MODEL NUMBERS CWD4810 CWD4825 CWD4850
OUTPUT SPECIFICATIONS
Operating Voltage (47-63 Hz) [Vrms] 48-660 48-660 48-660
Load Current Range [Arms] 0.15-10 0.15-25 0.15-50
Transient Overvoltage [Vpk] 1200 1200 1200
Max. Surge Current (16.6ms) [Apk] 400 600 850
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.3 1.3 1.3
Thermal Resistance Junction to Case (R ) [˚C/W]
θJC 0.35 0.35 0.2
Maximum I2 t for Fusing, (10 ms) [A 2s] 720 1620 3280
Max. Off-State Leakage Current @ Rated Voltage [mA] 1.0 1.0 1.0
Min. Off-State dv/dt @ Max. Rated Voltage [V/µs] 500 500 500
Max. Turn-On Time 1/2 Cycle 1/2 Cycle 1/2 Cycle
Max. Turn-Off Time 1/2 Cycle 1/2 Cycle 1/2 Cycle
Power Factor (Min.) with Max. Load 0.5 0.5 0.5
INPUT SPECIFICATIONS
Control Voltage Range 4-32 Vdc
Max. Turn-On Voltage 4 Vdc
Min. Turn-Off Voltage 1.0 Vdc
Nominal Input Impedence See note 7
Typical Input Current 10 mA @ 12 Vdc
All parameters at 25˚C unless otherwise specified.
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
Heat sinking required, for derating curves see page 2.
GENERAL NOTES
SERIES CW48
Rev. 081803
PAGE 1 OF 3
The Series CW48 has an SCR AC switch
output featuring low off-state leakage
(1mA, snubberless), zero and random
voltage switching and a broadened
operating range (48-660Vac).
This wide range permits optimum
perfomance at voltages from 240 Vac to
600 Vac line voltages.
Manufactured in Crydom's ISO 9001
Certified facility for optimum product
performance and reliability.
© 2003 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
Turn-on time for random turn-on version is 0.02 msec.
Turn-on and turn-off time for AC input models is 50ms.
CWA4810 CWA4825 CWA4850
DC Control
18-36 Vrms
18 Vrms
2 Vrms
AC Control
90-280 Vrms
90 Vrms
10 Vrms
21.5 k ohms
6 mA @ 120 Vrms
AC Control
24 Vac nominal 120/240Vac nominal
Input circuit incorporates active current limiter.
10mA for models with snubber.
E - suffix Std. (no suffix)
1 k ohm
24mA@24Vrms
CWD4890 CWD48125
48-660 48-660
0.25-90 0.25-125
1200 1200
1350 2000
1.3 1.25
0.14 0.13
8320 18000
1.0 1.0
500 500
1/2 Cycle 1/2 Cycle
1/2 Cycle 1/2 Cycle
0.5 0.5
CWA4890 CWA48125
Max. Surge Current (20ms) [Apk] 380 570 810 1290 1900
Maximum I 2 t for Fusing, (8.3 ms) [A 2s] 660 1500 3000 7560 16600
C
W
48
10
-
125
A
m
p
-
600
V
ac
-
A
C
O
U
T
P
U
T
1200V Blocking
Low Leakage
SCR Output
Zero and Random
Voltage Switching
LED Status Indicator
Panel Mount
Intergrated Removable
Fingerproof Cover
User Friendly, Universal
Connectors
EMC Compliant Design
48-530 Vrms for models with snubber.
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base 4000 Vrms
Insulation Resistance (Min.) @ 500 Vdc 109Ohm
Max. Capacitance Input/Output 8 pF
Ambient Operating Temperature Range -40 to 80˚C
Ambient Storage Temperature Range -40 to 125˚C
MECHANICAL SPECIFICATIONS
Weight: (typical) 3.0 oz. (86.5g)
Encapsulation Thermally Conductive Epoxy
Terminals Screw Type, Finger Proof
Crydom Heat Sinks offer excellent ther-
mal management and are perfectly
matched to the load current ratings of
Crydom panel mount relays. Request
Crydom's Heat Sink specification sheet
for all the details.
SERIES CW48
Rev. 081803
PAGE 2 OF 3
© 2003 CRYDOM CORP, Specifications subject to change without notice.
Available Options
-10 Random Turn-On.
Example: CWD4825-10
All dimensions are in inches (millimeters)
1.87
(47.5)
2.30
(58.4)
1.70
(43.2)
1.30
(33.0)
.45
(11.4)
1.10
(27.9)
1.00
(25.4)
1.
80
(
45.7
)
3/A1
4/A2 +
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
BASE PLATE
.125 (3.2)
Max. Torque
1/L1 2/T1
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
E24 Vac Input (18-36 Vac)
Example: CWA4825E
PInternal Overvoltage Protection.
Relay Will Self Trigger Between
900-1200 Vpk. Not Suitable For Capacitive Loads.
Example: CWD4825P
APPROVALS
UL E116949
CSA 1405925
VDE 40007242
Max. Wire Size Output: 2 x AWG 8 (3.8mm)
Input: 2 x AWG 12 (2.5mm)
SInternal Snubber Example: CWD4825S
EMC Compatibility
Input: EN61000-4-2, Level 3
EN61000-4-4, Level 3
Output: EN61000-4-2, Level 3
EN61000-4-4, Level 3
EN61000-4-5, Level 4
Output: 20 in lb (2.2Nm)
Input: 10 in lb (1.1Nm)
Level 4
Level 4
ESD
ESD
Burst
ESD (with P option)
Burst
Burst (with P option)
Surge
10
-
125
A
m
p
-
600
V
ac
-
A
C
O
U
T
P
U
T
Output: 8-32, Combo Drive
Input: 6-32, Combo Drive
MECHANICAL OUTLINE
OUTPUT
INPUT
C
W
48
HHeat Trasfer Pad (Attached)
Example: CWD4825H
SERIES CW48
Rev. 081803
PAGE 3 OF 3
© 2003 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com
WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
8
4
024 8106 20406080
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
121
123
120
Base Plate Temp [˚C]
10A
9˚C/W 7˚C/W 20
10
25
15
5
0510 202515 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
123
Base Plate Temp [˚C]
25A
2˚C/W 116
120
4˚C/W 50
40
20
010 20 40 5030 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
115
Base Plate Temp [˚C]
50A
1.5˚C/W
.1˚C/W
119
121
123
2˚C/W
80
40
020 40 80 060 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
118
121
124
Base Plate Temp [˚C]
90A
1˚C/W
.4˚C/W
.5˚C/W
3˚C/W
CURRENT DERATING CURVES
2
6
10
10
30
117
20
60
100
115
112
120
60
40
100
030 60 120 090 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
117
120
122
Base Plate Temp [˚C]
125A
.5˚C/W
1˚C/W
.4˚C/W
20
80 115
112
109
130
10
-
125
A
m
p
-
600
V
ac
-
A
C
O
U
T
P
U
T
C
W
48