Data sheet
ECOLINE
CP SNT 500W 24V 20A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date April 14, 2020 3:42:00 AM CEST
Catalogue status 03.04.2020 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 227.5 mm Width (inches) 8.957 inch
Height 125 mm Height (inches) 4.921 inch
Depth 110 mm Depth (inches) 4.331 inch
Weight 2 kg Net weight 2,914 g
Temperatures
Operating temperature, max. 70 °C (Derating ab 55 °C) Operating temperature, min. -10 °C
Storage temperature, max. 85 °C Storage temperature, min. -20 °C
Operating temperature -10 °C...70 °C (Derating ab
55 °C)
Storage temperature
-20 °C...85 °C
Environmental Product Compliance
REACH SVHC Lead 7439-92-1
Rated data UL
Certificate No. (cURus) E255651
Input
Connection range AWG26-12/0.13-6.0 mm² Connection system Screw connection
DC input voltage range
80...370 V DC
Input current 9 A @ 115 V AC / 6 A @
230 V AC
Input frequency
50/ 60 Hz
Input fuse Fusible link 10 A (T) / 250
V
Input fuse (internal)
Yes
Input voltage (voltage mode input) 88...132 V AC/176...264
V AC selectable; 250...370
V DC
Recommended back-up fuse 10 - 16 A, char. C, circuit
breaker
Surge protection
Varistor
Wire connection method Screw connection
Output
Connection range AWG26-12/0.13-6.0 mm² Control at 10...100% load <2%
Control at input voltage
0.5%
Mains failure bridge-over time 10 ms @ 115 V AC / 15
ms @ 230 V AC
Max. capacitance at output
40000 µF
Max. residual ripple < 100 mVSS / 20 MHz
bandwidth
Output current 2...20 A @ 200...240 V AC;
2...16 A @ 100...120 V AC
Output power
480 W
Output voltage
24 V
Output voltage 24...28 V (adjustable via
potentiometer)
Output voltage type
DC
Overload protection 105 %...130 % Ikonst
of max. Output line;
automatic reboot
Parallel connection option Recommended with diode
module
Status relay / CO contact 250 V AC (max. 30 V
DC) / 1 A
Surge protection 30...36 V Wire connection method Screw connection