https://www.phoenixcontact.com/us/products/2910337
05/19/2021Page2/6
Type 1 surge protection plug-VAL-US-240D/40-P-2910337
Technical data
Dimensions
Depth 55.3 mm
Horizontal pitch 1 Div.
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification II
T2
EN type T2
Mode of protection L-L
L-PEN
Mounting type on base element
Color jet black RAL 9005
Housing material PA 6.6
PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type Male
Number of positions 1
Surge protection fault message optical
Protective circuit
Nominal voltage UN240/415VAC (TN)
Nominal frequency fN50 Hz (60Hz)
Maximum continuous voltage UC275 VAC
Residual current IPE ≤ 450 µA
Standby power consumption PC≤ 120 mVA
Nominal discharge current In (8/20) µs 20 kA
Maximum discharge current Imax (8/20) µs 40 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up≤ 1.35 kV