Lorem ipsum dolor sit amet
Lorem ipsum dolor sit amet
Flexible
options for
every application
Rotary disconnect switches
Eatons new line of rotary disconnects provides OEM customers with a
flexible product offering that has industry-leading fault current ratings.
The product range encompasses both the ULT 98 and UL 508 standards, and is the latest in a series
of new and innovative products from the switching device product line.
The R5 (Rotary 508) Series of switches are UL 508 listed devices that are suitable for use as motor
disconnects. Ideal for panel builders and custom control cabinets, the R5 Series is excellent for isolation
of circuits in panels, or as enclosed motor disconnects when located downstream from appropriate
overcurrent protection.
This totally new line of products incorporates a truly modular design,
allowing for simple addition of fourth poles, neutral modules, auxiliary
contact modules and many other popular accessories.
Additionally, when protected by applicable upstream fusing, these products can be rated up to
65 kAIC—one of the highest short-circuit ratings in the industry. The R5 switches are available
in two frame sizes—A-Frame (16–40A) and B-Frame (60–80A).
The R9 (Rotary 98) product offering consists of UL 98 listed fusible and non-fusible products that
may be used as service entrance devices, or anywhere a local means of disconnect is needed or
required. Both the fusible and non-fusible products span six frame sizes, or footprints, and have
100 kAIC or 200 kAIC ratings.
The R9 offering includes a modular grouping of non-fusible switches
at the low end of the range (30–100A), providing a compact, flexible
solution where physical space is a concern.
As with the UL 508 products, these units allow for simple addition of fourth pole modules, neutral
modules and other accessories. The balance of the line includes two-, three- and four-pole devices
for safe isolation of any low voltage circuit. Further, the fusible products employ double-break-per-pole
functionality, a safety feature that fully isolates the fusing when the switch is in the OFF position.
In addition to the R5 and R9 products, the new offering also includes a series of smaller footprint 30A,
fusible molded-case switch disconnects in a compact design. These R4 (Rotary 489) units are listed to
UL 489, and provide a small overcurrent device with short-circuit ratings of 100 kAIC.
The R5, R9 and R4 products have available new, state-of-the-art selector and pistol handle designs to
give the final installation an up-to-date, professional look. In addition to the new handles, each offering
includes an entirely new line of shafts, auxiliary contacts, terminal shields and other accessories.
Powering business worldwide
Eaton delivers power in thousands of products and
systems that are answering the demands of todays
ever-changing world. We help customers manage
power needed for trucks, cars, machinery, aircraft,
buildings and entire business enterprises worldwide—
and we do it in a way that consumes fewer resources.
R5 Series Non-Fusible
UL 508 (CSA 22.2 No.14)
16–80A
See page 5
R9 Series Non-Fusible—Compact
UL 98 (CSA 22.2 No.4)
30A, 60A and 100A
See page 13
R9 Series Non-Fusible
UL 98 (CSA 22.2 No.4)
100–1200A
See page 20
R9 Series Fusible
UL 98 (CSA 22.2 No.4)
30–800A
See page 28
R9 Series DC Rated
UL 98 (CSA 22.2 No.4)
See page 47
MTS—Manual
Transfer Switches
See page 55
Enclosed Rotary
Disconnects (R5)
See page 64
Switching Devices PG00802002E—September 2012 www.eaton.com 1
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Switching Devices
Switching Devices
UL®/CSA® Standards for Disconnect Switches . . . . . . . . . . . . . . . . . . 2
R5 Series (UL 508) Non-Fusible 16–80A
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
R9 Series (UL 98) Non-Fusible 30–1200A
30–100A (Compact)
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
100–1200A
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
R9 Series (UL 98) Fusible 30–800A
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
R9 Series (UL 98) DC Rated Disconnects
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
MTS—Manual Transfer/Double Throw Switches
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Enclosed Rotary Disconnects
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Switching Devices
Introduction
Contents
Description Page
UL/CSA Standards for Disconnect Switches . . . . . 2
UL Standards for Electrical Machinery . . . . . . . . . . 2
Eaton Solutions for UL 508 and NFPA 79 . . . . . . . 3
UL®/CSA® Standards for
Disconnect Switches
UL 98—Enclosed and
Deadfront Switches
(CSA C22.2 No. 4)
These requirements cover
enclosed or deadfront
switches, with or without
provision for fuses, at 600V
or less. These products are
used as disconnecting means
without restrictions; they are
heavy-duty products requiring
2.00 inches (50.0 mm)
minimum of creepage
distance between phases,
which gives maximum safety
for users and installation.
The short-circuit withstand
of those products goes up
to 200 kA.
UL 489—Molded Case
Switches (CSA C22.22 No. 5)
These requirements cover
molded case circuit breakers,
molded case switches and
fused molded case switches,
rated at 600V or less and
6000A or less.
Typical Control Panel UL Standards for Electrical
Machinery
UL 508—Industrial Control
Equipment (CSA C22.2 No. 14)
These requirements cover
manual, magnetic and solid-
state starters and controllers,
overload relays, pushbuttons,
selector switches and
control lights.
These products are smaller,
requiring only a creepage
distance between phases
of 0.50 inch (12.7 mm).
Their use as a disconnecting
means is limited to local
disconnection of motors.
These products can be used
as a disconnect means only
when they have been
additionally tested “suitable
as motor disconnect.” This
additional testing ensures
that the switch has a proper
closing capacity on a short
circuit. UL 508 devices
cannot be used as main
disconnect of an electrical
panel, e.g., at the entrance
of control panels.
A manual motor controller
marked “suitable as motor
disconnect” shall be installed
only on the load side of
the branch circuit protective
device [UL 508A 30.33
and NEC 430.109 (6)].
NFPA® 79 Electrical
Standard for Industrial
Machinery
The following types of
machines are identified
as industrial machinery:
Metalworking machine
tools, including machines
that cut or form metal
Plastics machinery
Wood machinery, including
woodworking, laminating
and sawmill machines
Assembly machines
Material handling
machines, including
industrial robots and
transfer machines
Inspection and testing
machines, including
coordinate measuring
and in-process
gauging machines
UL 98 or UL 489
Non-Fusible
Disconnect Switches
or
Fusible Disconnect
Switches
UL 508
Non-Fusible Switches
Switching Devices PG00802002E—September 2012 www.eaton.com 3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
Introduction
Eaton solutions for UL 508A and NFPA 79
The changes in UL 508A and NFPA 79 impact the design and
construction of your equipment. Important modifications concern
major safety issues, the disconnect means and the interlocking
of the enclosure door.
The disconnect shall be operable independent of the door position.
The disconnect must be operable, by qualified persons,
independent of the door position without the use of accessory
tools or devices.
Note: NFPA 79; Paragraph 5.3.3.1 (5) T.
An operating mechanism for the disconnecting means shall be
operable independent of the door position without the use of
accessory tools or devices.
Note: UL 508A; Paragraph 66.6.3 c.
The disconnect means is not closable with the enclosure door open,
unless an interlock is operated by deliberate action.
The interlocking means shall fulfill the following requirement:
Prevent closing of the disconnect means while the enclosure
door is open, unless an interlock is operated by deliberate action.
Note: NFPA 79; Paragraph 6.2.3.1.2.
The disconnecting means is not closable with the enclosure
door open, unless an interlock is operated by deliberate action.
Note: UL 508A; Paragraph 66.1.5.
Operable independent of the position of the door
Door closed: operation with the
external handle through the door.
Door open: A robust optional kit with a
handle directly fitted on the shaft of the
switch allows the operation when the
door is open.
Operated by a deliberate action
1Push
Door open: It is necessary to push the
handle from OFF to ON. This deliberate
action permits the operator to turn and
switch ON. This action is necessary as
in most cases there is no padlock on the
switch when somebody opens the door
of an enclosure.
2Turn
ON to OFF action permits the operator
to turn and switch ON. That is a major
safety issue; switching ON directly
without any other action is extremely
dangerous. The use of a padlock does
not comply with the request of the
standard; when the panel door is
opened, there is generally no padlock,
and anybody can turn the switch ON.
1
2
4 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
Introduction
The disconnect means shall be able to be locked in the OPEN position
independent of the door position.
The circuit disconnecting device shall be provided with a
permanent means, permitting it to be locked in the OFF position
only independent of the door position. When locked, remote as
well as local closing shall be prevented.
Note: NFPA 79; Paragraph 5.3.3.1 (3).
An operating mechanism for the disconnecting means shall be
able to be locked in the OFF position independent of the door
position. When locked, closing of the disconnect is not possible.
Note: UL 508A; Paragraph 66.6.3 d.
The interlocking of the enclosure door shall be provided with means
to defeat the interlock without removing the power.
The interlocking means required by 66.1.5 shall be provided with
all of the following:
Means to defeat the interlock without removing power,
and requires the use of a tool to operate
Reactivated automatically when all the doors are closed
Note: Added 66.1.5.1 effective March 1, 2007. UL 508A;
Paragraph 66.1.5.1.
NFPA 79; Paragraph 6.2.3.1.2 states that the [enclosure]
interlocking means shall meet the following requirements:
Use a device or tool to allow qualified persons to defeat
the interlock
Be reactivated automatically when the door is closed
Locked in the open position independent of the door position
Door close: The external through-
the-door handle is padlocked when
locked closing of the disconnect is
not possible.
Door open: A strong metallic padlock
kit allows up to three padlocks. The
padlocking means is easily accessible,
when locked closing of the disconnect
is not possible.
Defeat the interlock without removing the power
A tool allows defeat of the interlock without
removing power. The interlocking is reactivated
automatically when the door is closed.
Switching Devices PG00802002E—September 2012 www.eaton.com 5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Contents
Description Page
Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . 5
Features, Benefits and Functions . . . . . . . . . . . . . . 5
Standards and Certifications. . . . . . . . . . . . . . . . . . 5
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Technical Data and Specifications. . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Product Overview
R5 Series (UL® 508 listed)
products are manually
operated modular switches.
Load break switching and
isolation provide safety
solutions for any low voltage
circuit, particularly for
machine and control circuits.
The R5 Series products are
manual motor controllers
suitable as motor disconnect.
Features, Benefits
and Functions
Up to 65 kAIC
short-circuit rating
Direct or external operation
Compact footprint
DIN rail or base mount
Wide range of accessories
Open and enclosed devices
Modular design
Integrated terminals
for additional safety
Padlockable design (direct,
toggle and external handles)
Product can be reverse fed
Overview
1External front handle
2Shaft extension for external handle
3Direct handle
4Switched fourth-pole module
5Terminal shroud
6Auxiliary contacts
Note: For further details, please see the installation instructions
supplied with each device.
Standards and Certifications
Conformity to Standards
UL 508 listed, Guide NLRV, File E165150
CSA® C22.2 No.14, File 217736
IEC 60947-3, EN 60947-3
CCC
CE
2
3
5
6
4
1
R5 Series Non-Fusible 16–80A
6 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Product Selection
R5 Series
Accessories
Notes
1Toggle version includes direct handle.
2Includes shaft and accessory cap.
Ampere
Rating
Three-Pole Toggle
Switch Only 1
Three-Pole Rotary
Switch Only
Direct
Handle
Front and Right
External Handle SH00
(Choose one)
Front and Right
External Handle SH0
(Choose one)
Shaft for SH0 and
SH00—5 x 5 mm—
In (mm)
16 R5A3016U DHR5 SH00
Black
3R, 12
SHB00N12
SH00
Red
3R, 12
SHR00N12
SH00
Black
4, 4X
SHB00N4X
SH00
Red
4, 4X
SHR00N4X
SH0
Black
3R, 12
SHB0N12
SH0
Red
3R, 12
SHR0N12
SH0
Black
4, 4X
SHB0N4X
SH0
Red
4, 4X
SHR0N4X
2.20 (55.5)
SF55SH5X5
3.50 (90.0)
SF90SH5X5
5.90 (150.0)
SF150SH5X5
7.90 (200.0)
SF200SH5X5
12.60 (320.0)
SF320SH5X5
25 R5A3025U
30 T5A3030U R5A3030U
40 T5A3040U R5A3040U
60 T5B3060U R5B3060U
80 T5B3080U R5B3080U
+++
Switch body Direct handle Switch body Shaft External handle
+++
Direct Operation External Operation
Ampere Rating Switched Fourth-Pole Module
Auxiliary Contacts
(Choose one)
Terminal
Shrouds
Door
Mounting Kit 2
16 S4PR516 1NO + 1NC
AC1NONC
2NO
AC2NO
1P
TS1R5A
3P
TS3R5A
DMK
25 S4PR525
30 S4PR530
40 S4PR540
60 1P
TS1R5B
3P
TS3R5B
80
Switching Devices PG00802002E—September 2012 www.eaton.com 7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Handles
Direct Handle
Door Interlocked External Handle (Defeatable) 1
Shafts
Shaft Extensions for External Handle
Guide Cone
Note
1 Allows door to be opened when switch is in the ON position.
Ampere Rating Handle Color Catalog Number
16–80 Black DHR5
Ampere Rating Handle Color Handle Size NEMA Type Rating Catalog Number
Front and Right Side Operation I–0
16–80 Black SH00 3R, 12 SHB00N12
16–80 Black SH00 4, 4X SHB00N4X
16–80 Red/Yellow SH00 3R, 12 SHR00N12
16–80 Red/Yellow SH00 4, 4X SHR00N4X
16–80 Black SH0 3R, 12 SHB0N12
16–80 Black SH0 4, 4X SHB0N4X
16–80 Red/Yellow SH0 3R, 12 SHR0N12
16–80 Red/Yellow SH0 4, 4X SHR0N4X
Direct Handle
Size 00 Handle
Size 0 Handle
Description Ampere Rating Use with Handle Type
Shaft Length
In (mm) Catalog Number
Standard lengths: 55 mm, 90 mm, 150 mm,
200 mm, 320 mm
For 3/4-pole switches: shafts are for external
front and side handle
For 6/8-pole switches and changeover
switches: shafts are for external
front and side handle
16–80 SH00/SH0 2.17 (55.0) SF055SH5X5
16–80 SH00/SH0 3.54 (90.0) SF090SH5X5
16–80 SH00/SH0 5.91 (150.0) SF150SH5X5
16–80 SH00/SH0 7.87 (200.0) SF2003H5X5
16–80 SH00/SH0 12.60 (320.0) SF320SH5X5
Description Ampere Rating Use with Handle Type Catalog Number
The guide cone facilitates an easier
connection between the shaft and a Size 00 or
Size 0 external selector handle. It allows the
shaft up to 10 mm of vertical play when making
the connection
16–80 SH00 and SH0 SFGAB
Shaft 5 x 5
8 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Additional Pole Configurations
Switched Fourth-Pole Module
Auxiliary Contact Configurations
Auxiliary Contact Module
Description Ampere Rating Number of Poles Type Catalog Number
Add one or two poles and transform:
• Three-pole R5 Series load break
switch into a four-pole
• Six-pole R5 Series switch into
an eight-pole
• Three-pole changeover switch into
a four-pole
16 1 Switched S4PR516
25 1 Switched S4PR525
30 1 Switched S4PR530
40 1 Switched S4PR540
Description Ampere Rating Type Catalog Number
Early-break/same-make and
signalization of positions 0 and I by
NO + NC or 2NO auxiliary contacts.
They can be mounted on the left or
on the right side of the device. Two
modules maximum.
16–80 1NO + NC AC1N0NC
16–80 2NO AC2NO
Switching Devices PG00802002E—September 2012 www.eaton.com 9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Te rm i n a l S h r o u d s
Door/Panel Mounting Kit
Note
1 Includes shaft and accessory cap.
Description Ampere Rating Number of Poles Position Catalog Number
Line and load protection against direct contact with the terminals
or connection parts: single- or three-pole.
Advantage: Perforations allowing thermographic inspection.
16–40 1 Line and load TS1R5A
16–40 3 Line and load TS3R5A
60–80 1 Line and load TS1R5B
60–80 3 Line and load TS3R5B
Description Ampere Rating Number of Poles Catalog Number
This kit enables direct mounting of the switch on the door panel.
Moreover, the connection clamps of the switch are always accessible.
The external handle is quick and easy to install due to an internal
locking nut mounted on the inside of the enclosure.
16–80 3 and 4 DMK 1
10 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Technical Data and Specifications
UL 508 (CSA 22.2 No. 14) Manual Motor Controller “Suitable as Motor Disconnect” from 16–80A
IEC 60947-3 Characteristics
Notes
1Short-circuit rating achieved when used with respective fuse type and maximum fuse rating.
2A/B: Category with index A = frequent operation; category with index B = infrequent operation.
3De-rate 1% per °C above 40°C, max 70°C.
4The power value is given for information only; the current values vary from one manufacturer to another.
5For a rated operating voltage, Ue = 400 Vac.
Technical Characteristics 16A 25A 30A 40A 60A 80A
Approvals
Short-circuit rating at 600 Vac (kA) 1
Branch circuit fuse type
Maximum fuse rating
UL 508/CSA 22.2 No. 14
10/65
J
60/30A
UL 508/CSA 22.2 No. 14
10/65
J
60/30A
UL 508/CSA 22.2 No. 14
10/65
J
60/30A
UL 508/CSA 22.2 No. 14
10/65
J
60/30A
UL 508/CSA 22.2 No. 14
50/65
J
100/60A
UL 508/CSA 22.2 No. 14
50/65
J
100/60A
Maximum UL Horsepower Ratings/Maximum Motor FLA Current, Three-Phase
208 Vac
220–240 Vac
440–480 Vac
600 Vac
3/10.6
5/15
10/14
10/11
7.5/24.2
7.5/22
15/21
20/22
7.5/24.2
7.5/22
15/21
20/22
7.5/24.2
7.5/22
20/27
25/27
15/46.2
15/42
30/40
30/32
15/46.2
20/54
40/52
40/41
Connection
Wire range (AWG), solid, single cable
Wire range (AWG), solid, two cables
Wire range (AWG), stranded, single cable
Wire range (AWG), stranded, two cables
#14–#10
2x #12
#14–#4
2x (#14–#12)
#14–#10
2x #12
#14–#4
2x (#14–#12)
#14–#10
2x #12
#14–#4
2x (#14–#12)
#14–#10
2x #12
#14–#4
2x (#14–#12)
#14–#10
2x #12
#14–#1
2x (#10–#6)
#14–#10
2x #12
#14–#1
2x (#10–#6)
Mechanical Characteristics
Endurance, number of mechanical cycles 10,000 10,000 10,000 10,000 10,000 10,000
Auxiliary Contacts
Electrical characteristics A300 A300 A300 A300 A300 A300
Technical Characteristics 16A 25A 32A 40A 63A 80A
Rated Operational Currents Ie (A)
Rated Voltage Load Duty Category A/B 2A/B 2A/B 2A/B 2A/B 2A/B 2
500 Vac AC-22 A/AC-22 B 16/16 25/25 32/32 40/40 63/63 80/80
500 Vac AC-23 A/AC-23 B 16/16 25/25 25/25 25/25 63/63 63/63
690 Vac AC-21 A/AC-21 B 16/16 25/25 32/32 40/40 63/63 80/80
690 Vac AC-22 A/AC-22 B 16/16 25/25 32/32 32/40 40/63 63/80
690 Vac AC-23 A/AC-23 B 16/16 25/25 25/25 25/25 40/40 40/40
Thermal Current Ith at 40°C (A)
Thermal current Ith (40°C) 316 25 32 40 63 80
Rated insulation voltage Ui (V) 800 800 800 800 800 800
Rated impulse withstand voltage Uimp (kV) 888888
Operational Power in AC-23 (kW)
At 400 Vac without prebreaking AC in AC-23 (kW) 24 7.5 11 15 18.5 30 37
At 500 Vac without prebreaking AC in AC-23 (kW) 24 7.51115153037
At 690 Vac without prebreaking AC in AC-23 (kW) 24 7.5 15 18.5 18.5 30 37
Fuse Protected Short-Circuit Withstand (kA rms Prospective)
Prospective short-circuit current (kA rms) 550 50 50 50 50 50
Associated fuse rating (A) 516 25 32 40 63 80
Overload Capacity (Ue 415 Vac)
Rated short-time withstand current 0.3 s. ICW (kA rms) 52.5 2.5 2.5 2.5 3 3
Rated short-circuit making capacity Icm (kA peak) 5666699
Connection
Minimum Cu cable cross section (mm2) 1.5 1.5 1.5 1.5 2.5 2.5
Maximum Cu cable section (mm2) 161616163535
Tightening torque minimum/maximum (Nm) 2/2.2 2/2.2 2/2.2 2/2.2 3.5/3.85 3.5/3.85
Switching Devices PG00802002E—September 2012 www.eaton.com 11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Dimensions
Approximate Dimensions in Inches (mm)
R5 Series 16–80A
Toggle Operation Direct Operation with Handle
External Front Operation External Side Operation
R5 Series 2
Notes
1One switched fourth-pole module (one per device maximum) or one unswitched neutral pole or one auxiliary contact.
2Maximum four additional blocks.
Overall Dimensions Terminal Shrouds Switch Body Switch Mounting Connection Terminal
Ampere
Rating D Min. D Max. E Min. E Max. AC F F1 G J M N T
16–40 1.18 (30.0) 9.25 (235.0) 3.94 (100.0) 14.65 (372.0) 4.33 (110.0) 1.77 (45.0) 0.59 (15.0) 2.68 (68.0) 0.59 (15.0) 1.18 (30.0) 2.95 (75.0) 0.59 (15.0)
63–80 1.18 (30.0) 9.25 (235.0) 3.94 (100.0) 14.65 (372.0) 4.33 (110.0) 2.06 (52.5) 0.69 (17.5) 2.99 (76.0) 0.69 (17.5) 1.38 (35.0) 3.35 (85.0) 0.69 (17.5)
2.68
(68.0)
F
T
M5
M
N
G
AC
3.19
(81.0)
2.52
(64.0)
0.24
(6.0)
1.97
(50.0)
2.87
(73.0)
F1
F1
0.35
(8.8)
0.35
(8.8)
90
F
T
M5
M
N
G
AC
2.52
(64.0)
0.24
(6.0)
1.97
(50.0)
2.95
(75.0)
F1F1
2.67
(68.0)
0.35
(8.8)
0.35
(8.8)
1
1
1
1
E
1.45
(37.0)
3.19
(81.0)
2.52
(64.0)
0.23
(6.0)
1.96
(50.0)
1.99
(50.6)
J
2.68
(68.0)
F
T
M5
M
D
N
G
AC
F1
0.35
(8.8) F1
Ø2.79
(Ø71.0)
0.35
(8.8)
1.42
(36.0)
1
1
12 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R5 Series (UL 508) Non-Fusible 16–80A
Approximate Dimensions in Inches (mm)
Door Drilling—SH00/SH0
With Fixing Nut With Four Fixing Screws
Operating Handle—SH00/SH0
Front and Right Side Operation Front Operation for R5
Changeover Switches
I–0–II or I–I+II–II
0.53
(13.5)
(3.0)
Ø0.89
(22.5)
1.57
(40.0)
Ø0.28
(7.0)
Ø1.22
(31.0)
1.10
(28.0)
0.16
(4.0)
I
II
90
°
90
°
90
0
I
Switching Devices PG00802002E—September 2012 www.eaton.com 13
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 30100A Compact
Contents
Description Page
Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . 13
Features, Benefits and Functions . . . . . . . . . . . . . . 13
Standards and Certifications. . . . . . . . . . . . . . . . . . 13
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . 14
Technical Data and Specifications. . . . . . . . . . . . . . 17
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Product Overview
The R9 Series (UL® 98 listed)
non-fusible 30–100A compact
range ensures making or
breaking on load and safety
isolation for low voltage
electrical circuits, particularly
for machine control circuits
up to 600V.
Features, Benefits
and Functions
Rating three-pole from
30A to 100A
Direct or external operation
handle (padlockable in
ON position)
Double breaking per phase
Standards and Certifications
UL 98, File E222859
CSA® 22.2 No. 4,
File 217736
IEC 60947-3
EN 60947-3
CE
Overview
1Direct handle
2Door interlocked external handle
3Shaft extension
4Terminal shrouds
5Unswitched neutral pole
6Switch body
7Switched fourth-pole module
8Modular type auxiliary contacts
Note: For further details, please see the installation instructions supplied with each device.
1
2
3
4
56
7
8
14 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 30–100A Compact
Product Selection
R9 Series 30–100A
Ampere
Rating
(Frame)
Number
of Poles
Switch Body
Only
Direct
Handle
Front and
Right External
Handle SH00
(Choose one)
Front and
Right External
Handle SH0
(Choose one)
Shaft for SH0
and SH00
Handles—
In (mm)
(Choose one)
Switched
Fourth-Pole
Module
Auxiliary
Contacts
(Choose one)
Terminal Shrouds
(Choose one)
30
(C-Frame)
3R9C3030U DHR9 SH00
Black
3R, 12
SHB00N12
SH00
Red
3R, 12
SHR00N12
SH00
Black
4, 4X
SHB00N4X
SH00
Red
4, 4X
SHR00N4X
SH0
Black
3R, 12
SHB0N12
SH0
Red
3R, 12
SHR0N12
SH0
Black
4, 4X
SHB0N4X
SH0
Red
4, 4X
SHR0N4X
2.20 (55.5)
SF55SH5X5
3.50 (90.0)
SF90SH5X5
5.91 (150.0)
SF150SH5X5
7.87 (200.0)
SF200SH5X5
12.60 (320.0)
SF320SH5X5
S4PR930 1NO + 1NC
AC1NONC
2NO
AC2NO
1P
TS1R9
3P
TS3R9CV
60
(C-Frame)
3R9C3060U S4PR960
100
(C-Frame)
3R9C3100U S4PR9100
+++
Switch body Direct handle Switch body Shaft External handle
+++
Direct Operation External Operation
Switching Devices PG00802002E—September 2012 www.eaton.com 15
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 30100A Compact
Handles
Direct Handle
Door Interlocked External Handle 1
Shafts
Shaft Extensions for External Handle
Guide Cone
Note
1 Allows door to be opened when switch is in the ON position.
Ampere Rating Handle Color Catalog Number
30–100 Black DHR9
Ampere Rating Handle Color Handle Size NEMA Type Rating Catalog Number
Front and Right External Handle
30–100 Black SH00 3R, 12 SHB00N12
30–100 Black SH00 4, 4X SHB00N4X
30–100 Red SH00 3R, 12 SHR00N12
30–100 Red SH00 4, 4X SHR00N4X
30–100 Black SH0 3R, 12 SHB0N12
30–100 Black SH0 4, 4X SHB0N4X
30–100 Red SH0 3R, 12 SHR0N12
30–100 Red SH0 4, 4X SHR0N4X
Description Ampere Rating Use with Handle Type
Shaft Length
In (mm) Catalog Number
Standard lengths: 55 mm, 90 mm, 150 mm,
200 mm, 320 mm
Shafts are for external front and right
side handles
30–100 SH00/SH0 2.20 (55.5) SF55SH5X5
30–100 SH00/SH0 3.50 (90.0) SF90SH5X5
30–100 SH00/SH0 5.91 (150.0) SF150SH5X5
30–100 SH00/SH0 7.87 (200.0) SF200SH5X5
30–100 SH00/SH0 12.60 (320.0) SF320SH5X5
Description Ampere Rating Use with Handle Type Catalog Number
The guide cone facilitates an easier
connection between the shaft and a Size 00
or Size 0 external selector handle. It allows
the shaft up to 10 mm of vertical play when
making the connection
16–80 SH00 and SH0 SFGAB
Direct Handle
Size 00 Handle
Size 0 Handle
Shaft 5 x 5
16 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 30–100A Compact
Additional Pole Configurations
Switched Fourth-Pole Module
Auxiliary Contact Configurations
Auxiliary Contacts
Te rm i n a l S h r o u d s
Description Ampere Rating Number of Poles Type Catalog Number
Transforms a three-pole, R9 Series load
break switch into a four-pole
30 1 Switched S4PR930
60 1 Switched S4PR960
100 1 Switched S4PR9100
Description Ampere Rating Type Catalog Number
Early-break/same-make and signalization
of positions 0 and I by NO + NC or 2NO
auxiliary contacts. They can be mounted
on the left or on the right side of the
device. Maximum four auxiliary contacts
(two modules)
30–100 1NO + 1NC AC1N0NC
30–100 2NO AC2NO
Description Ampere Rating Number of Poles Position Catalog Number
Line and load protection against
direct contact with the terminals
or connection parts: single- or
three-pole
Advantage: Perforations allowing
thermographic inspection
30–100 1 Line and load TS1R9
30–100 3 Line and load TS3R9CV
Switching Devices PG00802002E—September 2012 www.eaton.com 17
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 30100A Compact
Technical Data and Specifications
UL and CSA Characteristics
UL 98/CSA 22.2 No. 4
IEC 60647-3 Characteristics
Notes
1Short-circuit rating achieved when used with respective fuse type and maximum fuse rating.
2Category with index A = frequent operation.
3A/B: Category with index A = frequent operation; category with index B = infrequent operation.
4The power value is given for information only; the current values vary from one manufacturer to another.
5For a rated operating voltage, Ue = 400 Vac.
Technical Characteristics 30A 60A 100A
Short-circuit rating at 480 Vac (kA) 1100 kA 100 kA 100 kA
Short-circuit rating at 600 Vac (kA) 1100 kA 100 kA 25 kA
Fuse type J J J
Maximum fuse rating (A) 30 60 100
Maximum Horsepower Rating/Maximum Motor FLA Three-Phase
220–240 Vac 10/28 20/54 20/54
440–480 Vac 20/27 40/52 50/65
600 Vac 25/27 50/52 50/52
Maximum Horsepower Rating/Maximum Motor FLA Single-Phase
120 Vac 2/24 3/34 5/56
240 Vac 5/28 10/50 10/50
Connection
Solid, 1 wire #12–10 #12–10 #12–10
Stranded, 1 wire #12–2/0 #12–2/0 #12–2/0
Auxiliary Contacts
Electrical characteristic A300 A300 A300
Technical Characteristics 32A 63A 100A
Thermal Current Ith at 40°C (A)
Thermal current Ith (40°C) 30 60 100
Rated insulation voltage Ui (V) 800 800 800
Rated impulse withstand voltage Uimp (kV) 8 8 8
Rated Operation Currents Ie (A)
Load Duty Category Rated Voltage A 2A 2A 2
400 Vac AC-22 A 32 63 100
400 Vac AC-23 A 32 63 100
690 Vac AC-22 A 32 63 80
690 Vac AC-23 A 32 63 63
Operational Power in AC-23 (kW)
At 400 Vac without prebreak AC in AC-23 (kW) 34 15 30 45
At 500 Vac without prebreak AC in AC-23 (kW) 34 15 30 45
At 690 Vac without prebreak AC in AC-23 (kW) 34 18.5 30 45
Overload Capacity (Ue 415 Vac)
Rated short-time making capacity Icm (kA peak) 512 12 12
Connection
Minimum Cu cable cross section (mm2)2.5 2.510
Maximum Cu cable section (mm2)707070
18 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 30–100A Compact
Dimensions
R9 Series 30–100A Compact
Approximate Dimensions in Inches (mm)
Direct Operation
External Front Operation External Side Operation
Notes
1One switched fourth-pole module (one per device maximum) and/or one unswitched neutral pole.
2Auxiliary contact.
2.95
(75.0)
2.52
(64.0)
2.09
(53.0)
0.24
(6.0)
4.91
(124.6)
5.17
(131.4)
7.44
(189.0)
1.02
(26.0)
3.07
(78.0)
0.35
(8.8)
1.02
(26.0)
M5
26.00
(660.4)
1.02
(26.0) 1.02
(26.0)
0.35
(8.8)
1
2
1
2
0.51
(13.0)
4.
9
1
(
124.6
)
5
.17
(
131.4
)
7.44
(
189.0
)
1.02
(26.0)
3.07
(78.0)
0.35
(8.8)
1.02
(26.0)
M5
3.46
(88.0)
Ø2.80
(71.0)
1.18 min.
(30.0)
7.91 max.
(201.0)
0.35
(8.8)
1.02
(26.0) 1.02
(26.0)
1.46
(37.0)
3.94 min.
(100.0)
3.19
(81.0)
2.52
(64.0)
2.09
(53.0)
0.24
(6.0)
1.99
(50.6)
14.65 max.
(372.0)
1
2
1
2
Switching Devices PG00802002E—September 2012 www.eaton.com 19
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 30100A Compact
Approximate Dimensions in Inches (mm)
R9 Series 30–100A Compact
Door Drilling—SH00/SH0
With Fixing Nut With Four Fixing Screws
Operating Handle—SH00/SH0
Front and Right Side Operation
0.53
(13.5)
(3.0)
Ø0.89
(22.5)
1.57
(40.0)
Ø0.28
(7.0)
Ø1.22
(31.0)
1.10
(28.0)
0.16
(4.0)
90
0
I
20 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Contents
Description Page
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . 20
Features, Benefits and Functions. . . . . . . . . . . . . . 20
Standards and Certifications . . . . . . . . . . . . . . . . . 20
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Technical Data and Specifications . . . . . . . . . . . . . 24
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Product Overview
The R9 Series (UL® 98 listed)
non-fusible 100–1200A are
manually operated multipole
load-break switches. Quick-
make, quick-break design
provides safety isolation for
any low voltage circuit.
Features, Benefits
and Functions
High thermal and dynamic
withstand ratings
Arduous categories of
applications
High electrical and
mechanical endurances
Standards and Certifications
UL 98, File E222859
CSA® 22.2 No. 4,
File 217736
IEC 60947-3
EN 60947-3
Overview
1External front handle
2Shaft extensions for external handle
3Configurable U-type ACs, for pre-break and signalling or TEST
4Terminal screens
Note: For further details, please see the installation instructions supplied with each device.
1
2
3
4
Switching Devices PG00802002E—September 2012 www.eaton.com 21
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Product Selection
R9 Series Non-Fusible 100–1200A
Notes
1Each catalog number is for line or load side. For both line and load, please order two sets.
2Auxiliary contact requires holder (catalog number ACHFG) when used on F and G-Frame switches (non-fusible 600–1200A).
3Top (line side) supplied as standard.
4FS suffix = Finger Safe.
Ampere Rating
(Frame)
Number
of Poles
Switch
Body Only
Direct
Handle
Door Interlocked
External Pistol Handle
(Choose one)
Shaft Extensions for
External Handle—
In (mm)
(Choose one)
Auxiliary
Contacts
Terminal Screens
(Choose one)
Terminal
Lugs 1
100
(D-Frame)
3R9D3100U DHR9DE Size 2, Black
1, 3R, 12
Defeatable
PHB2N12F
Size 2, Red
1, 3R, 12
Defeatable
PHR2N12F
Size 2, Black
4, 4X
Defeatable
PHB2N4XF
Size 2, Red
4, 4X
Defeatable
PHR2N4XF
7.90 (200.0)
SF200PH10X10
12.60 (320.0)
SF320PH10X10
15.70 (400.0)
SF400PH10X10
19.70 (580.0)
SF500PH10X10
1NO + 1NC
AC1N0NCDE
AC1N0NCDELL
2NO + 2NC
AC2N0NCDE
AC2N0NCDELL
3-pole, Line side only
TS3R9DT
3-pole, Load side only
TS3R9DB
4-pole, Line or load side
TS4R9DTB
LK3R9DL
4R9D4100U LK4R9DL
200
(D-Frame)
3R9D3200U LK3R9DL
4R9D4200U LK4R9DL
400
(E-Frame)
3R9E3400U 3-pole, Line side only
TS3R9ET
3-pole, Load side only
TS3R9EB
4-pole, Line or load side
TS4R9ETB
LK3R9EM
4R9E4400U LK4R9EM
600
(F-Frame)
3R9F3600U DHR9FG Size 3, Black
4, 4X
Defeatable
PHB3N4XF
Size 3, Red
4, 4X
Defeatable
PHR3N4XF
Size 4, Black
4, 4X
Defeatable
PHB4N4XF
Size 4, Red
4, 4X
Defeatable
PHR4N4XF
7.90 (200.0)
SF200PH15X12
12.60 (320.0)
SF320PH15X12
1.70 (400.0)
SF400PH15X12
1NO AC U Type
AC1N0R9 2
1NC AC U Type
AC1NCR9 2
TS3R9F 3LK3R9FN
4R9F4600U TS4R9F 3
TS3R9FFS 4
LK4R9FN
800
(G-Frame)
3R9G3800U TS3R9G 3
TS3R9GFS 4
LK6R9G
LK8R9G
4R9G4800U TS4R9G 3
1000
(G-Frame)
3R9G31000U
4R9G41000U
1200
(G-Frame)
3R9G31200U
4R9G41200U
+++
Switch body Direct handle Switch body Shaft External handle
+++
Direct Operation External Operation
22 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Accessories
Direct Handle
Door Interlocked External Handle—Front Operation
Shaft Extensions for External Front Handle
Shaft Length Minimum Dimensions (X)—Inches (mm)
Note
1 Allow the door to be opened when the switch is in 1 (ON) position.
Description Ampere Rating Handle Color Catalog Number
Front operation 100–400 Black DHR9DE
600–1200 Black DHR9FG
Description Ampere Rating Switch Frame Handle Type Handle Color NEMA Type Defeatable 1Catalog Number
The door interlocked external
handle includes one lockable
handle and one escutcheon.
For dimensions, see Page 27.
100–400 D/E PH2 Black 1,3R,12 Yes PHB2N12F
100–400 D/E PH2 Red 1,3R,12 Yes PHR2N12F
100–400 D/E PH2 Black 4,4X Yes PHB2N4XF
100–400 D/E PH2 Red 4,4X Yes PHR2N4XF
600–1200 F/G PH3 Black 4,4X Yes PHB3N4XF
600–1200 F/G PH3 Red 4,4X Yes PHR3N4XF
600–1200 F/G PH4 Black 4,4X Yes PHB4N4XF
600–1200 F/G PH4 Red 4,4X Yes PHR4N4XF
Front Operation
Use
Ampere Rating
(Frame) Handle Type
Shaft Length
In (mm) Catalog Number
Standard lengths:
200 mm, 320 mm,
400 mm, 500 mm
100–400 (D-, E-Frame) PH2 7.90 (200.0) SF200PH10X10
100–400 (D-, E-Frame) PH2 12.60 (320.0) SF320PH10X10
100–400 (D-, E-Frame) PH2 15.70 (400.0) SF400PH10X10
100–400 (D-, E-Frame) PH2 19.70 (500.4) SF500PH10X10
600–1200 (F-, G-Frame) PH3/PH4 7.90 (200.0) SF200PH15X12
600–1200 (F-, G-Frame) PH3/PH4 12.60 (320.0) SF320PH15X12
600–1200 (F-, G-Frame) PH3/PH4 15.70 (400.0) SF400PH15X12
Description
Ampere Rating
(Frame)
X
In (mm)
Length
In (mm) Catalog Number
Standard lengths:
• 7.90 (200.6)
• 12.60 (320.0)
• 5.70 (398.8)
100–400 (D-, E-Frame) 5.31–10.43 (135.0–265.0) 7.90 (200.6) SF200PH10X10
5.31–10.43 (135.0–385.0) 12.60 (320.0) SF320PH10X10
5.31–10.43 (135.0–465.0) 15.70 (398.8) SF400PH10X10
5.31–22.20 (135.0–565.0) 19.70 (500.4) SF500PH10X10
600–1200 (F-, G-Frame) 8.70–13.50 (221.0–343.0) 7.90 (200.6) SF200PH15X12
8.70–18.23 (221.0–463.0) 12.60 (320.0) SF320PH15X12
8.70–21.38 (221.0–543.0) 15.70 (398.8) SF400PH15X12
Direct Handle
PH2 and PH3 Types
PH4 Type
Shaft Extensions
X
Switching Devices PG00802002E—September 2012 www.eaton.com 23
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Auxiliary Contacts 1
Terminal Screens
Line and Load Terminal Lugs
Notes
1 Early-break/same-make.
2 Gold plated for minimal resistance—for PLC applications.
3 Requires use of ACHFG auxiliary contact holder for F- and G-Frame switches.
4 For two-hole lug, consult factory.
Description
Ampere Rating
(Frame) Number of AC AC Type
Catalog
Number
100–200A, up to two ACs max. 100–400
(D-, E-Frame)
1NO / 1NC Standard AC1NONCDE
400A, up to two ACs max. 1NO / 1NC Low Level 2 AC1NONCDELL
2NO / 2NC Standard AC2NONCDE
2NO / 2NC Low Level 2 AC2NONCDELL
600–1200A, up to four ACs max. 600–1200
(F-, G-Frame)
1NO Standard AC1NOR9 3
1NC Standard AC1NCR9 3
Auxiliary contact holder (for use with
AC1NOR9 and AC1NCR9)
600–1200
(F-, G-Frame)
—— ACHFG
Description
Maximum Ampere
Rating (Frame)
Number
of Poles
Line/Load
Side
Catalog
Number
Line and load protection against direct
contact with terminals or connection parts.
Line side terminal shrouds are included
standard on 600–1200A non-fusible
switches. Shrouds are not included on
the 100–400A.
100–200
(D-Frame)
3Line TS3R9DT
3Load TS3R9DB
4 Line or load TS4R9DTB
400
(E-Frame)
3Line TS3R9ET
3Load TS3R9EB
600
(F-Frame)
4 Line or load TS4R9ETB
3 Line or load TS3R9F
800–1200
(G-Frame)
4 Line or load TS4R9F
3 Line or load TS3R9G
4 Line or load TS4R9G
Description
Maximum Ampere
Rating (Frame)
Number
of Poles
Number
of Lugs/Pole
Lug Capacity/
Phase
Cable
Type
Catalog
Number
Connection of copper cables on to the
terminals (no spade lugs). Each kit includes
lugs for line or load side. For line and load
side, order two kits.
For dimensions, see Page 26.
100–200
(D-Frame)
3 1 #6–300 kcmil Cu/Al LK3R9DL
4 1 #6–300 kcmil Cu/Al LK4R9DL
400
(E-Frame)
3 1 #2–600 kcmil Cu/Al LK3R9EM 4
4 1 #2–600 kcmil Cu/Al LK4R9EM 4
600
(F-Frame)
3 1 (2) #2–600 kcmil Cu/Al LK3R9FN
4 1 (2) #2–600 kcmil Cu/Al LK4R9FN
800–1200
(G-Frame)
3 2 2x (2) #2–600 kcmil Cu/Al LK6R9G
4 2 2x (2) #2–600 kcmil Cu/Al LK8R9G
24 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Technical Data and Specifications
UL and CSA Characteristics
IEC 60947-3 Characteristics
Notes
1Short-circuit rating achieved when used with respective fuse type and maximum fuse rating.
2Category with index A = frequent operation.
3For a rated operating voltage, Ui = 400 Vac.
Technical Characteristics 100A 200A 400A 600A 800A 1000A 1200A
Short circuit rating at 600 Vac (kA) 1200 kA 200 kA 200 kA 200 kA 200 kA 100 kA 100 kA
Fuse type J J J J L L L
Maximum fuse rating (A) 100 200 400 600 800 1000 1200
Maximum Horsepower Rating/Maximum Motor FLA Three-Phase
220–240 Vac 30/80 75/192 125/312 200/480 200/480 200/480 200/480
440–480 Vac 75/96 150/180 250/302 400/477 500/590 500/590 500/590
600 Vac 100/99 200/192 350/336 350/336 500/472 500/472 500/472
Maximum Horsepower Rating/Maximum Motor FLA Direct Current
125 Vdc Two-pole in series 10/76 15/112 20/148 20/148
250 Vdc Three-pole in series 15/55 15/55 50/173 50/173
Connection
Minimum connection section/AWG #6 #6 #2 2 x #2 2 x #2 4 x #2 4 x #2
Maximum connection section/AWG 300 kcmil 300 kcmil 600 kcmil 2 x 600 kcmil 2 x 600 kcmil 4 x 600 kcmil 4 x 600 kcmil
Auxiliary Contacts
Electrical characteristics A300 A300 A300 A600 A600 A600 A600
Technical Characteristics 100A 200A 400A 600A 800A 1000A 1200A
Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp (kV) 88812121212
Rated Operational Currents Ie (A)
Rated Voltage
Load Duty
Category A 2A 2A 2A 2A 2A 2A 2
400 Vac AC-22 A 100 200 400 630 800 1000 1200
400 Vac AC-23 A 100 200 400 630 800 1000 1000
690 Vac AC-22 A 100 200 400 500 630 630 630
690 Vac AC-23 A 100 200 315 200 400 400 400
Connection
Minimum Cu cable cross section (mm2) 35 70 185 2 x 150 2 x 185 2 x 240
Minimum Cu busbar section (mm2) ———2 x 30 x 52 x 40 x 52 x 50 x 52 x 60 x 5
Operational Power in Ac-23 (kW)
At 400 Vac without prebreaking AC in AC23 (kW) (2 x 3) 51 100 220 355 450 560 560
At 500 Vac without prebreaking AC in AC23 (kW) (2 x 3) 63 140 280 450 560 560 560
At 690 Vac without prebreaking AC in AC23 (kW) (2 x 3) 90 185 185 185 400 400 400
Overload Capacity (Ue 415 Vac)
Rated short-circuit making capacity Icm (kA peak) 317.6 32 48 48 75 48 75
Switching Devices PG00802002E—September 2012 www.eaton.com 25
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Dimensions
Approximate Dimensions in Inches (mm)
Front Operation—D- and E-Frames
R9 Series Non-Fusible 100–400A
Ampere
Rating (A)
Overall Dimensions—
In (mm)
Terminal Shrouds Switch Body
AC AD F 3P F 4P H J1 3P J1 4P K
100 3.72 (94.6) 10.10 (256.0) 3.05 (77.5) 7.09 (180.0) 9.06 (230.0) 4.22 (107.0) 2.17 (55.0) 4.13 (105.0) 1.80 (45.6)
200 3.72 (94.6) 10.10 (256.0) 3.05 (77.5) 7.09 (180.0) 9.06 (230.0) 4.22 (107.0) 2.17 (55.0) 4.13 (105.0) 1.80 (45.6)
400 4.92 (128.0) 16.00 (406.0) 4.15 (115.0) 9.05 (230.0) 11.40 (290.0) 6.53 (166.0) 2.95 (75.0) 5.31 (135.0) 2.65 (67.5)
Ampere
Rating (A)
Switch Mounting Connection
M 3P M 4P N R1 R2 T U V W Y Z AA AC
100 6.30 (160.0) 8.27 (210.0) 5.31 (135.0) 0.35 (9.0) 0.27 (7.0) 1.97 (50.0) 0.98 (25.0) 1.18 (30.0) 0.43 (11.0) 0.14 (3.5) 1.35 (34.4) 6.30 (160.0) 0.60 (15.0)
200 6.30 (160.0) 8.27 (210.0) 5.31 (135.0) 0.35 (9.0) 0.27 (7.0) 1.97 (50.0) 0.98 (25.0) 1.18 (30.0) 0.43 (11.0) 0.14 (3.5) 1.35 (34.4) 6.30 (160.0) 0.60 (15.0)
400 8.26 (210.0) 10.60 (270.0) 7.67 (195.0) 0.35 (9.0) 0.27 (7.0) 2.56 (65.0) 1.77 (45.0) 1.97 (50.0) 0.43 (13.0) 0.20 (5.0) 2.08 (53.0) 10.20 (260.0) 0.80 (20.0)
Y
AC
K
CA
V
NAA
H
Z
J1 U
R1
M
AD
T
FC
R2
W
Eaton
The switch will operate correctly when
rotated clockwise 90 degrees.
The switch will not operate correctly when
rotated counterclockwise 90 degrees.
26 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Approximate Dimensions in Inches (mm)
Front Operation—F- and G-Frames
R9 Series Non-Fusible 600A
R9 Series Non-Fusible 800–1200A
Terminal Screens Switch Body Switch Mounting Connection Terminals
AC F 3P F 4P H J 2P J 4P M 4P M 4P N N1 AA Z
18.11 (460.0) 11.02 (280.0) 14.17 (360.0) 5.51 (140.0) 5.00 (127.5) 6.59 (167.5) 10.03 (255.0) 13.19 (335.0) 6.89 (175.0) 2.34 (59.5) 12.6 (320.0) 1.85 (47.0)
Terminal Screens Switch Body Switch Mounting Connection Terminals
AC F 3P F 4P H J 3P J 4P M 3P M 4P N N1 N2 Z
18.12 (460.0) 14.64 (372.0) 19.37 (492.0) 5.51 (140.0) 6.83 (173.5) 9.19 (233.5) 13.66 (347.0) 18.38 (467.0) 6.89 (175.0) 2.34 (59.5) 1.10 (28.0) 1.85 (47.0)
HZ
M
Ø0.51
(Ø13.0)
J
N1
N
AA
F
X
Y
3.15
(80.0)
AC
Eaton
The switch will operate correctly when rotated
clockwise 90 degrees.
The switch will not operate correctly when
rotated counterclockwise 90 degrees.
M
J
F
X
Y
N
N2
H
Z
N1
AC
0.78
(19.8)
0.78
(19.8)
1.57
(40.0)
Ø0.43
(Ø10.9)
8.85
(224.8)
4.72
(119.9)
Eaton
The switch will operate correctly when rotated
clockwise 90 degrees.
The switch will not operate correctly when
rotated counterclockwise 90 degrees.
Switching Devices PG00802002E—September 2012 www.eaton.com 27
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Non-Fusible 100–1200A
Approximate Dimensions in Inches (mm)
Direct Handle—Front Operation
R9 Series Non-Fusible 400A R9 Series Non-Fusible 600–1200A
Door Interlocked External Handle
PH2 Type Handle PH3 Type Handle PH4 Type Handle
Direction of Operation
Door Drilling Templates
Top and Bottom Terminal Lugs
R9 Series Non-Fusible 100–200A R9 Series Non-Fusible 400A R9 Series Non-Fusible 600–1200A
2.36
(60.0)
7.48
(190.0)
3.35
(85.0)
1.57
(40.0)
5.31
(135.0)
1.79
(45.5)
Ø3.07 (Ø78.0)
4.92
(125.0)
1.77
(45.0)
Ø3.07
(Ø78.0)
8.27
(210.0)
2.40
(61.0)
2.36
(60.0)
13.78
(350.0)
Ø78.00
(1981.2)
90
0
I
90
0
I
90
0
I
1.57
(40.0)
4Ø7
Ø1.46
(37.0) 1. 10
(28.0)
1.57
(40.0)
4Ø7
Ø1.46
(37.0) 1. 10
(28.0)
1.57
(40.0)
4Ø7
Ø1.46
(37.0) 1. 10
(28.0)
2.87
(72.9)
3.15
(80.0)
1.49
(37.8)
0.40
(Ø10.2)
2.80
(71.5)
Ø 0.40 (Ø10.16)
Ø 4.70 (Ø119.38)
1.30
(35.0)
1.80
(46.0)
0.44
(11.13)
0.63
(15.9)
1.0 0
(25.4)
1.52
(38.6)
1.12
(28.4)
0.45
(Ø11.4)
28 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Contents
Description Page
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . 28
Features, Benefits, and Functions . . . . . . . . . . . . . 28
Standards and Certifications . . . . . . . . . . . . . . . . . 28
Illustrations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Technical Data and Specifications . . . . . . . . . . . . . 39
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Product Overview
R9 Series (UL® 98 listed)
Fusible 30–800A manual
operated multi-pole fusible
disconnect switches use
double break contacts per
pole that ensure complete
isolation of the fuse when the
switch is in the OFF position.
When installed with fuses,
they provide protection for
low voltage electrical
installations against short
circuit and overload.
Features, Benefits
and Functions
Load break functionality
Double break contacts
Up to 200 kA short-circuit
rating with Class CC, J
or L fuses
Compact footprints
The optional TEST position
function (up to 400A)
enables testing of the
control circuit auxiliaries
without switching the main
contacts. This function
provides a simple
alternative to a separately
wired pushbutton
Defeatable pistol handles
automatically re-latch when
the panel door
is closed
Front or side operation
Flange operation
NFPA® 79 compliant kits
Two-, three- and four-
pole devices
Standards and Certifications
UL 98, File E222859 for
30 to 800A ratings
UL 489, File E305341 for
H-Frame switches
CSA® 22.2 No. 4,
File 217736
CSA 22.2 No. 5,
File 217736, H-Frame only
IEC 60947-1, EN 60947-1
IEC 60947-3, EN 60947-3
CE mark
NFPA 79
Switching Devices PG00802002E—September 2012 www.eaton.com 29
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Illustrations
R9 Fusible 30A/CC and 30A/J H-Frame—Direct and External Operation
1External front handles
2Direct handle
3Shaft extensions for external handles
4Configurable U Type ACs, for pre-break and signaling or TEST
R9 Fusible 30A/J–800A/L (I–N-Frames)—Direct and External Operation
1External front handle
2External right side handle (not applicable for N-Frame 600/800A)
3Direct handle
4Shaft extensions for external handles
5Configurable U Type ACs, for pre-break and signaling or TEST
6Side auxiliary contacts
7Terminal shrouds
1
2
3
4
1
2
3
4
5
6
7
4
30 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Product Selection
Front and Right Side Operation
Note
1100 kA short-circuit rating.
Ampere Rating
(Frame)
(Fuse Class)
Number
of Poles
Switch
Body Only
Direct
Handle
External Selector
Handle
(Choose one)
Shaft Extension for
Selector Handle Only
(Choose one)
External Front
Pistol Handle
External Right
Side Pistol Handle
30 1
Compact
(H-Frame) (CC)
3R4H3030FCC DHR9HC Black
1,3R,12
SHB0N12HV
Red
1,3R,12
SHR0N12HV
Black
4,4X
SHB0N4XHV
Red
4,4X
SHR0N4XHV
7.90 (200.0)
SF200SH5X5H
Black
1,3R,12
PHB1N12F
Red
1,3R,12
PHR1N12F
Black
4,4X
PHB1N4XF
Red
4,4X
PHR1N4XF
Black
4,4X
(w/ TEST Position)
PHB1N4XFT
Red
4,4X
(w/ TEST Position)
PHR1N4XFT
30 1
(H-Frame) (CC)
3 + switched neutral R4H3030FCCSN 12.60 320.0)
SF320SH5X5H
30 1
Compact
(H-Frame) (J)
3R4H3030FJ DHR9HJ 15.70 (400.0)
SF400SH5X5H
30 1
(H-Frame) (J)
3 + switched neutral R4H3030FJSN
30
(I-Frame) (CC)
3R9I3030FCC DHR9J2M ——
4R9I4030FCC
30
(J-Frame) (J)
2R9J2030FJ Black
4, 4X
PHB1N4XS
Red
4, 4X
PHR1N4XS
3R9J3030FJ
4R9J4030FJ
60 1
(J-Frame) (J)
2R9J2060FJ
3R9J3060FJ
4R9J4060FJ
+++
Switch body Direct handle Switch body Shaft External handle
+++
Direct Operation External Operation
Switching Devices PG00802002E—September 2012 www.eaton.com 31
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Front and Right Side Operation, continued
Shaft Extensions for
Pistol Handle Only
In (mm)
(Choose one)
NFPA79
Kit
Auxiliary
Contacts
(Choose one)
S Type Auxiliary
Contacts
(Choose one)
Terminal
Shrouds
7.90 (200.0)
SF200PH5X5
12.60 (320.0)
SF320PH5X5
15.70 (400.0)
SF400PH5X5
NFPA79H 1 AC
NO
AC1NOR9
1 AC
NC
AC1NCR
Integral to switch
7.90 (200.0)
SF200PH10X10
12.60 (320.0)
SF320PH10X10
15.70 (400.0)
SF400PH10X10
19.70 (500.0)
SF500PH10X10
NFPA79JKL 1 AC
NO + NC
AC1NO1NCJ2N
2 AC
NO + NC
AC2NO2NCJ2N
1 AC
NO + NC
w/ TEST
AC1NO1NCJ2NT
2 AC
NO + NC
w/ TEST
AC2NO2NCJ2NT
32 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Front and Right Side Operation, continued
Notes
1200 kA short-circuit rating.
2Requires test handle.
Ampere Rating
(Frame)
(Fuse Class)
Number
of Poles
Switch
Body Only
Direct Handle
(Black)
External Front
Pistol Handle
(Choose one)
External Right Side
Pistol Handle (Choose one)
60 1
(K-Frame) (J)
2R9K2060FJ DHR9J2M Black
1,3R,12
PHB2N12F
Red
1,3R,12
PHR2N12F
Black
4,4X
PHB2N4XF
Red
4,4X
PHR2N4XF
Black
4,4X
(w/ TEST Position)
PHB2N4XFT 2
Red
4,4X
(w/ TEST Position)
PHR2N4XFT 2
Black
4, 4X
PHB2N4XS
Red
4, 4X
PHR2N4XS
3R9K3060FJ
4R9K4060FJ
100
(K-Frame) (J)
2R9K2100FJ
3R9K3100FJ
4R9K4100FJ
200
(L-Frame) (J)
2R9L2200FJ
3R9L3200FJ
4R9L4200FJ
400
(M-Frame) (J)
3R9M3400FJ
4R9M4400FJ
600
(N-Frame) (J)
2R9N2600FJ DHR9N Black
4, 4X
PHB3N4XF
Red
4,4X
PHR3N4XF
3R9N3600FJ
4R9N4600FJ
800
(N-Frame) (L)
2R9N2800FL
3R9N3800FL
4R9N4800FL
Switching Devices PG00802002E—September 2012 www.eaton.com 33
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Front and Right Side Operation, continued
Notes
1200 kA short-circuit rating.
2Requires test handle.
Ampere Rating
(Frame)
(Fuse Class)
Number
of Poles
Switch
Body Only
Shaft Extensions
for External Handle
In (mm) (Choose one)
NFPA79
Kit
Auxiliary
Contacts
(Choose one)
Auxiliary
Contacts
(Choose one)
Terminal
Shrouds
60 1
(K-Frame) (J)
2R9K2060FJ 7.90 (200.0)
Pistol
SF200PH10X10
12.60 (320.0)
Pistol
SF320PH10X10
15.70 (400.0)
Pistol
SF400PH10X10
19.70 (500.0)
Pistol
SF500PH10X10
NFPA79JKL 1 AC
NO
AC1NOR9
1 AC
NC
AC1NCR9
1 AC
NO + NC
AC1NO1NCJ2N
2 AC
NO + NC
AC2NO2NCJ2N
1 AC
NO + NC
w/ TEST
AC1NO1NCJ2NT 2
2 AC
NO + NC
w/ TEST
AC2NO2NCJ2NT 2
Integral to switch
3R9K3060FJ
4R9K4060FJ
100
(K-Frame) (J)
2R9K2100FJ
3R9K3100FJ
4R9K4100FJ
200
(L-Frame) (J)
2R9L2200FJ TSR9L2
3R9L3200FJ TSR9L3
4R9L4200FJ TSR9L4
400
(M-Frame) (J)
3R9M3400FJ TSR9M3
4R9M4400FJ TSR9M4
600
(N-Frame) (J)
2R9N2600FJ 7.90 (200.0)
Pistol
SF200PH12X12
12.60 (320.0)
Pistol
SF320PH12X12
15.70 (400.0)
Pistol
SF400PH12X12
19.70 (500.0)
Pistol
SF500PH12X12
NFPA79N 1 AC
NO + NC
AC1NO1NCJ2N
2 AC
NO + NC
AC2NO2NCJ2N
TSR9N2
3R9N3600FJ TSR9N3
4R9N4600FJ TSR9N4
800
(N-Frame) (L)
2R9N2800FL TSR9N2
3R9N3800FL TSR9N3
4R9N4800FL TSR9N4
34 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Accessories
NFPA 79 Compliant
“Flange” Handle for Flange-Operated Switches
Cable Operator
Rod Operator
NFPA 79 “Through the Door” Kit
Note
1 Defeatable.
Description
Ampere Rating
(Frame) Handle Type NEMA Type Catalog Number
For side-operated switches only.
Provides heavy-duty flange style
operation. Meets both UL 508A and
NFPA 79 requirements. Please order
cable or rod link between handle
and switch.
30–400 (J-, K-, L-, M-Frame) Standard handle 1, 3, 3R, 4, 12 FHS 1
30–400 (J-, K-, L-, M-Frame) Chrome-plated handle 1, 3, 3R, 4, 4X, 12 FHCP 1
Description
Ampere Rating
(Frame) NEMA Type
Cable Length
In (mm) Catalog Number
Link between “Flange” handle
and side-operated switches.
Please order mechanism and
“Flange” handle.
30–400 (J-, K-, L-, M-Frame) Mechanism for
“Flange” handle
CFM1
36.00 (914.4) CFC36
60.00 (1524.0) CFC60
120.00 (3048.0) CFC120
Description
Ampere Rating
(Frame)
For Enclosure Depth
In (mm) Catalog Number
Link between “Flange” handle
and side-operated switches.
Mechanism included.
Please order “Flange” handle.
30–400 (J-, K-, L-, M-Frame) 8.00–24.00 (203.2–609.6) RFM1
Description
Ampere Rating
(Frame) Catalog Number
For front-operated switches only.
Meets both UL 508A and NFPA 79
requirements. Kit includes
mechanism, shaft and internal
handle. Please also order a “PH”
type external pistol handle.
30 (H-Frame) NFPA79H
30–400 (J-, K-, L-, M-Frame) NFPA79JKL
600–800 (N-Frame) NFPA79N
Mechanism for
Flange Handle
Switching Devices PG00802002E—September 2012 www.eaton.com 35
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Direct Handles
Door Interlocked External Front Handles
Right Side External Handles
Note
1 Includes TEST position.
Description
Ampere Rating
(Frame) Fuse Catalog Number
Front operation. Black. 30 (H-Frame) CC DHR9HC
30 (H-Frame) J DHR9HJ
30 (I-Frame) CC DHR9J2M
30–400 (J-, K-, L-, M-Frame) J DHR9J2M
600–800 (N-Frame) J/L DHR9N
Description
Ampere Rating
(Frame) Handle Type NEMA Type Color
Standard
Catalog Number
The handle locking function of the
front external operation handle
prevents the user from opening
the door of the enclosure when the
switch is in the ON position, and
when the switch is padlocked in
the OFF position (PH1, PH2 and PH3
type handles only). Opening the
door when the switch is in the OFF
position is possible by defeating the
locking function with the use of a
tool (authorized persons only). The
locking function is restored when
the door is closed back.
30 (H-Frame) SO 1, 3R, 12 Black SHB0N12HV
30 (H-Frame) SO 1, 3R, 12 Red/yellow SHR0N12HV
30 (H-Frame) SO 4, 4X Black SHB0N4XHV
30 (H-Frame) SO 4, 4X Red/yellow SHR0N4XHV
30–60 (H-, I-, J-Frame) PH1 1, 3R, 12 Black PHB1N12F
30–60 (H-, I-, J-Frame) PH1 1, 3R, 12 Red/yellow PHR1N12F
30–60 (H-, I-, J-Frame) PH1 4, 4X Black PHB1N4XF
30–60 (H-, I-, J-Frame) PH1 4, 4X Red/yellow PHR1N4XF
30–60 (H-, I-, J-Frame) PH1 4, 4X Black PHB1N4XFT 1
30–60 (H-, I-, J-Frame) PH1 4, 4X Red/yellow PHR1N4XFT 1
60–400 (K-, L-, M-Frame) PH2 1, 3R, 12 Black PHB2N12F
60–400 (K-, L-, M-Frame) PH2 1, 3R, 12 Red/yellow PHR2N12F
60–400 (K-, L-, M-Frame) PH2 4, 4X Black PHB2N4XF
60–400 (K-, L-, M-Frame) PH2 4, 4X Red/yellow PHR2N4XF
60–400 (K-, L-, M-Frame) PH2 4, 4X Black PHB2N4XFT 1
60–400 (K-, L-, M-Frame) PH2 4, 4X Red/yellow PHR2N4XFT 1
600–800 (N-Frame) PH3 4, 4X Black PHB3N4XF
600–800 (N-Frame) PH3 4, 4X Red/yellow PHR3N4XF
Ampere Rating
(Frame) Handle Type NEMA Type Color
Standard
Catalog Number
30–60 (J-Frame) PH1 4, 4X Black PHB1N4XS
30–60 (J-Frame) PH1 4, 4X Red/yellow PHR1N4XS
60–400 (K-, L-, M-Frame) PH2 4, 4X Black PHB2N4XS
60–400 (K-, L-, M-Frame) PH2 4, 4X Red/yellow PHR2N4XS
SO Type Handle
PH1 Type Handle
PH2 Type Handle
PH3 Type Handle
36 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Shaft Extensions for External Handles
Handle Types SH and PH, X Minimum Dimensions
Ampere Rating (Frame) Handle Type
Shaft Length
In (mm) Catalog Number
30 (H-Frame) SH0 7.90 (200.0) SF200SH5X5H
30 (H-Frame) SH0 12.60 (320.0) SF320SH5X5H
30 (H-Frame) SH0 15.70 (400.0) SF400SH5X5H
30 (H-Frame) PH1 7.90 (200.0) SF200PH5X5
30 (H-Frame) PH1 12.60 (320.0) SF320PH5X5
30 (H-Frame) PH1 15.70 (400.0) SF400PH5X5
30–400 (I-, J-, K-, L-, M-Frame) PH2 7.90 (200.0) SF200PH10X10
30–400 (I-, J-, K-, L-, M-Frame) PH2 12.60 (320.0) SF320PH10X10
30–400 (I-, J-, K-, L-, M-Frame) PH2 15.70 (400.0) SF400PH10X10
30–400 (I-, J-, K-, L-, M-Frame) PH3 19.70 (500.0) SF500PH10X10
600–800 (N-Frame) PH3 7.90 (200.0) SF200PH12X12
600–800 (N-Frame) PH3 12.60 (320.0) SF320PH12X12
600–800 (N-Frame) PH3 15.70 (400.0) SF400PH12X12
600–800 (N-Frame) PH3 19.70 (500.0) SF500PH12X12
Ampere Rating (Frame)
Dimensions X
In (mm) Handle Type
Shaft Length
In (mm) Catalog Number
30 (H-Frame) 4.02–9.65 (102.0–245.0) SH0 7.90 (200.0) SF200SH5X5H
30 (H-Frame) 4.02–14.37 (102.0–365.0) SH0 12.60 (320.0) SF320SH5X5H
30 (H-Frame) 4.02–17.52 (102.0–445.0) SH0 15.70 (400.0) SF400SH5X5H
30 (H-Frame) 4.02–9.65 (102.0–245.0) PH1 7.90 (200.0) SF200PH5X5
30 (H-Frame) 4.02–14.37 (102.0–365.0) PH1 12.60 (320.0) SF320PH5X5
30 (H-Frame) 4.02–17.52 (102.0–445.0) PH1 15.70 (400.0) SF400PH5X5
30–100 (I-, J-, K-Frame) 5.30–9.06 (135.0–230.0) PH2, PH3 7.90 (200.0) SF200PH10X10
200 (L-Frame) 5.70–9.06 (145.0–230.0) PH2, PH3 7.90 (200.0) SF200PH10X10
400 (M-Frame) 7.87–10.24 (200.0–260.0) PH2, PH3 7.90 (200.0) SF200PH10X10
30–100A (I-, J-, K-Frame) 5.30–13.78 (135.0–350.0) PH2, PH3 12.60 (320.0) SF320PH10X10
200 (L-Frame) 5.70–13.78 (145.0–350.0) PH2, PH3 12.60 (320.0) SF320PH10X10
400 (M-Frame) 7.87–14.96 (200.0–380.0) PH2, PH3 12.60 (320.0) SF320PH10X10
30–100 (I-, J-, K-Frame) 5.30–16.93 (135.0–430.0) PH2, PH3 15.70 (400.0) SF400PH10X10
200 (L-Frame) 5.70–16.93 (145.0–430.0) PH2, PH3 15.70 (400.0) SF400PH10X10
400 (M-Frame) 7.87–18.10 (200.0–460.0) PH2, PH3 15.70 (400.0) SF400PH10X10
30–100 (I-, J-, K-Frame) 5.30–20.87 (135.0–530.0) PH2, PH3 19.70 (500.0) SF500PH10X10
200 (L-Frame) 5.70–20.87 (145.0–530.0) PH2, PH3 19.70 (500.0) SF500PH10X10
400 (M-Frame) 7.87–22.05 (200.0–560.0) PH2, PH3 19.70 (500.0) SF500PH10X10
600–800 (N-Frame) 10.63–11.97 (270.0–304.0) PH3 12.60 (320.0) SF320PH12X12
600–800 (N-Frame) 10.63–16.69 (270.0–424.0) PH3 12.60 (320.0) SF320PH12X12
600–800 (N-Frame) 10.63–19.84 (270.0–504.0) PH3 15.70 (400.0) SF400PH12X12
600–800 (N-Frame) 10.63–23.78 (270.0–604.0) PH3 19.70 (50.00) SF500PH12X12
X
Switching Devices PG00802002E—September 2012 www.eaton.com 37
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Auxiliary Contacts—NO + NC 1
Auxiliary Contacts—NO or NC 3
Characteristics for Pre-Break Auxiliary Contacts
Te rm i n a l S h r o u d s
Notes
1 Same-make/same-break auxiliary contacts.
2 Auxiliary contacts without “Test” cannot be used on I–M-Frame switches.
3 Early-break/same-make auxiliary contacts.
4 For replacement only. Both line and load side terminal shrouds are included with 400A switch.
Operating Current Ie (Amperes)
Description
Ampere Rating
(Frame)
Number
of ACs Nominal Current (Amperes)
Catalog
Number
For the R9 Series Fusible 30–800A,
indication of the O and I positions by
1 to 4 NO + NC auxiliary contacts.
Electrical principle:
Cabling by terminal cage with
#16 AWG maximum.
High electrical characteristics:
A600/D600
600–800 (N-Frame) 1NO + 1NC 10 AC1NO1NCJ2N 2
600–800 (N-Frame) 2NO + 2NC 10 AC2NO2NCJ2N 2
30–400 (I–M-Frame) 1NO + 1NC (w/ TEST) 10 AC1NO1NCJ2NT
30–400 (I–M-Frame) 2NO + 2NC (w/ TEST) 10 AC2NO2NCJ2NT
Description Ampere Rating (Frame) Number of ACs Catalog Number
The different functions (pre-break, 0 and 1 indication,
TEST feature) are easily configurable with pegs
(one or two pegs per position). Two superposed
auxiliary contacts maximum.
For 30A/CC (H-Frame), maximum of four ACs.
For 30A/J (H-Frame), maximum of two ACs.
For 30 to 100A/J (I, J and K-Frame), maximum
of four ACs.
For 200 to 600A/J (L and M-Frame),
maximum of eight ACs.
Cabling to the control circuit by terminals
with a maximum section of 2 x 2.5 mm2.
Electrical characteristics: A300
NO Auxiliary Contact
30–600 (H–M-Frame) 1 AC1NOR9
NC Auxiliary Contact
30–600 (H–M-Frame) 1 AC1NCR9
Operating Current Ie (Amperes)
Ampere Rating Contact Type
Nominal Current
Amperes 250 Vac AC-13 400 Vac AC-13 24 Vdc DC-13 48 Vdc DC-13
30–800 NO + NC 10 6 4 5 3
Description Ampere Rating (Frame) Number of Poles Catalog Number
Line or load side protection against direct contact
with terminals or the connection parts
30–100 (H-, I-, J-, K-Frame) 2/3/4 Integral to switch
200 (L-Frame) 2 TSR9L2
200 (L-Frame) 3 TSR9L3
200 (L-Frame) 4 TSR9L3
400 (M-Frame) 2 TSR9M2 4
400 (M-Frame) 3 TSR9M3 4
400 (M-Frame) 4 TSR9M4 4
600–800 (N-Frame) 2 TSR9N2
600–800 (N-Frame) 3 TSR9N3
600–800 (N-Frame) 4 TSR9N4
Terminal Shrouds
38 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Line and Load Terminal Lugs
Shorting Links
Description Ampere Rating (Frame) Fuse
Number
of Lugs
Lug Capacity/
Phase Cable Type Catalog Number
Connection of bare copper cables
on to the terminals
(no spade lugs).
30 (H-, I-Frame) CC/J #14–#10 Cu Integral to switch
30 (H-, I-Frame) CC/J #14–#10 Cu Integral to switch
30–60 (J-Frame) J #10–#6 Cu Integral to switch
60–100 (K-Frame) J #12–#1 Cu Integral to switch
200 (L-Frame) J 2 #6–300 kcmil Cu/Al LK2R9DL
200 (L-Frame) J 3 #6–300 kcmil Cu/Al LK3R9DL
200 (L-Frame) J 4 #6–300 kcmil Cu/Al LK4R9DL
400 (M-Frame) J 3 (2) #2–600 kcmil Cu/Al LK3R9FN
400 (M-Frame) J 4 (2) #2–600 kcmil Cu/Al LK4R9FN
600–800 (N-Frame) J/L 2 (2) #2–600 kcmil Cu/Al LK2R9FN
600–800 (N-Frame) J/L 3 (2) #2–600 kcmil Cu/Al LK3R9FN
600–800 (N-Frame) J/L 4 (2) #2–600 kcmil Cu/Al LK4R9FN
Ampere Rating (Frame) Fuse Pack Quantity Catalog Number
60 (J-,K-Frame) J 3 SLJK360
100 (K-Frame) J 3 SLK3100
200 (L-Frame) J 3 SLL3
400 (M-Frame) J 3 SLM3
600–800 (N-Frame) J/L 3 SLN3
Switching Devices PG00802002E—September 2012 www.eaton.com 39
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Technical Data and Specifications
UL and CSA Characteristics
R9 Series Fusible 30–800A
Notes
1Two-pole in series.
2Three-pole in series.
Description 30A 30A 30A 30A 60A 60A 100A
General Use Ratings
Switch Frame H H I J J K K
600 Vac (A) 30 30 30 30 60 60 100
600 Vdc (A)
Short-Circuit Ratings
Short-circuit rating at
600 Vac (kA)
100 100 100 200 100 200 200
Fuse type CC J CC J J J J
Maximum fuse rating (A) 30 30 30 30 60 60 100
Maximum Horsepower Rating/Maximum Motor FLA Three-Phase
220–240 Vac 7.5/22 7.5/22 7.5/22 7.5/22 15/42 15/42 30/80
440–480 Vac 15/21 15/21 15/21 15/21 30/40 30/40 60/77
600 Vac 20/22 20/22 20/22 20/22 50/52 50/52 75/77
Maximum Horsepower Rating/Maximum Motor FLA Single-Phase
220–240 Vac 3/17 3/17 10/50 10/50 10/50
440–480 Vac 7.5/21 7.5/21 10/26 10/26 10/26
600 Vac 10/20 10/20 10/20 10/20 10/20
Maximum Horsepower Rating/Maximum Motor FLA DC
125 Vdc 13/25 3/25 3/25 3/25 5/40 5/40 7.5/58
250 Vdc 25/20 5/20 5/20 5/20 10/38 10/38 20/72
Mechanical Characteristics
Endurance
(number of operating cycles)
10,000 10,000 10,000 10,000 10,000 10,000 10,000
Terminal Lugs
Type Integrated Integrated Integrated Integrated Integrated Integrated Integrated
Minimum conn. section #14 #14 #14 #10 #10 #12 #12
Maximum conn. section #10 #10 #10 #6 #6 #1 #1
40 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
R9 Series Fusible 30–800A, continued
Notes
1Two-pole in series.
2Three-pole in series.
Description 200A 400A 600A 800A
General Use Ratings
Switch Frame L M N N
600 Vac (A) 200 400 600 800
600 Vdc (A) 600 2800 2
Short-Circuit Ratings
Short-circuit rating at 600 Vac (kA) 200 200 200 200
Fuse type J J J L
Maximum fuse rating (A) 200 400 600 800
Maximum Horsepower Rating/Maximum Motor FLA Single-Phase
220–240 Vac
440–480 Vac
600 Vac
Maximum Horsepower Rating/Maximum Motor FLA Three-Phase
220–240 Vac 60/154 125/312 200/480 200/480
440–480 Vac 125/156 250/302 500/590 500/590
600 Vac 150/144 350/336 500/472 500/472
Maximum Horsepower Rating/Maximum Motor FLA DC
125 Vdc 1 20/148
250 Vdc 2 50/173 2——
Mechanical Characteristics
Endurance
(number of operating cycles)
8000 6000 5000 5000
Terminal Lugs
Type Option Option Option Option
Minimum conn. section #6 #2 2x#2 2x#2
Maximum conn. section 3/0 300 kcmil 2 x 600 kcmil 2 x 600 kcmil
Switching Devices PG00802002E—September 2012 www.eaton.com 41
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Dimensions
Approximate Dimensions in Inches (mm)
Front Operation
R9 Series Fusible 30A/CC—H-Frame
R9 Series Fusible 30A/J—H-Frame
Switch Body Switch Mounting Connection Terminals
FHH1JJ1NN1AAZ
3.78 (96.0) 3.28 (83.3) 5.19 (131.8) 1.47 (37.3) 0.59 (15.0) 3.13 (79.5) 1.00 (25.4) 4.56 (115.8) 1.12 (28.4)
Switch Body Switch Mounting Connection Terminals
FHJJ1NN1AAZ
4.13 (104.9) 3.89 (98.8) 1.47 (37.3) 0.59 (15.0) 3.30 (83.8) 1.00 (25.4) 4.56 (115.8) 1.12 (28.4)
H
Z
H1
AA
NN1
F
JJ1
H
Z
F
J
J1
AA
N
N1
42 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Approximate Dimensions in Inches (mm)
R9 Series Fusible 30A/CC—I-Frame
R9 Series Fusible 30A/J and 60A/J (100 kA)—J-Frame
Ampere Rating
(Fuse)
Switch body Switch Mounting Connection Terminals
F 3P F 4P H J M N N1 AA Z
30 (CC) 4.92 (125.0) 6.06 (154.0) 3.89 (99.0) 1.77 (45.0) 1.14 (29.0) 5.31 (135.0) 2.63 (66.5) 5.87 (149.0) 1.21 (31.0)
MJ
F
N1
N
H
AA
Z
1.14
(29.0)
0.41
(10.3)
4.98
(126.5)
6.02
(153.0)
5.35
(135.9)
5.87
(149.1)
1.41
(35.8) 1.46
(37.1)
4.84
(122.9)
1.41
(35.8)
4.02
(102.1)
Switching Devices PG00802002E—September 2012 www.eaton.com 43
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Approximate Dimensions in Inches (mm)
R9 Series Fusible 60A/J (200 kA) and 100A/J—K-Frame
R9 Series Fusible 200A/J—L-Frame
7.32
(185.9)
5.87
(149.1)
1.41
(35.8)
1.46
(37.1)
4.81
(122.2)
1.41
(35.8)
6.77
(172.0)
5.23
(132.8)
7.72
(196.1)
6.61
(167.9)
6.18
(157.0)
1.41
(35.8)
5.11
(129.8)
1.96
(49.8)
5.28
(134.1)
6.50
(165.1)
7.67
(194.8)
11.46
(291.1)
44 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Approximate Dimensions in Inches (mm)
R9 Series Fusible 400A/J—M-Frame
R9 Series Fusible 600–800A J/L—N-Frame
H
AA
H1
Z
0.40
(10.2)
5.00
(127.0)
1.14
(30.0) M
M10
J
F
M
N1
N
6.53
(166.0)
Switch Body Switch Mounting Connection Terminals
F 3P F 4P H H1 J M N N1 AA Z
10.80 (276.0) 13.70 (348.0) 5.56 (141.5) 11.41 (290.0) 0.88 (22.5) 2.84 (72.0) 8.83 (224.0) 4.41 (112.0) 14.31 (363.5) 1.06 (27.0)
9.84
(249.9) 6.10
(154.9)
3.12
(79.2)
0.27
(6.9)
2.32
(58.9)
14.96
(380.0)
Min. 10.43
(Min. 264.9)
0.43
(10.9)
2.56
(65.0) 1.34
(34.0)
0.35
(8.9)
3.70
(94.0)
3.70
(94.0)
Fix 9.84
(Fix 250.0)
5.00
(127.0)
11.81
(300.0)
0.86
(21.8)
9.27
(235.5)
9.27
(235.5)
10.23
(259.8)
3.36
(85.3)
2.00
(50.8)
ø0.51
(ø13.0)
3.36
(85.3)
11.81
(300.0)
3.54 (89.9)
0.27 (6.9)
0.27 (6.9)
3P
14.33
(364.0)
4P
18.03
(458.0)
3P
11. 1 8
(284.0)
4P
14.88
(378.0)
Switching Devices PG00802002E—September 2012 www.eaton.com 45
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Approximate Dimensions in Inches (mm)
30CC (H-Frame) 30J (H-Frame)
30J to 400J 600J and 800L
Flange Handle
4.41
(112.0)
2.31
(58.7)
5.12
(130.0)
2.36
(60.0)
7.48
(190.0)
3.35
(85.0)
1.57
(40.0)
5.31
(135.0)
1.79
(45.5)
3.50
(88.9) 2.16
(54.9)
0.86
(21.8)
1.06
(26.9)
4.68
(118.9)
1.55
(39.4)
0.88
(22.3)
1.0 0
(25.4)
1.0 0
(25.4)
6.22
(158.0)
2.32
(58.9)
7. 1 0
(180.3)
Ø0.50
(Ø12.7)
Ø0.28
(Ø7.1)
2.70
(68.6)
5.66
(143.8)
46 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) Fusible 30–800A
Approximate Dimensions in Inches (mm)
Door Interlocked External Handle
PH1 Type Handle PH2 Type Handle PH3 Type Handle
Direction of Operation
Door Drilling Template
Line and Load Side Lugs
200A (L-Frame) 400–800A (M and N-Frames)
2.75
(70.0)
1.73
(44.0)
Ø3.07 (Ø78.0)
Ø3.07 (Ø78.0)
4.92
(125.0)
1.77
(45.0)
Ø3.07
(Ø78.0)
8.27
(210.0)
2.40
(61.0)
90
0
I
90
0
I
90
0
I
1.57
(40.0)
4Ø7
Ø1.46
(37.0) 1. 10
(28.0)
1.57
(40.0)
4Ø7
Ø1.46
(37.0) 1. 10
(28.0)
1.57
(40.0)
4Ø7
Ø1.46
(37.0) 1. 10
(28.0)
1.0 0
(25.4)
1.52
(38.6)
1.12
(28.4)
0.45
(Ø11.4)
2.87
(72.9)
3.15
(80.0)
1.49
(37.8)
0.40
(Ø10.2)
Switching Devices PG00802002E—September 2012 www.eaton.com 47
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.0
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Contents
Description Page
Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . 47
Features, Benefits and Functions . . . . . . . . . . . . . . 47
Application Description. . . . . . . . . . . . . . . . . . . . . . 47
Standards and Certifications. . . . . . . . . . . . . . . . . . 47
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Technical Data and Specifications. . . . . . . . . . . . . . 51
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Product Overview
UL listed disconnect
switches 600 Vdc for
photovoltaic applications
100 to 400A
R9 Series (UL® 98 listed)
DC rated disconnects are
manually operated multi-pole
load break switches. They
provide safety isolation for
any low voltage circuit in a
photovoltaic application.
Features, Benefits
and Functions
Unique switching
technology
Up to 600 Vdc according
to UL 98 / CSA®
Up to 1000 Vdc according
to IEC 947-3
Application Description
In three- and four-pole
versions from 100 to 400A
Standards and Certifications
UL 98, cULus®,
File E222859
CSA 22.2 No. 4,
File 217736 1
IEC 60947-3
EN 60947-3
IEC 60-364-7-712
(Rules for the installations
and sites special
photovoltaic applications)
1Q4 2010
Simplified large photovoltaic system layout
R9 DC
100 to 400A
to 1000V
R9 DC
R9 DC
R9 DC
100–600A
up to 1000V
Array Combiner
Source Combiner
R9 DC
100–400A
up to 1000V
Standard R9 Series
AC disconnect switch
non-fusible up to 1200A
or fusible up to 800A
Array Combiner
48 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Product Selection
Front Operation—Three- and Four-Pole
Notes
1Defeatable handle.
2Top (line side).
3Bottom (load side).
4Top or bottom (line or load side).
Ampere
Rating
Number
of Poles
Switch
Body Direct Handle
External Handle
(Choose one)
Shaft for External
Handle
In (mm) (Choose one)
Auxiliary Contacts
(Choose one)
Terminals
Shroud Terminal Lugs
Jumpers for
Connecting
Poles in Series
100 3 R9D3100UDC DHR9DE S2 Type
Black
1, 3R, 12 1
PHB2N12F
Red/Yellow
1, 3R, 12 1
PHR2N12F
Black
4, 4X 1
PHB2N4XF
Red/Yellow
4, 4X 1
PHR2N4XF
7.90 (200.0)
SF200PH10X10
12.60 (320.0)
SF320PH10X10
15.7 0 (400.0)
SF400PH10X10
C Type
1st Contact
NO+NC
AC1NONCDE
C Type
2nd Contact
NO+NC
AC2NONCDE
3P 2
TS3R9DT
3P 3
TS3R9DB
4P 4
TS4R9DTB
3P 4
LK3R9DL
4P 4
LK4R9DL
2 pieces
DCJUMPD2
3 pieces
DCJUMPD3
4R9D4100UDC
200 3 R9D3200UDC
4R9D4200UDC
400 3 R9E3400UDC 3P 2
TS3R9ET
3P 3
TS3R9EB
4P 4
TS4R9ETB
3P 4
LK3R9EM
4P 4
LK4R9EM
2 pieces
DCJUMPE2
3 pieces
DCJUMPE3
4R9E4400UDC
+++
Switch body Direct handle Switch body Shaft External handle
+++
Switching Devices PG00802002E—September 2012 www.eaton.com 49
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Accessories
Direct Handle
Door Interlocked External Handle Front Operation—l–0, Three- and Four-Pole
Auxiliary Contacts
Terminal Screens
Note
1 Order two sets for line and load sides.
Description Ampere Rating Handle Color Catalog Number
Front operation 100–400 Black DHR9DE
Ampere Rating Handle Handle Color NEMA Type Catalog Number
100–400 PH2 Type Black 1, 3R, 12 PHB2N12F 1
100–400 PH2 Type Red/yellow 1, 3R, 12 PHR2N12F 1
100–400 PH2 Type Black 4, 4X PHB2N4XF 1
100–400 PH2 Type Red/yellow 4, 4X PHR2N4XF 1
Description Ampere Rating Number of AC Type Catalog Number
Early-break/same-make and
signaling of positions 0 and 1:
1 to 2NO/NC auxiliary contacts
1 to 2 low level NO/NC auxiliary
contacts
Characteristics: NO/NC
AC: IP2 with front and side operation
Connection to the control circuit:
By 6.35 mm fast-on terminal
Electrical Characteristics:
30,000 operations; A300
NO/NC Contact for Three and Four Poles
100–400 1 AC
NO + NC
C Type AC1NONCDE
100–400 2 AC
NO + NC
C Type AC2NONCDE
Low Level NO/ NC Contact for Three and Four Poles
100–400 1 AC
NO + NC
C Type AC1NONCDELL
100–400 2 AC
NO + NC
C Type AC2NONCDELL
Description Ampere Rating Number of Poles Position Catalog Number
Line or load side protection against
direct contact with terminals or
connection parts
Three- and Four-Pole
100–200 3 Top (line) TS3R9DT
100–200 3 Bottom (load) TS3R9DB
100–200 4 Top or bottom (line or load) TS4R9DTB
400 3 Top (line) TS3R9ET
400 3 Bottom (load) TS3R9EB
400 4 Top or bottom (line or load) TS4R9ETB
Direct Handle
PH2 Type Handle
50 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Line and Load Terminal Lugs
Jumpers for Connecting Poles in Series
Shaft Extensions for External Front Dimensions (X)—Inches (mm)
Note
1 For other connections, refer to installation instructions.
Description Ampere Rating Connection Type
Number of Cables
per Terminal Lugs per Kit Cable Type Catalog Number
Connection of bare copper
cables onto the terminals
100–200 6–300 kcmil 1 2 Cu/Al LK2R9DL
100–200 6–300 kcmil 1 4 Cu/Al LK4R9DL
400 2–600 kcmil 1 2 Cu/Al LK2R9EM
400 2–600 kcmil 1 4 Cu/Al LK4R9EM
Description Ampere Rating Kit of Figure Number of Poles in Series Catalog Number
The jumpers will make easy
the connection of the poles in series,
allowing the following
configurations: 1
100–200 2 Pieces 1 3 DCJUMPD2
100–200 3 Pieces 2 4 DCJUMPD3
400 2 Pieces 1 3 DCJUMPE2
400 3 Pieces 2 4 DCJUMPE3
Description
Ampere
Rating
Dimension X
In (mm) Handle
Shaft Length
In (mm) Catalog Number
Standard lengths:
7.9 inches/200 mm
12.6 inches/320 mm
15.7 inches/400 mm
For Three- and Four-Pole
100–400 135–265 (3429.0–6731.0) PH2 Type 7.90 (200.0) SF200PH10X10
100–400 135–385 (3429.0–9779.0) PH2 Type 12.60 (320.0) SF320PH10X10
100–400 135–465 (3429.0–11811.0) PH2 Type 15.70 (400.0) SF400PH10X10
Line and Load Terminal
Lugs
-
+
Load
Load
-
+
X
Switching Devices PG00802002E—September 2012 www.eaton.com 51
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Technical Data and Specifications
100–400A
Characteristics According to UL 98
Characteristics According to IEC 60947-3
Ampere Rating
Thermal Current Ith
at 40°C (A) 100 200 400
General Use Purpose Ampere Rating
Rated voltage In series A A A
600 Vdc 3P 100 200 400
Overload Capacity
Prospective short-circuit current (kA rms) 20 20 20
Type of fuse A70P100 A70P200 LDC
Fuse rating 100 200 400
Connection Terminals
Minimum connection section/AWG #6 #6 #2
Maximum connection section/AWG 300 kcmil 300 kcmil 600 kcmil
Auxiliary Contacts
Electrical characteristics A300 A300 A300
Ampere Rating
Thermal Current Ith
at 40°C (A) 160 250 630
Rated Operational Currents Ie (A), DC-22 B
Rated voltage In series A A A
750 Vdc 3P 160 250 400
750 Vdc 4P
1000 Vdc 4P 160 250 400
52 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Dimensions
Approximate Dimensions in Inches (mm)
R9 Series DC Rated Disconnects 100–400A
Front Operation
R9 Series DC Rated Disconnects
Ampere
Rating C AC AD F 3P F 4P H J1 3P J1 4P K M 3P M 4P
100–200 3.72 (94.5) 10.10 (256.5) 3.05 (77.5) 7.09 (180.1) 9.06 (230.0) 4.22 (107.2) 2.17 (55.1) 4.13 (104.9) 1.80 (45.7) 6.30 (160.0) 8.27 (210.1)
400 4.92 (125.0) 16.00 (406.4) 4.51 (114.5) 9.05 (230.0) 11.40 (290.0) 6.53 (166.0) 2.95 (75.7) 5.31 (134.9) 2.65 (67.3) 8.26 (209.8) 10.60 (269.2)
Ampere
Rating N R1 R2 T U V W Y Z AA CA
100–200 5.31 (135.0) 0.35 (8.9) 0.27 (6.9) 1.97 (50.0) 0.98 (24.9) 1.18 (30.0) 0.43 (10.9) 0.14 (3.6) 1.35 (34.3) 6.30 (160.0) 0.60 (15.2)
400 7.60 (193.0) 0.35 (8.9) 0.27 (6.9) 2.56 (65.0) 1.77 (45.0) 1.97 (50.0) 0.43 (10.9) 0.20 (5.1) 2.08 (52.8) 10.20 (259.1) 0.80 (20.3)
Y
AC
K
CA
V
NAA
H
Z
J1 U
R1
M
AD
T
FC
R2
W
Eaton
The switch will operate correctly when
rotated clockwise 90 degrees.
The switch will not operate correctly when
rotated counterclockwise 90 degrees.
Switching Devices PG00802002E—September 2012 www.eaton.com 53
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Approximate Dimensions in Inches (mm)
Jumpers
100–200A 400A
Terminal Lugs
100–200A 400A
22.50
(571.5)
19.00
(482.6)
81.00
(2057.4)
22.50
(571.5)
5.00
(127.0)
65.00
(1651.0)
0.49
(12.5)
Ø0.43
(Ø11.0)
0.47
(12.0)
0.59
(15.0)
1.97
(50.0)
0.49
(12.5)
0.16
(4.0)
1.0 0
(25.4)
1.52
(38.6)
1.12
(28.4)
0.45
(Ø11.4)
2.80
(71.5)
Ø 0.40 (Ø10.16)
Ø 4.70 (Ø119.38)
1.30
(35.0)
1.80
(46.0)
0.44
(11.13)
0.63
(15.9)
54 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
R9 Series (UL 98) DC Rated Disconnects
Approximate Dimensions in Inches (mm)
Door Interlocked External Handle—100 to 400A, Three- and Four-Pole
PH2 Type Handle
Direction of Operation
Door Drilling Template
Ø3.07 (Ø78.0)
4.92
(125.0)
1.77
(45.0)
90
0
I
1.57
(40.0)
4Ø7
Ø1.46
(37.0) 1. 10
(28.0)
Switching Devices PG00802002E—September 2012 www.eaton.com 55
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Contents
Description Page
Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . 55
Standards and Certifications . . . . . . . . . . . . . . . . . 55
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Technical Data and Specifications. . . . . . . . . . . . . . 59
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Product Overview
R9 Series (UL® 98 listed)
non-fusible disconnects are
heavy-duty manual transfer
switches, they transfer load
manually between two low
voltage circuits and provide
safety disconnection.
These switches are
extremely durable and are
tested and approved for use
in the most demanding
applications as resistive load
or total system applications.
Three load break
positions (I, 0, II)
On load switching
Direct or external handle
480 Vac total system
600 Vac resistive load
Standards and Certifications
UL 98, cULus®,
File E222859
UL 1008 (600–1200A)
CSA® 22.2 No. 4,
File 217736
IEC 60947-3
EN 60947-3
CE
Overview
1External front handle
2Direct handle
3Shaft extension for external handle
4Pre-break ACs (standard on 600–1200A)
5Terminal screen
5
4
1
3
2
56 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Product Selection
Manual Transfer/Double Throw Switches—UL 98 Standard 1
Notes
1All ratings, 100–1200A, are UL 98 listed; switches rated 600–1200A are also UL 1008 listed.
2Line or load (top or bottom); for both line and load, order two kits.
3Low level auxiliary contact—gold plated for minimal resistance—for PLC applications.
Ampere
Rating
Number
of Poles
Switch
Body Only 1
Direct
Handle (Black)
External Three-
Position Handle
(Choose one)
Shaft Extensions for
External Handle
In (mm)
(Choose one)
Bridging
Bars
Auxiliary
Contacts
Terminal
Screens 2
100 3 RMTS3100U DHMTSSL Size 2, Black
I–0–II
Type 4/4X
PHB2N4X3P
Size 2, Red
I–0–II
Type 4/4X
PHR2N4X3P
7.90 (200.6)
SF200PH10X10
12.60 (320.0)
SF320PH10X10
15.70 (398.8)
SF400PH10X10
3P
BB3P200
4P
BB4P200
NO/NC
AC1NONCMTS400
Low level
AC1NONCMTS400LL 3
3P
TS3MTS200TB
4P
TS4MTS200TB
4RMTS4100U
200 3 RMTS3200U
4RMTS4200U
400 3 RMTS3400U Size 3, Black
I–0–II
Type 4/4X
PHB3N4X3P
Size 3, Red
I–0–II
Type 4/4X
PHR3N4X3P
7.90 (200.6)
SF200PH15X12
12.60 (320.0)
SF320PH15X12
15.70 (398.8)
SF400PH15X12
3P
BB3P400
4P
BB4P400
3P
TS3MTS400TB
4P
TS4MTS400TB
4RMTS4400U
600 3 RMTS3600U DHMTSDL Size 4, Black
I–0–II
Type 4/4X
PHB4N4X3P
Size 4, Red
I–0–II
Type 4/4X
PHR4N4X3P
3P
BB3P600
4P
BB4P600
NO/NC
contact
standard
3P
TS3MTS600
4P
TS4MTS600
4RMTS4600U
800 3 RMTS3800U DHMTSDLM 3P
BB3P1200
4P
BB4P1200
3P
TS3MTS1200
4P
TS4MTS1200
4RMTS4800U
1200 3 RMTS31200U
4RMTS41200U
+++
Switch body Direct handle Switch body Shaft External handle
+++
Direct Operation External Operation
Switching Devices PG00802002E—September 2012 www.eaton.com 57
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Accessories
Direct Handle
External Handle
Shaft Extension
Ampere Rating Handle Color Handle Type Catalog Number
100–400 Black Single lever DHMTSSL
600 Black Double lever DHMTSDL
800–1200 Black Double lever DHMTSDLM
Description Ampere Rating Handle Type Handle Color NEMA Type
Lockable in
the “3” Positions Catalog Number
The handle locking function
prevents the user from
opening the door of the
enclosure when the switch is
in the "ON" position.
Opening the door when the
switch is in the "ON" position
is possible by defeating the
locking function with the use
of a tool (authorized persons
only). The locking function is
restored when the door is
once again closed.
100–200 PH2 Black 4, 4X Yes PHB2N4X3P
100–200 PH2 Red/Yellow 4, 4X Yes PHR2N4X3P
400 PH3 Black 4, 4X Yes PHB3N4X3P
400 PH3 Red/Yellow 4, 4X Yes PHR3N4X3P
600–1200 PH4 Black 4, 4X Yes PHB4N4X3P
600–1200 PH4 Red/Yellow 4, 4X Yes PHR4N4X3P
Ampere Rating Handle Type
Length
In (mm) Catalog Number
100–800 PH1 7.90 (200.6) SF200PH10X10
125–800 PH1 12.60 (320.0) SF320PH10X10
100–200 PH2 15.70 (398.8) SF400PH10X10
630–1200 PH2, PH3 7.90 (200.6) SF200PH15X12
600–1200 PH2, PH3 12.60 (320.0) SF320PH15X12
400–1200 PH2, PH3 15.70 (398.8) SF400PH15X12
800–1200 V1 12.60 (320.0) SF320V1
800–1200 V1 15.70 (398.8) SF400V1
PH4 Type
PH2 and PH3 Type
58 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Bridging Bars
Terminals Protection Screen
Mounting Spacers
Auxiliary Contacts
Line and Load Terminal Lugs
Note
1 Gold plated for minimal resistance—for PLC applications.
Description Ampere Rating Number of Bridging Bars Catalog Number
Creation of a common point, above or below
the switch, between positions I and II.
100–200 3 BB3P200
100–200 4 BB4P200
400 3 BB3P400
400 4 BB4P400
600 3 BB3P600
600 4 BB4P600
800–1200 3 BB3P1200
800–1200 4 BB4P1200
Description Ampere Rating Number of Poles Catalog Number
Top or bottom (line or load) protection
against direct contacts with terminal
or connecting parts.
100–200 3 TS3MTS200TB
100–200 4 TS4MTS200TB
400 3 TS3MTS400TB
400 4 TS4MTS400TB
600 6 TS3MTS600
600 4 TS4MTS600
800–1200 3 TS3MTS1200
800–1200 4 TS4MTS1200
Description Ampere Rating Number of Poles Catalog Number
Raises the device’s terminals 10 mm away
from the bottom of the enclosure or frame
on which the device is mounted.
100–400 1 set of 2 spacers MSP400
Description Ampere Rating Contact (s) Catalog Number
Early-break/same-make and signalization per
position 1 and 2.
Electrical characteristics:
A300.
100–400 1NO/NC per position 1 and 2 AC1NONCMTS400
100–400 1NO/NC per position 1 and 2 low level AC1NONCMTS400LL 1
600–1200 1NO/NC per position 1 and 2 Standard
Description Ampere Rating
Connection
Type
Number of
Poles
Number of Cables/
Lug Lugs per Kit Cable Type Catalog Number
Connection of bare
copper cables onto the
terminals (without
spade lugs).
100–200 6–300 kcmil 3 1 3 Cu/Al LK3R9DL
100–200 6–300 kcmil 4 1 4 Cu/Al LK4R9DL
400 4–600 kcmil 3 1 3 Cu/Al LK3R9EM
400 4–600 kcmil 4 1 4 Cu/Al LK4R9EM
600 2x (#2–600 kcmil) 3 2 3 Cu/Al LK3R9FN
600 2x (#2–600 kcmil) 4 2 4 Cu/Al LK4R9FN
800–1200 2x (#2–600 kcmil) 3 2 6 Cu/Al LK6R9G
800–1200 2x (#2 –600 kcmil) 4 2 8 Cu/Al LK8R9G
Switching Devices PG00802002E—September 2012 www.eaton.com 59
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Technical Data and Specifications
UL 1008 Characteristics
UL 98/CSA 22.2 No. 4 Characteristics
Notes
1Short-circuit rating achieved when used with respective fuse type and maximum fuse rating.
2Only UL 98 listed. For UL 1008 availability, contact Eaton.
3Two-pole in series.
4Three-pole in series.
Description 100A 200A 400A 600A 800A 1200A
Operation voltage 600 600 600 600 600 600
Short-circuit rating at 600 Vac (kA) 1100 100 65 100 100 100
Type of fuse J J J L L L
Maximum fuse rating (A) 200 400 600 800 1000 1600
Short-circuit rating with circuit breaker (kA/ms) 10/25 10/25 14/50 35/50 35/50 35/50
Operational Power/Current Maximum Operational Three-Phase
240 Vac total system (A) 100 100 250 400 700 700
240 Vac resistive load (A) 100 200 400 600 800 1200
480 Vac total system (A) 100 100 125 350 600 600
480 Vac resistive load (A) 100 200 400 600 800 1200
600 Vac resistive load (A) 100 200 400 400 800 1200
Mechanical Endurance
Endurance (number of operating cycles) 6050 6050 6050 6050 3550 3550
Connection Terminals
Minimum connection section/AWG #6 #6 #4/2 x #6 2x #2 4x #2 4x #2
Maximum connection section/AWG 300 kcmil 300 kcmil 600 kcmil/2x 350 kcmil 2x 600 kcmil 4x 600 kcmil 4x 600 kcmil
Description 100A 2200A 2400A 2600A 800A 1200A
Short-circuit rating at 600 Vac (kA) 200 200 200 200 100 100
Type of fuse J J J J L L
Maximum fuse rating (A) 100 200 400 600 800 1200
Maximum Motor, hp/FLA Three-Phase Motor Maximum
220–240 Vac 30/80 75/192 125/312 200/480 200/480 200/480
440–480 Vac 75/96 180/180 250/302 400/477 500/590 500/590
600 Vac 100/99 200/192 350/336 350/336 500/472 500/472
Maximum Motor Power, hp/DC FLA Motor Maximum
125 Vdc 37.5/58 15/112 20/148 20/148
250 Vdc 420/72 40/140 50/173 50/173
Mechanical Characteristics
Endurance (number of operating cycles) 10,000 8000 6000 6000 3500 3500
Operating torque (lbs.in/Nm) 88.5/10 88.5/10 128.3/14.5 327.5/37 442.5/50 442.5/50
Auxiliary Contacts
Electrical characteristics A300 A300 A300 A300 A300 A300
60 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Dimensions
Approximate Dimensions in Inches (mm)
100 to 200A
400A
6.41
(162.8)
5.19
(131.8) 1.53
(38.9)
5.51
(140.0)
4.29
(109.0)
6.77
(172.0)
5.51
(140.0)
0.41
(10.4)
1.18
(30.0)
0.98
(24.9)
1.37
(34.8)
0.53
(13.5)
Ø0.43
Ø(11.0)
View “A
View “B”
“B
“A”
Ø0.35
Ø(9.0)
Ø0.27
Ø(6.9)
0.29
(7.4)
1.97
(50.0)
6.30
(160)
5.31
(134.9)
2.67
(67.8)
3P
Fix 6.30
(160.0)
4P
Fix 8.26
(210.0)
3P
9.64
(245.0)
4P
11.41
(290.0)
9.41
(239.0)
7.48
(190.0)
2.04
(51.8)
0.41
(10.4)
View “A
View “B”
Ø0.35
Ø(9.0)
Ø0.27
Ø(6.9)
0.29
(7.4)
8.26
(209.8)
8.26
(209.8)
6.53
(165.9)
10.90
(277.0)
“A”
1.38
(35.1)
Ø0.43
Ø(11.0)
0.49
(12.4)
“B
1.37
(34.8)
7.67
(194.8)
3.85
(97.8)
10.23
(259.8)
2.56
(65.0)
3P
Fix 8.26
(210.0)
4P
Fix 10.63
(270.0)
3P
11.85
(301.0)
4P
14.21
(361.0)
Switching Devices PG00802002E—September 2012 www.eaton.com 61
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Approximate Dimensions in Inches (mm)
600A
800 to 1200A
14.56
(369.8)
9.98
(253.5) 2.61
(66.3)
9.09
(230.9)
9.09
(230.9)
13.66
(347.0)
View “A
“A
Ø0.41
Ø(10.5)
1.12
(28.4)
0.82
(20.8)
1.96
(49.8)
0.98
(24.9)
2.02
(51.3)
4.92
(125.0)
9.84
(249.9)
13.38
(339.9)
3.15
(80.0)
3P
Fix 10.04
(255.0)
4P
Fix 13.18
(335.0)
3P
15.19
(386.0)
4P
18.34
(466.0)
14.56
(369.8)
9.98
(253.5)
2.65
(67.3)
8.30
(210.8)
8.30
(210.8)
8.03
(204.0)
13.66
(347.0)
Ø0.41
Ø(10.5) View “A
“A
3.54
(89.9)
1.49
(37.8)
1.02
(25.9)
0.82
(20.8)
1.02
(25.9)
1.49
(37.8) 2.02
(51.3)
11.34
(288.0)
4.72
(119.9)
9.84
(249.9)
4.92
(125.0)
3P
Fix 13.66
(347.0)
4P
Fix 18.38
(467.0)
3P
15.19
(386.0)
4P
18.34
(466.0)
62 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Approximate Dimensions in Inches (mm)
Terminal Lugs
100–200A 400A 600–1200A
100–200A
PH2 Type Direction of Operation Door Drilling Template
400A
PH3 Type Direction of Operation Door Drilling Template
1.0 0
(25.4)
1.52
(38.6)
1.12
(28.4)
0.45
(Ø11.4)
2.80
(71.5)
Ø 0.40 (Ø10.16)
Ø 4.70 (Ø119.38)
1.30
(35.0)
1.80
(46.0)
0.44
(11.13)
0.63
(15.9)
2.87
(72.9)
3.15
(80.0)
1.49
(37.8)
0.40
(Ø10.2)
Ø3.07
(Ø78.0)
1.77
(45.0)
4.92
(125.0)
4 Ø 0.27
4 Ø 7.0
Ø D
90
90
I
II
0.79
(20.0)
0
0.79
(20.0)
0.55
(14.0) 0.55
(14.0)
Ø78
(Ø1981.2)
61.00
(1549.4)
210
(5334.0)
90
90
I
II
0
4 Ø 0.27
4 Ø 7.0
Ø D 0.79
(20.0)
0.79
(20.0)
0.55
(14.0) 0.55
(14.0)
Switching Devices PG00802002E—September 2012 www.eaton.com 63
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Manual Transfer/Double Throw Switches
Approximate Dimensions in Inches (mm)
600–1200A
PH4 Type Direction of Operation Door Drilling Template
0
I
II
2.36
(60.0)
13.77
(350.0)
4 Ø 7
(4 Ø 7)
Ø D
90
90
0.79
(20.0)
Ø3.07
(Ø78.0)
0.79
(20.0)
0.55
(14.0)
0.55
(14.0)
64 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Enclosed Rotary Disconnects
Enclosed Rotary Disconnects
Contents
Description Page
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . 64
Features, Benefits and Functions. . . . . . . . . . . . . . 64
Standards and Certifications . . . . . . . . . . . . . . . . . 64
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Product Overview
Provide users with the ability
to lock directly wired motor
loads in the OFF position to
comply with OSHA lockout/
tagout regulations. Also for
machine applications that
require compact, economical
disconnect switches.
Enclosed rotary disconnect
switches allow safe control
and safe disconnect of any
motor application.
Features, Benefits
and Functions
Padlockable in the OFF
position (up to three
padlocks) to meet OSHA
lockout requirements
Available in 16–80A ratings
600 Vac, three- and four-
pole non-fusible device
Rated for making and
breaking loads
Accepts auxiliary contacts;
capability to signal PLC
controllers
Ground lug connection
provided
Possibility of adding one
power pole and one
auxiliary contact
NEMA® Type 1, 3R, 12,
4, 4X
Open rotary disconnects
can be found in Volume 5,
Motor Control and Protection
Catalog CA08100006E.
Standards and Certifications
Meets NEC® Article 430
requirements for a
separate disconnect
means within sight
of all motor loads
UL® listed under
Section 508
UL listed File No. E165150
CSA® listed under 22.2
No. 14, File 162136
Switching Devices PG00802002E—September 2012 www.eaton.com 65
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Enclosed Rotary Disconnects
Product Selection
Enclosed Rotary Non-Fusible 1
Accessories for Enclosed Rotary Disconnects 67
Notes
1Short-circuit current ratings are same as those listed in the table on Page 10, for the respective disconnect amperage.
2For CSA listed switches, add prefix letter “C” to the front of the catalog number.
3NEMA Type 12 enclosures (16–80A) can be field modified to meet NEMA Type 3R rainproof requirements when a factory-provided drain hole is opened.
4“GB” suffix = Gray cover, Black handle; “GR” suffix = Gray cover, Red handle; “YR” suffix = Yellow cover, Red handle.
5cULus only.
6Ordered and shipped as separate components—not integral to enclosed device.
7Enclosed disconnects can accept one power pole, neutral or up to two auxiliary contacts (one mounted on either side of switch).
Contact the Safety Switch Flex Center (1-888-329-9272) for factory-installed accessories or other special modifications.
Ampere
Rating
Maximum Horsepower Ratings
NEMA 1 2
Enclosure
Indoor
NEMA 12 2 3
Enclosure
Dust-Tight/
Rainproof
NEMA 4X 2
Enclosure
Corrosion-Resistant,
Stainless Steel
NEMA 4X 2
Enclosure
Corrosion-Resistant,
Non-Metallic
NEMA 4X
Enclosure
Polycarbonate-
Non-MetallicThree-Phase AC
208V 240V 480V 600V Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Three-Pole, 600 Vac
16 351010ER53016UG ER53016UD ER53016UW ER53016UX
25 7-1/2 7-1/2 15 20 ER53025UG ER53025UD ER53025UW ER53025UX
30 7-1/2 7-1/2 15 20 ER53030UG ER53030UD ER53030UW ER53030UX ER53030UPGB 45
40 7-1/2 7-1/2 20 25 ER53040UG ER53040UD ER53040UW ER53040UX
60 15 15 30 30 ER53060UG ER53060UD ER53060UW ER53060UX ER53060UPGB 45
80 15 20 40 40 ER53080UG ER53080UD ER53080UW ER53080UX
Four-Pole, 600 Vac
16 351010ER54016UG ER54016UD ER54016UW ER54016UX
25 7-1/2 7-1/2 15 20 ER54025UG ER54025UD ER54025UW ER54025UX
30 7-1/2 7-1/2 20 25 ER54030UG ER54030UD ER54030UW ER54030UX
40 7-1/2 7-1/2 20 25 ER54040UG ER54040UD ER54040UW ER54040UX
Disconnect
Ampere Rating
Switched
Fourth Pole
Unswitched
Neutral Pole
Auxiliary Contacts
(Choose one)
Terminal
Shrouds
16 S4PR516 UNMR5A 1NO + 1NC
AC1NONC
2NC
AC2NC
Single-pole
TS1R5A
Three-pole
TS3R5A
25 S4PR525
30 S4PR530
40 S4PR540
60 S4PR560 UNMR5B Single-pole
TS1R5B
Three-pole
TS3R5B
80 S4PR580
66 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Enclosed Rotary Disconnects
Dimensions
Approximate Dimensions in Inches (mm)
NEMA Type 1 (16–40A)
NEMA Type 1 (60–80A)
Note:
Wire range of switch lugs for 16–25A is #6–#10 copper, and for 30–40A is #8–#14.
Wire range of ground lugs is #2–#14 copper or aluminum.
8.47
(215.1) 6.86
(174.2)
0.31
(7.9)
2 Mounting Holes
2.68
(68.1)
2.68
(68.1)
0.27
(6.9) 0.56
(14.2)
3.20
(81.3)
1.44
(36.6)
Concentric knockouts for
0.5-, 0.75-inch conduit,
quantity 4, knockout
locations same in top
and bottom
6.42
(163.1) 6.55
(166.4) 5.50
(139.7)
4.11
(104.4)
8.11
(206.0)
5.00
(127.0)
8.42
(213.9) 8.56
(217.4)
0.27
(6.9) 0.56
(14.2)
7.75
(196.9)
3.50
(88.9)
10.47
(265.9)
5.67
(144.0)
4.23
(107.4)
1.96
(49.8)
1.32
(33.5) 2.46
(62.5)
1.86
(47.2)
Concentric knockout
for 0.5, 0.75, 1 conduit,
quantity 2, knockout
location same in top
and bottom
Concentric knockout
for 1.25, 1.5, 2 conduit,
quantity 2, knockout
location same in top
and bottom
5.75
(146.1) 0.31
(7.9)
2 Mounting Holes
3.53
(89.7)
10.11
(256.8)
Note:
Wire range of switch lugs is #1–#14 copper.
Wire range of ground lugs is #2–#14 copper or aluminum.
Switching Devices PG00802002E—September 2012 www.eaton.com 67
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Enclosed Rotary Disconnects
Approximate Dimensions in Inches (mm)
NEMA Type 12/3R (16–40A)
NEMA Type 12/3R (60–80A)
n 0.31
(7.9) Hole
2.68
(68.1)
9.26
(235.2)
9.98
(253.5)
8.14
(206.8)
8.99
(228.3)
3.91
(99.3)
2.68
(68.1)
0.31
(7.9)
7.35
(186.7) 6.45
(163.8)
5.66
(143.8)
4.26
(108.0)
Screw to be removed when
used as Type 3R device
Note:
Wire range of switch lugs for 16–25A is #6–#10
copper, and for 30–40A is #8–#14 copper or aluminum.
11.98
(304.3)
5.81
(147.6)
4.38
(111.3)
10.14
(257.6)
10.99
(279.1)
11.26
(286.0)
5.75
(146.1)
3.50
(88.9)
3.53
(89.7)
0.31
(7.9) n 0.31
(7.9) Hole
9.35
(237.5)
8.45
(214.6)
Screw to be removed when used as Type 3R device
Notes:
Wire range of switch lugs is #1–#14 copper.
Wire range of ground lugs is #2–#14 copper or aluminum.
68 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Enclosed Rotary Disconnects
Approximate Dimensions in Inches (mm)
NEMA Type 4X Stainless (16–40A)
NEMA Type 4X Stainless (60–80A)
9.95
(252.7)
4.23
(107.4)
5.63
(143.0)
8.11
(206.0)
8.97
(227.8)
9.23
(234.4)
6.43
(163.3)
7.33
(186.2)
3.91
(99.3)
2.68
(68.1)
2.68
(68.1)
0.31
(7.9) n 0.31
(7.9) Hole
Notes:
Wire range of switch lugs for 16–25A is
#6–#10 copper, and for 30–40A is #8–#14.
Wire range of ground lugs is #2–#14
copper or aluminum.
4.35
(110.5)
5.78
(146.8)
10.11
(256.8)
10.97
(278.6)
11.95
(303.6)
8.43
(214.1)
9.32
(236.7)
11.23
(285.2)
5.75
(146.1)
3.50
(88.9)
3.53
(89.7)
0.31
(7.9)
Notes:
Wire range of switch lugs is #4–#14 copper.
Wire range of ground lugs is #2–#14 copper
or aluminum.
n 0.31
(7.9) Hole
Switching Devices PG00802002E—September 2012 www.eaton.com 69
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Enclosed Rotary Disconnects
Approximate Dimensions in Inches (mm)
NEMA Type 4X Thermoset Polyester (16–40A)
NEMA Type 4X Thermoset Polyester (60–80A)
Four Mounting Holes
4.70
(119.4)
6.10
(154.9)
9.63
(244.6)
2.65
(67.3)
2.65
(67.3)
8.88
(225.6)
0.31
(7.9)
4.00
(101.6)
5.00
(127.0)
7.52
(191.0)
9.52
(241.8) 9.63
(245.0)
Notes:
Wire range of switch lugs for 16–25A is #6–#10 copper, and for 30–40A is #8–#14.
Wire range of ground lugs is #2–#14 copper or aluminum.
13.41
(340.6)
11.43
(290.3)
9.00
(228.6)
8.00
(203.2)
4.48
(113.8)
13.56
(344.4)
12.75
(323.8)
4.51
(114.6)
13.56
(344.4)
5.24
(133.1)
6.67
(169.4)
Notes:
Wire range of switch lugs is #1–#14 copper.
Wire range of ground lugs is #2–#14 copper or aluminum.
70 Switching Devices PG00802002E—September 2012 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Switching Devices
Enclosed Rotary Disconnects
Approximate Dimensions in Inches (mm)
NEMA Type 4X—Polycarbonate (30A)
NEMA Type 4X—Polycarbonate (60A)
0.13
(3.3)
0.02
(0.5)
3.62
(91.9)
4.37
(111.0)
6.00
(152.4)
6.38
(162.1)
5.90
(149.9)
0.79
(20.1)
3.90
(99.1)
Ø2.68
(68.1)
7.32
(185.9)
7.80
(198.1)
0.16
(4.1)
0.02
(0.5)
3.62
(91.9)
4.37
(111.0)
8.27
(210.0)
0.59
(15.0)
4.45
(113.0)
4.94
(125.5)
Ø2.67
(67.8)
Notes:
Notes:
Notes:
R5 A 3 016 U
UL Listing
R5 = UL 508
R9 = UL 98
R4 = UL 489
Frame Designation
A = UL 508 (16–40A)
B = UL 508 (60–80A)
C = UL 98 Non-fusible (30–100A modular)
V = UL 98 Non-fusible (60–100A visible blade)
D = UL 98 Non-fusible (100–200A)
E = UL 98 Non-fusible (400A)
F = UL 98 Non-fusible (600A)
G = UL 98 Non-fusible (800–1200A)
H = UL 489 Fusible (30A compact)
I = UL 98 Fusible (30A)
J = UL 98 Fusible (30–60A)
K = UL 98 Fusible (60–100A)
L = UL 98 Fusible (200A)
M = UL 98 Fusible (400A)
N = UL 98 Fusibe (600–800A)
Poles
2 = Two-pole
3 = Three-pole
4 = Four-pole
Ampere Rating
016 = 16A
025 = 25A
030 = 30A
040 = 40A
060 = 60A
080 = 80A
100 = 100A
200 = 200A
400 = 400A
600 = 600A
800 = 800A
1000 = 1000A
1200 = 1200A
Protection
U = Non-fusible
F = Fusible
Fuse Type Accepted
CC = Class CC
J = Class J
L = Class L
Blank = Non-fusible device
SH B 00 4X F
SF 150 SH 5X5
Handle Type
SH = Selector handle
PH = Pistol handle
Product Type
SF = Shaft
Color
B = Black/blue
R = Red/yellow
Length
55 = 55 mm
90 = 90 mm
150 = 150 mm
200 = 200 mm
320 = 320 mm
400 = 400 mm
500 = 500 mm
Size
(Smallest to Largest)
00 = Size 00
0 = Size 0
1 = Size 1
2 = Size 2
3 = Size 3
4 = Size 4
Applicable
Handle Type
SH = Selector handle
PH = Pistol handle
NEMA Type Rating
12 = Type 1, 3R, 12
4X = Type 4, 4X
Operation
F = Front
S = Right Side
Blank = Front or right side
Shaft Cross Section
5x5 = 5 mm x 5 mm
6x6 = 6 mm x 6 mm
10x10 = 10 mm x 10 mm
12x12 = 12 mm x 12 mm
15x12 = 15 mm x 12 mm
Additional Features*
T = Test position function
Blank = No test function
*HV at the end of some catalog numbers
indicates use with H and V switches only.
Not all handles are designed to go with all
disconnects. Consult specific section of the
catalog for available options.
Additional Features*
*H at the end of some catalog numbers
indicates use with H-Frame switches only.
Not all shafts are designed to go with all
disconnects. Consult specific section of the
catalog for available options.
Disconnects
External Handles
Shafts
Catalog Numbering Systems
Direct
Handles
Direct
Handles
Auxiliary
Contacts
Auxiliary
Contacts
Fusible
Disconnect
Non-Fusible
Disconnect
Available
Shafts
Available
Shafts
External
Handles
R Series Rotary Disconnects
SH_00_
R4 H-Frame
30A-CC/J
DHR9HC
SF_
_
_PH10X10
SF_
_
_PH10X10
SF_
_
_PH10X10 SF_
_
_PH10X10
SF_
_
_PH10X10 SF_
_
_PH10X10
SF_
_
_PH10X10 SF_
_
_PH15X12
SF_
_
_PH12X12 SF_
_
_PH15X12
AC1NOR9
AC1NCR9
SF_
_SH5X5
SF_
_
_SH5X5
SF_
_
_SH5X5H
SF_
_
_PH5X5
SF_
_SH5X5
SF_
_
_SH5X5
AC1NO1NCJ2N
AC2NO2NCJ2N
AC1NO1NCJ2N
AC2NO2NCJ2N
AC1NO1NCJ2N
AC2NO2NCJ2N
AC1NO1NCJ2N
AC2NO2NCJ2N
AC1NO1NCJ2N
AC2NO2NCJ2N
SF_
_
_SH6X6
SF_
_
_PH6X6
AC1NO1NCJ2N
AC2NO2NCJ2N
R5 A- & B-Frame
(16–40A & 60–80A) DHR5
DHR9
DHR9V
R9 C-Frame
30–100A Modular
AC1NONC
AC2 NO
AC1NONC
AC2 NO
AC1NONC
AC2 NO
AC1NOR9
AC1NCR9
AC1NOR9
AC1NCR9
AC1NOR9
AC1NCR9
ACHFG
R9 J-Frame
30–60A J
R9 I-Frame
30A-CC
DHR9HJ
DHR9J2M
DHR9J2M DHR9DE
DHR9J2M
DHR9J2M
SH_0_
PH_1_
PH_2_
PH_3_
PH_4_
R9 K-Frame
60–100A J
R9 V-Frame
60–100A Visible Blade
R9 D-Frame
100–200A AC1NONC_
AC1 NONC_
R9 E-Frame
400A
R9 F-Frame
600A
R9 G-Frame
800–1200A
R9 L-Frame
200A J
R9 M-Frame
400A J
R9 N-Frame
600–800A J/L
DHR9N
DHR9DE
DHR9FG
DHR9FG
For reference onlyplease consult specific catalog pages for detailed information.
60A J-Frame (100 kAIC), K-Frame (200 kAIC).
AC1NOR9
AC1NCR9
AC1NOR9
AC1NCR9
AC1NOR9
AC1NCR9
AC1NOR9
AC1NCR9
AC1NOR9
AC1NCR9
AC1NOR9
AC1NCR9
Eaton is dedicated to ensuring that reliable, efficient and safe
power is available when it’s needed most. With unparalleled
knowledge of electrical power management across industries,
experts at Eaton deliver customized, integrated solutions to
solve our customers’ most critical challenges.
Our focus is on delivering the right solution for the application.
But, decision makers demand more than just innovative products.
They turn to Eaton for an unwavering commitment to personal
support that makes customer success a top priority. For more
information, visit www.eaton.com/electrical.
Eaton is a registered trademark
of Eaton Corporation.
All other trademarks are property
of their respective owners.
Eaton Corporation
Electrical Sector
1111 Superior Avenue
Cleveland, OH 44114 USA
Eaton.com
© 2012 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. PG00802002E / Z12653