation tests, protection class, degree of protection, and rated voltage 7.4 Specifications for insulation tests, protection class, degree of protection, and rated voltage Test voltage Proof of dielectric strength must be provided in the type test at a test voltage to IEC 61131-2: Circuits with rated voltage Vinagainst other circuits or ground Test voltage < 50 V 500 V DC < 150 V 2500 V DC < 250 V 4000 V DC Pollution degree/overvoltage category according to IEC 61131-2 Pollution degree 2 Overvoltage category at UN = 24 V DC: II Protection class according to IEC 61010-2 Protection class I Degree of protection IP65 Degree of protection according to IEC 60529 Protection against the ingress of dust and full touch protection Protection against water jet directed onto the enclosure from all directions (water may not cause damage) Degree of protection IP66 and IP67 Degree of protection according to IEC 60529 Protection against the ingress of dust and full touch protection IP66: Water from heavy seas or water projected in powerful jets shall not enter the enclosure in harmful quantities. IP67: Ingress of water in a harmful quantity shall not be possible when the enclosure is immersed in water under defined conditions of pressure and time ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 65 General specifications 7.4 Specifications for insulation tests, protection class, degree of protection, and rated voltage Rated voltage for operation The table below shows the rated voltage and corresponding tolerances for operation of the ET 200eco Distributed I/O Device. Rated voltage Tolerance 24 V DC (SELV/PELV) 20.4 V DC to 28.8 V DC Note The following applies to an ECOFAST terminating resistor: Proper functioning of the terminating resistor can only be ensured if the electronics / sensor supply (1L+) does not exceed a tolerance of 10%. ET 200eco Distributed I/O Device 66 Operating Instructions, 08/2014, A5E00158716-AD 8 Technical specifications 8.1 Overview Contents ET 200eco consists of various components. This chapter contains their specifications. 8.2 ECOFAST terminal block (6ES7194-3AA00-0AA0) Properties Properties of the ECOFAST terminal block: For insertion and screw mounting on any I/O module. Connection of supply voltages and PROFIBUS DP via ECOFAST connector (at socket X01, power supply). Connection for looping the supply voltages and PROFIBUS DP to the next PROFIBUS node using an additional ECOFAST connector (at the "loop-through" socket X02). Internal connection between feed line socket X01 and loop-through socket X02 (T-functionality). Adjustable PROFIBUS address (1 to 99) using a configuration connector. Terminal assignment of the ECOFAST sockets The table below shows the terminal assignment of the two ECOFAST sockets for connecting the supply voltages and PROFIBUS DP. Table 8- 1 Pin-out of the X01 and X02 sockets Pin Assignment Feed male connector X01 Loop-through socket X02 A PROFIBUS DP signal A B PROFIBUS DP signal B 1 1L+ electronics / sensor supply 2 Electronics/sensor supply ground (1M) 3 Load voltage ground (2M) 4 2L+ load voltage supply View of the socket (front view of the terminal block) ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 67 Technical specifications 8.2 ECOFAST terminal block (6ES7194-3AA00-0AA0) Block diagram The diagram below shows the ECOFAST terminal block. Figure 8-1 Block diagram of the ECOFAST terminal block Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) Weight 79 x 60 x 30 Approx. 313 g Power loss Power loss of the module 1 The Typ. 2 W1 power loss depends on the current looped through via the terminal block. Note The maximum feed current should not exceed 8 A with 1L+ and 10 A with 2L+. ET 200eco Distributed I/O Device 68 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.3 M12, 7/8" terminal block (6ES7194-3AA00-0BA0) 8.3 M12, 7/8" terminal block (6ES7194-3AA00-0BA0) Properties Properties of the M12, 7/8" terminal block: For insertion and screw mounting on any I/O module. Connection of - PROFIBUS DP via M12 connector (at feed line socket DP1) - Supply voltages via 7/8" connector (at feed line socket X01) Connection for looping the supply voltages and PROFIBUS DP to the next PROFIBUS node using an additional M12 or 7/8" connector (at the "loop-through" sockets DP2 or X02). Internally interconnected feed line sockets DP1 or X01 and loop-through sockets DP2 or X02 (T-functionality). Adjustable PROFIBUS address (1 to 99, two rotary selector switches). Terminal assignment of the M12, 7/8" sockets The tables below show the terminal assignment of the two M12, 7/8" sockets for connecting the supply voltages and PROFIBUS DP. Table 8- 2 Pin Pin-out of the DP1 and DP2 (M12) connectors Pin-out of the M12 feed line socket DP1 and loop-through socket DP2 (PROFIBUS DP) 1 Power supply + (P5V2) 2 Data channel A (RxD/TxD-N) 3 Data reference potential (M5V2) 4 Data channel B (RxD/TxD-P) 5 Shielding Thread Shielding Table 8- 3 Pin View of the connector (front view of the terminal block) Pin-out of the X01 and X02 connectors (7/8") Pin-out of the 7/8" feed line socket X01 and loop-through socket X02 (PROFIBUS DP) 1 Load voltage ground (2M) 2 Electronics / sensor supply ground (1M) 3 PE 4 1L+ electronics / sensor supply 5 2L+ load voltage supply View of the connector (front view of the terminal block) ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 69 Technical specifications 8.3 M12, 7/8" terminal block (6ES7194-3AA00-0BA0) Block diagram The diagram below shows the M12, 7/8" terminal block. Figure 8-2 Block diagram of the M12, 7/8" terminal block Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) Weight 79 x 60 x 29 Approx. 392 g Power loss Power loss of the module 1 The Typ. 2 W1 power loss depends on the current looped through via the terminal block. Note The maximum feed current should not exceed 6 A with 1L+ and 8 A with 2L+. ET 200eco Distributed I/O Device 70 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.4 I/O module 8 DI (6ES7141-3BF00-0XA0) 8.4 I/O module 8 DI (6ES7141-3BF00-0XA0) Properties Properties of the I/O module 8 DI: 8 digital inputs Rated input voltage 24V DC Suitable for switches and proximity switches (BEROs) Terminal assignment of the DI sockets The table below shows the terminal assignment of the eight sockets for connection of the digital inputs. Table 8- 4 Pin-out of the digital input sockets X1 to X8 Assignment Pin Socket X1 1 Socket X2 Socket X3 Socket X4 24 V sensor supply 2 n.c. 3 Ground for sensor supply 4 Input signal Channel 0 Channel 1 5 Pin Front view of the socket Channel 2 Channel 3 Socket X7 Socket X8 PE Socket X5 Socket X6 1 24 V sensor supply 2 n.c. 3 Ground for sensor supply 4 Input signal Channel 4 5 Channel 5 Channel 6 Channel 7 PE ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 71 Technical specifications 8.4 I/O module 8 DI (6ES7141-3BF00-0XA0) Block diagram The block diagram below shows the I/O module 8 DI. Figure 8-3 Block diagram of I/O module 8 DI ET 200eco Distributed I/O Device 72 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.4 I/O module 8 DI (6ES7141-3BF00-0XA0) Technical specifications of I/O module 8 DI Technical specifications Dimensions and weight Dimensions W x H x D (mm) 60 x 210 x 28 Weight Approx. 210 g Module-specific data Transmission rates 9.6/19.2/45.45/93.75/187.5/500 kBaud 1.5/3/6/12 MBaud Bus protocol PROFIBUS DP Number of channels 8 digital inputs Cable length * Max. 30 m unshielded Manufacturer ID 80DBH Voltages, currents, potentials Rated electronics / sensor supply voltage 1L+ * Reverse polarity protection Number of simultaneously controllable inputs * 24 V DC Yes 8 up to 55 C All mounting positions Electrical isolation No * Between channels * between PROFIBUS DP and all other circuitry Yes Permitted potential difference * Between different electric circuits Isolation test voltage 75 V DC, 60 V AC 500 V DC Current consumption * Typ. 70 mA From supply voltage 1L+ Power loss of the module Typ. 2.4 W Status, interrupts, diagnostics Status display green LED per channel Alarms No Diagnostic functions * Group error display red LED (SF) * Channel error display No * Diagnostic information can be read Supported Sensor supply outputs Number of outputs 8 Output current Up to 55 C max. 1 A (total current) Short-circuit protection Yes, electronic ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 73 Technical specifications 8.4 I/O module 8 DI (6ES7141-3BF00-0XA0) Technical specifications Sensor selection data Input voltage * Rated value * for "1" signal * for "0" signal 24 V DC 13 to 30 V -3 to 5 V Input current * at "1" signal * at "0" signal Typ. 7 mA Input delay * At "0" to "1" transition * At "1" to "0" transition Typ. 3 ms Typ. 3 ms Input characteristics According to IEC 61131-2, Type 1 Connection of 2-wire BEROs Supported * Permitted quiescent current Max. 1.5 mA ET 200eco Distributed I/O Device 74 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.5 I/O module 16 DI (6ES7141-3BH00-0XA0) 8.5 I/O module 16 DI (6ES7141-3BH00-0XA0) Properties Properties of the I/O module 16 DI: 16 digital inputs Rated input voltage 24V DC Suitable for switches and proximity switches (BEROs) Terminal assignment of the DI sockets The table below shows the terminal assignment of the eight sockets for connection of the digital inputs. Table 8- 5 Pin-out of the digital input sockets X1 to X8 Assignment Pin Socket X1 1 Socket X2 Socket X3 Socket X4 24 V sensor supply 2 Input signal Channel 8 Channel 9 Channel 10 3 Ground for sensor supply 4 Input signal Channel 0 Channel 1 5 Pin Front view of the socket Channel 11 Channel 2 Channel 3 Socket X7 Socket X8 PE Socket X5 Socket X6 1 24 V sensor supply 2 Input signal Channel 12 Channel 13 Channel 14 3 Ground for sensor supply 4 Input signal Channel 4 5 Channel 5 Channel 6 Channel 15 Channel 7 PE ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 75 Technical specifications 8.5 I/O module 16 DI (6ES7141-3BH00-0XA0) Block diagram The block diagram below shows the I/O module 16 DI. Figure 8-4 Block diagram of I/O module 16 DI ET 200eco Distributed I/O Device 76 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.5 I/O module 16 DI (6ES7141-3BH00-0XA0) Technical specifications of I/O module 16 DI Technical specifications Dimensions and weight Dimensions W x H x D (mm) 60 x 210 x 28 Weight Approx. 210 g Module-specific data Transmission rates 9.6/19.2/45.45/93.75/187.5/500 kBaud 1.5/3/6/12 MBaud Bus protocol PROFIBUS DP Number of channels 16 digital inputs Cable length * Max. 30 m unshielded Manufacturer ID 80DAH Voltages, currents, potentials Rated electronics / sensor supply voltage 1L+ * Reverse polarity protection Number of simultaneously controllable inputs * 24 V DC Yes 16 up to 55 C All mounting positions Electrical isolation No * Between channels * between PROFIBUS DP and all other circuitry Yes Permitted potential difference * Between different electric circuits Isolation test voltage 75 V DC, 60 V AC 500 V DC Current consumption * Typ. 70 mA From supply voltage 1L+ Power loss of the module Typ. 3.6 W Status, interrupts, diagnostics Status display green LED per channel Alarms No Diagnostic functions * Group error display red LED (SF) * Channel error display No * Diagnostic information can be read Supported Sensor supply outputs Number of outputs 8 Output current Up to 55 C max. 1 A (total current) Short-circuit protection Yes, electronic ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 77 Technical specifications 8.5 I/O module 16 DI (6ES7141-3BH00-0XA0) Technical specifications Sensor selection data Input voltage * Rated value * for "1" signal * for "0" signal 24 V DC 13 to 30 V -3 to 5 V Input current * at "1" signal * at "0" signal Typ. 7 mA Input delay * At "0" to "1" transition * At "1" to "0" transition Typ. 3 ms Typ. 3 ms Input characteristics According to IEC 61131-1, Type 1 Connection of 2-wire BEROs Supported * Permitted quiescent current Max. 1.5 mA ET 200eco Distributed I/O Device 78 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.6 I/O module 8 DO 2A (6ES7142-3BF00-0XA0) 8.6 I/O module 8 DO 2A (6ES7142-3BF00-0XA0) Properties Properties of the I/O module 8 DO 2A: 8 digital outputs Output current 2 A per output Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and indicator lights Terminal assignment of the DO sockets The table below shows the terminal assignment of the eight sockets for connection of the digital outputs. Table 8- 6 Pin-out of the digital output sockets X1 to X8 Assignment Pin Socket X1 Socket X2 Socket X3 1 n.c. 2 n.c. 3 Load voltage ground (2M) 4 Output signal Channel 0 Channel 1 5 Pin Front view of the socket Socket X4 Channel 2 Channel 3 Socket X7 Socket X8 PE Socket X5 Socket X6 1 n.c. 2 n.c. 3 Load voltage ground (2M) 4 Output signal Channel 4 5 Channel 5 Channel 6 Channel 7 PE ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 79 Technical specifications 8.6 I/O module 8 DO 2A (6ES7142-3BF00-0XA0) Block diagram The block diagram below shows the I/O module 8 DO 2A. Figure 8-5 Block diagram of I/O module 8 DO 2A ET 200eco Distributed I/O Device 80 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.6 I/O module 8 DO 2A (6ES7142-3BF00-0XA0) Technical specifications of I/O module 8 DO 2A Technical specifications Dimensions and weight Dimensions W x H x D (mm) 60 x 210 x 28 Weight Approx. 210 g Module-specific data Transmission rates 9.6/19.2/45.45/93.75/187.5/500 kBaud 1.5/3/6/12 MBaud Bus protocol PROFIBUS DP Number of channels 8 digital outputs Cable length Max. 30 m * unshielded Manufacturer ID 80DDH Voltages, currents, potentials Rated electronics / sensor supply voltage 1L+ * Reverse polarity protection 2L+ rated load voltage * 24 V DC Yes 24 V DC Yes Reverse polarity protection Total current of the outputs * 4 A each1) 2) up to 55 C All mounting positions Electrical isolation No * Between channels * between PROFIBUS DP and all other circuitry Yes Permitted potential difference * Between different electric circuits Isolation test voltage 75 V DC, 60 V AC 500 V DC Current consumption * From supply voltage 1L+ * from 2L+ rated load voltage Typ. 70 mA Typ. 60 mA Power loss of the module Typ. 4 W Status, interrupts, diagnostics Status display green LED per channel Alarms No Diagnostic functions * Group error display red LED (SF) * Channel error display No * Diagnostic information can be read Supported ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 81 Technical specifications 8.6 I/O module 8 DO 2A (6ES7142-3BF00-0XA0) Technical specifications Actuator selection data Output voltage at "1" signal Min. 2L+ (-0.8 V) Output current * at "1" signal 2A * at "0" signal (residual current) Max. 0.5 mA Load resistance range 12 to 4 k Lamp load Max. 10 W Wiring 2 outputs in parallel * for redundant load control Supported * For performance increase Not supported Control of a digital input Supported Switching frequency * with resistive load Max. 100 Hz * with inductive load to IEC 947-5-1, DC13 Max. 0.5 Hz * with lamp load Max. 1 Hz Internal limiting of the inductive shutdown voltage to Typ. 2L+ (-44 V) Short-circuit protection of output Yes, electronic * Response threshold Typ. 4 A (per channel) 1 4 A total current for sockets X1, X3, X5, X7 and 4 A total current for sockets X2, X4, X6 and X8. 2 Observe the current carrying capacity of the cable. ET 200eco Distributed I/O Device 82 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.7 I/O module 16 DO 0.5A (6ES7142-3BH00-0XA0) 8.7 I/O module 16 DO 0.5A (6ES7142-3BH00-0XA0) Properties Properties of the I/O module 16 DO 0.5A: 16 digital outputs Output current 0.5 A per output Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and indicator lights Terminal assignment of the DO sockets The table below shows the terminal assignment of the eight sockets for connection of the digital outputs. Table 8- 7 Pin-out of the digital output sockets X1 to X8 Assignment Pin Socket X1 Socket X2 Socket X3 1 n.c. 2 Output signal Channel 8 Channel 9 Channel 10 3 Load voltage ground (2M) 4 Output signal Channel 0 Channel 1 5 Pin Front view of the socket Socket X4 Channel 11 Channel 2 Channel 3 Socket X7 Socket X8 PE Socket X5 Socket X6 1 n.c. 2 Output signal Channel 12 Channel 13 Channel 14 3 Load voltage ground (2M) 4 Output signal Channel 4 5 Channel 5 Channel 6 Channel 15 Channel 7 PE ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 83 Technical specifications 8.7 I/O module 16 DO 0.5A (6ES7142-3BH00-0XA0) Block diagram The block diagram below shows the I/O module 16 DO 0.5A. Figure 8-6 Block diagram of I/O module 16 DO 0.5A ET 200eco Distributed I/O Device 84 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.7 I/O module 16 DO 0.5A (6ES7142-3BH00-0XA0) Technical specifications of I/O module 16 DO 0.5A Technical specifications Dimensions and weight Dimensions W x H x D (mm) 60 x 210 x 28 Weight Approx. 210 g Module-specific data Transmission rates 9.6/19.2/45.45/93.75/187.5/500 kBaud 1.5/3/6/12 MBaud Bus protocol PROFIBUS DP Number of channels 16 digital outputs Cable length * Max. 30 m unshielded Manufacturer ID 80FBH Voltages, currents, potentials Rated electronics / sensor supply voltage 1L+ * Reverse polarity protection 2L+ rated load voltage * 24 V DC Yes 24 V DC Yes Reverse polarity protection Total current of the outputs * 4A1) up to 55 C All mounting positions Electrical isolation No * Between channels * between PROFIBUS DP and all other circuitry Yes Permitted potential difference * Between different electric circuits Isolation test voltage 75 V DC, 60 V AC 500 V DC Current consumption * From supply voltage 1L+ * from 2L+ rated load voltage Typ. 70 mA Typ. 80 mA Power loss of the module Typ. 4 W Status, interrupts, diagnostics Status display green LED per channel Alarms No Diagnostic functions * Group error display red LED (SF) * Channel error display No * Diagnostic information can be read Supported ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 85 Technical specifications 8.7 I/O module 16 DO 0.5A (6ES7142-3BH00-0XA0) Technical specifications Actuator selection data Output voltage at "1" signal Min. 2L+ (-0.8 V) Output current * at "1" signal 0.5 A * at "0" signal (residual current) Max. 0.1 mA Load resistance range 48 to 4 k Lamp load Max. 5 W Wiring 2 outputs in parallel * for redundant load control Supported * For performance increase Not supported Control of a digital input Supported Switching frequency * with resistive load Max. 100 Hz * with inductive load to IEC 947-5-1, DC13 Max. 0.5 Hz * with lamp load Max. 1 Hz Internal limiting of the inductive shutdown voltage to Typ. 2L+ (-47 V) Short-circuit protection of output Yes, electronic * 1 Response threshold Typ. 1.4 A (per channel) Observe the current carrying capacity of the cable. ET 200eco Distributed I/O Device 86 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.8 I/O module 8 DI / 8 DO 2A (6ES7143-3BH00-0XA0) 8.8 I/O module 8 DI / 8 DO 2A (6ES7143-3BH00-0XA0) Properties Properties of the I/O module 8 DI / 8 DO 2A: 8 digital inputs Rated input voltage 24V DC Suitable for switches and proximity switches (BEROs) 8 digital outputs Output current 2 A per output Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and indicator lights Terminal assignment of the DI sockets The table below shows the terminal assignment of the eight sockets for connection of the digital inputs and outputs. Table 8- 8 Pin-out of the digital I/O sockets X1 to X8 Assignment Pin Socket X1 1 Socket X2 Socket X3 Socket X4 24 V sensor supply 2 Input signal Channel 0 Channel 1 Channel 2 3 Sensor / load voltage supply ground 4 Output signal Channel 0 Channel 1 5 Pin Front view of the socket Channel 3 Channel 2 Channel 3 Socket X7 Socket X8 PE Socket X5 Socket X6 1 24 V sensor supply 2 Input signal Channel 4 Channel 5 Channel 6 3 Sensor / load voltage supply ground 4 Output signal Channel 4 5 Channel 5 Channel 6 Channel 7 Channel 7 PE ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 87 Technical specifications 8.8 I/O module 8 DI / 8 DO 2A (6ES7143-3BH00-0XA0) Block diagram The block diagram below shows the I/O module 8 DI / 8 DO 2A. Figure 8-7 Block diagram of I/O module 8 DI / 8 DO 2A ET 200eco Distributed I/O Device 88 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.8 I/O module 8 DI / 8 DO 2A (6ES7143-3BH00-0XA0) Technical specifications of the I/O module 8 DI / 8 DO 2A Technical specifications Dimensions and weight Dimensions W x H x D (mm) 60 x 210 x 28 Weight Approx. 210 g Module-specific data Transmission rates 9.6/19.2/45.45/93.75/187.5/500 kBaud 1.5/3/6/12 MBaud Bus protocol PROFIBUS DP Number of channels 8 digital inputs and 8 digital outputs Cable length * Max. 30 m unshielded Manufacturer ID 80DCH Voltages, currents, potentials Rated electronics / sensor supply voltage 1L+ * Reverse polarity protection 2L+ rated load voltage * 24 V DC No Reverse polarity protection Number of simultaneously controllable inputs * 24 V DC No 8 up to 55 C All mounting positions Total current of the outputs * 4 A each1) 2) up to 55 C All mounting positions Electrical isolation No * Between channels * between PROFIBUS DP and all other circuitry Yes Permitted potential difference * Between different electric circuits Isolation test voltage 75 V DC, 60 V AC 500 V DC Current consumption * From supply voltage 1L+ * from 2L+ rated load voltage Typ. 70 mA Typ. 60 mA Power loss of the module Typ. 5 W Status, interrupts, diagnostics Status display green LED per channel Alarms No Diagnostic functions * Group error display red LED (SF) * Channel error display No * Diagnostic information can be read Supported ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 89 Technical specifications 8.8 I/O module 8 DI / 8 DO 2A (6ES7143-3BH00-0XA0) Technical specifications Sensor supply outputs Number of outputs 8 Output current Up to 55 C max. 0.75 A (total current) Short-circuit protection Yes, electronic Sensor selection data Input voltage * Rated value * for "1" signal * for "0" signal 24 V DC 13 to 30 V -3 to 5 V Input current * at "1" signal * at "0" signal Typ. 7 mA Input delay * At "0" to "1" transition * At "1" to "0" transition Typ. 3 ms Typ. 3 ms Input characteristics According to IEC 61131-2, Type 1 Connection of 2-wire BEROs Supported * Max. 1.5 mA Permitted quiescent current Actuator selection data Output voltage at "1" signal Min. 2L+ (-0.8 V) Output current * at "1" signal 2A * at "0" signal (residual current) Max. 0.5 mA Load resistance range 18.5 to 4 k Lamp load Max. 10 W Wiring 2 outputs in parallel * for redundant load control Supported * For performance increase Not supported Control of a digital input Supported Switching frequency * with resistive load Max. 100 Hz * with inductive load to IEC 947-5-1, DC13 Max. 0.5 Hz * with lamp load Max. 1 Hz Internal limiting of the inductive shutdown voltage to Typ. 2L+ (-44 V) Short-circuit protection of output Yes, electronic * Response threshold Typ. 4 A per channel 1 4 A total current for sockets X1, X3, X5, X7 and 4 A total current for sockets X2, X4, X6 and X8. 2 Observe the current carrying capacity of the cable ET 200eco Distributed I/O Device 90 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.9 I/O module 8 DI / 8 DO 1.3A (6ES7143-3BH10-0XA0) 8.9 I/O module 8 DI / 8 DO 1.3A (6ES7143-3BH10-0XA0) Properties Properties of the I/O module 8 DI / 8 DO 1.3A: 8 digital inputs Rated input voltage 24V DC Suitable for switches and proximity switches (BEROs) 8 digital outputs Output current 1.3 A per output Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and indicator lights Terminal assignment of the DI sockets The table below shows the terminal assignment of the eight sockets for connection of the digital inputs and digital outputs. Table 8- 9 Pin-out of the digital I/O sockets X1 to X8 Assignment Front view of the socket Pin Socket X1 Socket X2 Socket X3 Socket X4 1 24 V sensor supply n.c. 24 V sensor supply n.c. 2 Input signal channel 1 Output signal channel 1 Input signal channel 3 Output signal channel 3 3 Ground for sensor supply Load voltage supply ground Ground for sensor supply Load voltage supply ground 4 Input signal channel 0 Output signal channel 0 Input signal channel 2 Output signal channel 2 5 PE Pin Socket X5 Socket X6 Socket X7 Socket X8 1 24 V sensor supply n.c. 24 V sensor supply n.c. 2 Input signal channel 5 Output signal channel 5 Input signal channel 7 Output signal channel 7 3 Ground for sensor supply Load voltage supply ground Ground for sensor supply Load voltage supply ground 4 Input signal channel 4 Output signal channel 4 Input signal channel 6 Output signal channel 6 5 PE ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 91 Technical specifications 8.9 I/O module 8 DI / 8 DO 1.3A (6ES7143-3BH10-0XA0) Block diagram The block diagram below shows the I/O module 8 DI / 8 DO 1.3A. Figure 8-8 Block diagram of I/O module 8 DI / 8 DO 1.3A ET 200eco Distributed I/O Device 92 Operating Instructions, 08/2014, A5E00158716-AD Technical specifications 8.9 I/O module 8 DI / 8 DO 1.3A (6ES7143-3BH10-0XA0) Technical specifications of the I/O module 8 DI / 8 DO 1.3A Technical specifications Dimensions and weight Dimensions W x H x D (mm) 60 x 210 x 28 Weight Approx. 210 g Module-specific data Transmission rates 9.6/19.2/45.45/93.75/187.5/500 kBaud 1.5/3/6/12 MBaud Bus protocol PROFIBUS DP Number of channels 8 digital inputs and 8 digital outputs Cable length * Max. 30 m unshielded Manufacturer ID 80FCH Voltages, currents, potentials Rated electronics / sensor supply voltage 1L+ * Reverse polarity protection 2L+ rated load voltage * 24 V DC Yes Reverse polarity protection Number of simultaneously controllable inputs * 24 V DC Yes 8 up to 55 C All mounting positions Total current of the outputs * 5.2 A1) up to 55 C All mounting positions Electrical isolation No * Between channels * between PROFIBUS DP and all other circuitry Yes Permitted potential difference * Between different electric circuits Isolation test voltage 75 V DC, 60 V AC 500 V DC Current consumption * From supply voltage 1L+ * from 2L+ rated load voltage Typ. 70 mA Typ. 60 mA Power loss of the module Typ. 5 W Status, interrupts, diagnostics Status display green LED per channel Alarms No Diagnostic functions * Group error display red LED (SF) * Channel error display No * Diagnostic information can be read Supported ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 93 Technical specifications 8.9 I/O module 8 DI / 8 DO 1.3A (6ES7143-3BH10-0XA0) Technical specifications Sensor supply outputs Number of outputs 8 Output current Up to 55 C max. 1 A (total current) Short-circuit protection Yes, electronic Sensor selection data Input voltage * Rated value * for "1" signal * for "0" signal 24 V DC 13 to 30 V -3 to 5 V Input current * at "1" signal * at "0" signal Typ. 7 mA Input delay * At "0" to "1" transition * At "1" to "0" transition Typ. 3 ms Typ. 3 ms Input characteristics According to IEC 61131-2, Type 1 Connection of 2-wire BEROs Supported * Max. 1.5 mA Permitted quiescent current Actuator selection data Output voltage at "1" signal Min. 2L+ (-1.2 V) Output current * at "1" signal 1.3 A * at "0" signal (residual current) Max. 0.5 mA Load resistance range 18.5 to 4 k Lamp load Max. 10 W Wiring 2 outputs in parallel * for redundant load control Supported * For performance increase Not supported Control of a digital input Supported Switching frequency * with resistive load Max. 100 Hz * with inductive load to IEC 947-5-1, DC13 Max. 0.5 Hz * with lamp load Max. 1 Hz Internal limiting of the inductive shutdown voltage to Typ. 2L+ (-44 V) Short-circuit protection of output Yes, electronic * 1 Response threshold Typ. 4 A per channel Observe the current carrying capacity of the cable. ET 200eco Distributed I/O Device 94 Operating Instructions, 08/2014, A5E00158716-AD A Appendix A.1 Article numbers Introduction The tables below show the article numbers of all components of the ET 200eco automation system. ET 200eco components Table A- 1 ET 200eco components - article numbers Description Article number I/O module 8 DI DC 24V; 8 X M12 6ES7141-3BF00-0XA0 I/O module 16 DI DC 24V; 8 X M12 6ES7141-3BH00-0XA0 I/O module 8 DO DC 24V/2A; 8 X M12 6ES7142-3BF00-0XA0 I/O module 16 DO DC 24V/0,5A; 8 X M12 6ES7142-3BH00-0XA0 I/O module 8 DI / 8 DO DC 24V/2A; 8 X M12 6ES7143-3BH00-0XA0 I/O module 8 DI / 8 DO DC 24V/1,3A; 8 X M12 6ES7143-3BH10-0XA0 Terminal block M12, 7/8" 6ES7194-3AA00-0BA0 ECOFAST terminal block 6ES7194-3AA00-0AA0 ET 200eco accessories Table A- 2 ET 200eco accessories - article numbers Description Article number Labels 20 mm x 7 mm 3RT1900-1SB2 ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 95 Appendix A.1 Article numbers Accessories for I/O modules Table A- 3 Accessories for I/O modules - article numbers Description Article number Pre-assembled cables: * M12 connecting cable (PUR sheath), pre-assembled, socket and connector on both ends, 3 x 0.34 mm2 1.5 m 3RK1902-4PB15-3AA0 * M12 connecting cable (PUR sheath), 5 x 0.34 mm2, pre-assembled with socket on one end (socket on one end, other end open) 1.5 m 3RK1902-4HB15-5AA0 5.0 m 3RK1902-4HB50-5AA0 10.0 m 3RK1902-4HC01-5AA0 Miscellaneous: M12 caps 3RX9802-0AA00 * Y-cable for connection of two I/Os 6ES7194-6KA00-0XA0 * Y-connector M12, 5-pin (for the connection of two actuators and sensors to digital I/Os). 6ES7194-1KA01-0XA0 * M12 connector, 5-pin, max. 0.75 mm2, screw terminals 3RK1902-4BA00-5AA0 * M12 connector, angular, 5-pin, max. 0.75 mm2, screw terminals 3RK1902-4DA00-5AA0 * 3RK1901-1KA00 ET 200eco Distributed I/O Device 96 Operating Instructions, 08/2014, A5E00158716-AD Appendix A.1 Article numbers Accessories for the ECOFAST terminal block Table A- 4 Accessories for the ECOFAST terminal block - article numbers Description Article number Pre-assembled cables * * ECOFAST hybrid cable (2 x Cu and 2x2 Cu, O 1.5 mm2 ), pre-assembled with ECOFAST connector, trailable PROFIBUS ECOFAST hybrid cable GP, cable with 4xCu and 2xCu, shielded, pre-assembled with 2 ECOFAST connectors, trailable 0.5 m 6XV1830-7BH05 1.0 m 6XV1830-7BH10 1.5 m 6XV1830-7BH15 3.0 m 6XV1830-7BH30 5.0 m 6XV1830-7BH50 10.0 m 6XV1830-7BN10 15.0 m 6XV1830-7BN15 20.0 m 6XV1830-7BN20 25.0 m 6XV1830-7BN25 30.0 m 6XV1830-7BN30 35.0 m 6XV1830-7BN35 40.0 m 6XV1830-7BN40 45.0 m 6XV1830-7BN45 50.0 m 6XV1830-7BN50 0.5 m 6XV1860-3PH05 1.0 m 6XV1860-3PH10 1.5 m 6XV1860-3PH15 3.0 m 6XV1860-3PH30 5.0 m 6XV1860-3PH50 10.0 m 6XV1860-3PN10 15.0 m 6XV1860-3PN15 20.0 m 6XV1860-3PN20 25.0 m 6XV1860-3PN25 30.0 m 6XV1860-3PN30 35.0 m 6XV1860-3PN35 40.0 m 6XV1860-3PN40 45.0 m 6XV1860-3PN45 50.0 m 6XV1860-3PN50 ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 97 Appendix A.1 Article numbers Description Article number Hybrid cable (for assembly by the customer) Connectors (not pre-assembled): * PROFIBUS ECOFAST Hybrid Plug 180 (ECOFAST Cu), 5 pieces female contact insert (for loop-through) 6GK1905-0CB00 * PROFIBUS ECOFAST Hybrid Plug 180 (ECOFAST Cu), female contact insert (angular) 6GK1905-0CD00 * PROFIBUS ECOFAST Hybrid Plug 180 (ECOFAST Cu), 5 pieces pin insert (for loop-through) 6GK1905-0CA00 * PROFIBUS ECOFAST Hybrid Plug 180 (ECOFAST Cu), pin insert (angular) 6GK1905-0CC00 Cables (not pre-assembled): * ECOFAST hybrid cable (2 x Cu, and 2x2 Cu), cut to length 6XV1830-7AH10 * ECOFAST hybrid cable, not pre-assembled (2 x Cu, and 20 m 2x2 Cu) 50 m 6XV1830-7AN20 100 m * PROFIBUS ECOFAST hybrid cable GP, trailable cable with 4xCu and 2xCu, shielded, cut to length (max. delivery length 1000 m) * PROFIBUS ECOFAST hybrid cable GP, trailable cable with 4xCu and 2xCu, shielded 6XV1830-7AN50 6XV1830-7AT10 6XV1860-2P 20 m 6XV1860-4PN20 50 m 6XV1860-4PN50 100 m 6XV1860-4PT10 Miscellaneous * Configuration connector for setting the PROFIBUS address (spare part) 1 piece 6ES7194-1KB00-0XA0 * ECOFAST terminating resistor for PROFIBUS DP 1 piece 6GK1905-0DA10 5 pieces 6GK1905-0DA00 * ECOFAST caps 10 pieces 6ES7194-1JB10-0XA0 ET 200eco Distributed I/O Device 98 Operating Instructions, 08/2014, A5E00158716-AD Appendix A.1 Article numbers Accessories for the M12, 7/8" terminal block Table A- 5 Accessories for the M12, 7/8" terminal block - article numbers Description Article number Pre-assembled cables * * * * * 0.3 m 6XV1822-5BE30 0.5 m 6XV1822-5BE50 1.0 m 6XV1822-5BH10 1.5 m 6XV1822-5BH15 2.0 m 6XV1822-5BH20 3.0 m 6XV1822-5BH30 5.0 m 6XV1822-5BH50 10.0 m 6XV1822-5BN10 15.0 m 6XV1822-5BN15 7/8" connecting cable for power supply, trailable power line, 5 x 1.5 mm2, pre-assembled on one end with 7/8" connector with female contact insert, angular (socket at one end, other end open) 3.0 m 3RK1902-3GB30 5.0 m 3RK1902-3GB50 10.0 m 3RK1902-3GC10 7/8" connecting cable for power supply, trailable power line, 5 x 1.5 mm2, both ends prefabricated with 7/8" connectors, angular (socket at one end, pin at other end) 3.0 m 3RK1902-3NB30 5.0 m 3RK1902-3NB50 10.0 m 3RK1902-3NC10 PROFIBUS M12 connecting cable, trailable cable pre-assembled at both ends with PROFIBUS M12 connectors 180 (socket on one end, pin on the other end) 0.3 m 6XV1830-3DE30 0.5 m 6XV1830-3DE50 1.0 m 6XV1830-3DH10 1.5 m 6XV1830-3DH15 2.0 m 6XV1830-3DH20 3.0 m 6XV1830-3DH30 5.0 m 6XV1830-3DH50 10.0 m 6XV1830-3DN10 15.0 m 6XV1830-3DN15 3.0 m 3RK1902-1NB30 5.0 m 3RK1902-1NB50 10.0 m 3RK1902-1NC10 Cable 5x1.5 mm2 for the supply voltage, pre-assembled with 7/8" connectors PROFIBUS M12 connecting cable, trailable cable preassembled at both ends with PROFIBUS M12 connectors, angular (socket on one end, pin on the other end) ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 99 Appendix A.1 Article numbers Description Article number Cable (for assembly by the customer) Connectors (not pre-assembled): * 7/8" connector, angular, with female contact insert 3RK1902-3DA00 * 7/8" connector, angular, with pin insert 3RK1902-3BA00 * PROFIBUS M12 connector, axial cable outlet, female contact insert (B-coded) 5 pieces 6GK1905-0EB00 * PROFIBUS FastConnect, M12 connector with rugged metal enclosure, axial cable outlet, for use with ET 200pro, female contact insert (B-coded) 5 pieces 6GK1905-0EB10 * M12 connection plug for ET 200 with axial cable outlet, for fabrication in the field, pin insert 5 pieces 6GK1905-0EA00 * PROFIBUS FastConnect, M12 connector with rugged metal enclosure, axial cable outlet, for use with ET 200pro, pin insert (B-coded) 5 pieces 6GK1905-0EA10 * 7/8" connection plug with axial cable outlet, for fabrication in the field, for ET 200, pin insert 5 pieces 6GK1905-0FA00 * 7/8" connection plug with axial cable outlet, for fabrication in the field, for ET 200, female contact insert 5 pieces 6GK1905-0FB00 Cables (not pre-assembled): * Power cable, trailable power cable, 5 x 1.5 mm2 6XV1830-8AH10 * PROFIBUS FC standard cable (minimum order quantity 20 m) 6XV1830-0EH10 * PROFIBUS FC rugged cable (minimum order quantity 20 m) 6XV1830-0JH10 * PROFIBUS FC food cable (minimum order quantity 20 m) 6XV1830-0GH10 * PROFIBUS FC trailing cable (minimum order quantity 20 m) 6XV1830-3EH10 * FC FRNC cable (FRNC sheath) 6XV1830-0LH10 * FC underground cable 6XV1830-3FH10 * Festoon cable GP (PVC sheath) 6XV1830-3GH10 * FC flexible cable GP (PUR sheath) 6XV1831-2K Miscellaneous * 3RX9802-0AA00 M12 caps 3RK1901-1KA00 * M12 terminating resistor for PROFIBUS DP 5 pieces 6GK1905-0EC00 * 7/8" caps 10 pieces 6ES7194-3JA00-0AA0 ET 200eco Distributed I/O Device 100 Operating Instructions, 08/2014, A5E00158716-AD Appendix A.1 Article numbers Technical reference to PROFIBUS DP with SIMATIC S7 and STEP 7 Table A- 6 Technical reference to PROFIBUS DP and SIMATIC S7 Technical reference Article numbers Distributed configuration with PROFIBUS DP Commercial book number: Instruction manual for getting ISBN 3-89578-123-1 started with PROFIBUS DP and with the implementation of auAt your local SIEMENS tomation tasks using office: PROFIBUS DP and A19100-L531-B772 SIMATIC S7. - Aufbau, Projektierung und Einsatz des PROFIBUS-DP mit SIMATIC S7- (Structure, configuration, and use of PROFIBUS DP with SIMATIC S7) Josef Weigmann, Gerhard Kilian Publicis MCD Verlag, 2nd Edition, 2000 Contents Shows many practical application examples of PROFIBUS DP applications based on SIMATIC S7. ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 101 Appendix A.2 Dimensional drawings A.2 Dimensional drawings Introduction The section below shows the dimension drawings of the most important components of ET 200eco. I/O module installed with M12, 7/8" terminal block Figure A-1 Dimension drawing of the I/O module installed with M12, 7/8" terminal block ET 200eco Distributed I/O Device 102 Operating Instructions, 08/2014, A5E00158716-AD Appendix A.3 I/O address space I/O module installed with ECOFAST terminal block Figure A-2 Dimension drawing of the I/O module installed with ECOFAST terminal block ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 103 Appendix A.3 I/O address space A.3 I/O address space I/O module 8 DI Assignment in the process image of inputs per module: Figure A-3 Address space of I/O module 8 DI ET 200eco Distributed I/O Device 104 Operating Instructions, 08/2014, A5E00158716-AD Appendix A.3 I/O address space I/O module 16 DI Assignment in the process image of inputs per module: Figure A-4 Address space of I/O module 16 DI ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 105 Appendix A.3 I/O address space I/O module 8 DO 2A Assignment in the process image of outputs per module: Figure A-5 Address space of I/O module 8 DO 2A ET 200eco Distributed I/O Device 106 Operating Instructions, 08/2014, A5E00158716-AD Appendix A.3 I/O address space I/O module 16 DO 0.5A Assignment in the process image of outputs per module: Figure A-6 Address space of I/O module 16 DO 0.5A ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 107 Appendix A.3 I/O address space I/O module 8 DI / 8 DO 2A Assignment in the I/O process image per module: Figure A-7 Address space of I/O module 8 DI / 8 DO 2A: ET 200eco Distributed I/O Device 108 Operating Instructions, 08/2014, A5E00158716-AD Appendix A.3 I/O address space I/O module 8 DI / 8 DO 1.3A Assignment in the I/O process image per module: Figure A-8 Address space of I/O module 8 DI / 8 DO 1.3A: ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 109 Glossary ECOFAST (Energy and Communication Field Installation System) System for the extensive decentralization and modularization of the installation and comprehensive diagnostics on the component level. ET 200eco Distributed I/O device with block I/Os structural-design technology. Grounding Grounding involves connecting an electrically conductive part with the ground electrode via a metallic conductor. I/O module Sensors and actuators are connected via a coupler plug or Y-connector to the I/O module. PE sheath Cable with sheath (protective covering) made of polyethylene (PE) PE sheath Cable with sheath (protective covering) made of polyethylene (PE) T functionality This functionality is integrated in each terminal block and loops the PROFIBUS DP and the voltage supply through to the next PROFIBUS node. Result: If you remove the terminal block during operation, the downstream PROFIBUS nodes will not fail. Terminal block Pluggable module for switching the connection method. Available in ECOFAST versions and M12, 7/8". ET 200eco Distributed I/O Device 110 Operating Instructions, 08/2014, A5E00158716-AD Glossary Voltage designations ECOFAST Alternative voltage designations for ECOFAST: Electronic / Sensor supply (1L+) = Load voltage not connected (l.v.) Load voltage supply (2L+) = connected load voltage (V) ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 111 Index 2 24 V DC supply, 20 A Additional support, 4 Article numbers, 95 Technical reference to PROFIBUS DP with SIMATIC S7 and STEP 7, 101 B Base module BM 141-ECOFAST 8DI Technical specifications, 68 Basic knowledge requirements, 3 Burst pulses, 61 C CE Label, 60 Climatic environmental conditions, 63 Commissioning, 47 Components and protective measures, 21 Configuration, 47 electrical, 24 ET 200eco, 47 Continuous shock, 64 D Definition Electromagnetic compatibility, 61 Station status, 56 Diagnostics, 47 Disabling, 53 ID-specific, 59 Reading, 53 with STEP 7, 53 Diagnostics by LED Display, 50 Dimension drawings, 102 Disposal, 4 DP master, 8 DP slave, 8 Dual connection of actuators/sensors, 33 E ECOFAST connectors Connecting, 39 Wiring, 38 Electrical configuration, 24 Electrical isolation between..., 23 Electromagnetic compatibility, 61 Electrostatic discharge, 61 EMC, 61 EMERGENCY OFF equipment, 20 Emission of radio interference, 62 ET 200eco, 21, 23, 47 Configuration, 47 operating on grounded mains, 21, 23 Status and error displays, 51 ET 200eco components, 11 ET 200eco Distributed I/O System Definition, 10, 11 Field of application, 10 View, 10 F FB 230, 53 Field of application, 8 Fuse external, 26 G General rules, 20 Grounded mains, 21 GSD file, 47 Guide to the manual, 4 I I/O module 16 DI Block diagram, 76 Pin assignment:digital inputs, 75, 75 ET 200eco Distributed I/O Device 112 Operating Instructions, 08/2014, A5E00158716-AD Index Terminal assignment of the M12 circular connector, 30 Terminal assignment of the Y-connector, 35 I/O module 16 DO 0.5A Block diagram, 84 Pin assignment:digital inputs, 83, 83 Terminal assignment of the M12 circular connector, 31 Terminal assignment of the Y-connector, 35 I/O module 8 DI Block diagram, 72 Pin assignment:digital inputs, 71, 71 Terminal assignment of the M12 circular connector, 29 I/O module 8 DI / 8 DO 1.3A Block diagram, 92 Pin assignment:digital inputs, 91, 91 Terminal assignment of the M12 circular connector, 32 Terminal assignment of the Y-connector, 36 I/O module 8 DI / 8 DO 2A Block diagram, 88 Pin assignment:digital inputs, 87, 87 Terminal assignment of the Y-connector, 36 I/O module 8 DO / 8 DI 2A Terminal assignment of the M12 circular connector, 31 I/O module 8 DO 2A Block diagram, 80 Pin-out, 79, 79 Terminal assignment of the M12 circular connector, 30 ID-specific diagnostics, 59 IEC 204, 20 IEC 61131-2, 60 Installing, 13 Insulation test, 65 Integrating the GSD file in the configuration software, 47 M M12 connector Connecting, 29 M12, 7/8" terminal block Wiring, 41 Manual Purpose, 3, 3 Manufacturer ID Configuration, 58 Master PROFIBUS address Configuration, 57 Mechanical environmental conditions, 63 Mounting dimensions, 12 Mounting position, 12 O Overall configuration on TN-S mains, 23 P Pollution degree, 65 PROFIBUS DP, 8, 9 Devices, 9 PROFIBUS DP network Configuration, 9 PROFIBUS standard, 60 Protection against external electrical interference, 21 Protection class, 65 Pulse-shaped disturbance, 61 R Rated voltage, 66 Readership of this manual, 4 Recycling, 4 Regulations, 20 S Safety isolation, 22 Scope of this manual, 3 Setting the PROFIBUS address, 17 SFC 13 DPNRM_DG, 53, 54 Shipping conditions, 61 Shock, 64 Sinusoidal disturbance, 61 Slave diagnostics, 53 Configuration of extended slave diagnostics, 55 Specifications, 67 Standard EN 50170, Volume 2, PROFIBUS, 9 Standards and certifications, 60 Startup of ET 200eco, 49 Startup of the system after certain events, 20 Station status Configuration, 56 Definition, 56 Status and error displays, 51 ET 200eco, 51 ET 200eco Distributed I/O Device Operating Instructions, 08/2014, A5E00158716-AD 113 Index Storage conditions, 61 support additional, 4 T Technical specifications Climatic environmental conditions, 63 ECOFAST terminal block, 68 Electromagnetic compatibility, 61 I/O module 16 DI, 77 I/O module 16 DO 0.5A, 85 I/O module 8 DI, 73 I/O module 8 DI / 8 DO 1.3A, 93, 93 I/O module 8 DI / 8 DO 2A, 89, 89 I/O module 8 DO 2A, 81 M12, 7/8" terminal block, 70 Mechanical environmental conditions, 63 Shipping and storage conditions, 61 Temperature, 62 Terminating resistor, 40, 44 Test voltage, 65 TN-S mains, 23 V Vibration, 64 W Wiring Procedure, 27 Wiring, 20 Y Y-connector, 33 Connecting, 34 ET 200eco Distributed I/O Device 114 Operating Instructions, 08/2014, A5E00158716-AD