P. 1 IMJFS07 – REV D
RATINGS AND SPECIFICATIONS FOR LAMBDA MODEL NO. JFS0750:
I. MAXIMUM RATINGS
SPECIFICATION UNITS JFS0750-24 JFS0750-48
OUTPUT VOLTAGE RANGE V 20-29 36-56
MAXIMUM OUTPUT CURRENT
(POWER) AT 50°C (AT
V
OUTNOM
)
A (W) 31.2 (750) 15.6 (750)
MAXIMUM OUTPUT CURRENT
(POWER) AT 60°C (AT
V
OUTNOM
)
A (W) 23.4 (562) 11.7 (562)
MAXIMUM OUTPUT CURRENT
(POWER) AT 70°C (AT
V
OUTNOM
)
A (W) 15.6 (375) 7.8 (375)
OPERATING TEMPERATURE °C CONTINUOUS DUTY FROM –20°C TO +70°C
THIRTY MINUTE WARM-UP REQUIRED AT –20°C
II. INPUT SPECIFICATIONS
SPECIFICATION UNITS JFS0750-24 JFS0750-48
INPUT VOLTAGE RANGE VAC 85-265 (47-63 Hz.)
INPUT CURRENT (RMS) A 9.0 AT 110VAC
INPUT CURRENT (PEAK, AT
COLD START)
A 35 AT 110VAC
IN
70 AT 220VAC
IN
INPUT POWER (MAXIMUM) W 1050 AT 85 VAC
IN
INPUT SURGE PROTECTION COMPLIANT TO IEC1000-4-5, LEVEL 3 STANDARDS
INPUT EMI, CONDUCTED
EMISSIONS
FCC CFR PART 15, SUBPART J CLASS A STANDARDS
EN55022 CLASS A STANDARDS
EFFICIENCY AT P
OUTMAX
% 75 TYPICAL AT 85VAC
IN
POWER FACTOR
CORRECTION AT P
OUTMAX
% 99 TYPICAL, PER IEC1000-3-2 STANDARDS
INPUT CURRENT
HARMONICS
COMPLIANT WITH EN60555-2 ABOVE TEN
PERCENT RATED POWER
III. OUTPUT SPECIFICATIONS
SPECIFICATION UNITS JFS0750-24 JFS0750-48
LINE AND LOAD REGULATION % ±1 FROM NO LOAD TO FULL LOAD, 85-265VAC
RIPPLE AND NOISE AT 20 MHz
MEASUREMENT BANDWIDTH
(0-70°C) PER EIAJ METHOD
mV 250
PEAK TO PEAK
500
PEAK TO PEAK
TEMPERATURE DRIFT % ±2 OVER TEMPERATURE RANGE AND LIFE
HOLD-UP TIME ms OUTPUT REMAINS ABOVE V
OUTMIN
LIMIT FOR
16ms UPON REMOVAL OF INPUT VOLTAGE AT Vin Nom (110Vac)
LOAD TRANSIENT RESPONSE
(± 25% LOAD CHANGE)
RECOVERY TO WITHIN TWO PERCENT
OF OUTPUT WITHIN 5ms.
ESD SUSCEPTIBILITY IEC1000-4-2 LEVEL 4
(8kV DIRECT DISCHARGE) STANDARDS
IV. OPERATING MODES
DESCRIPTION OPERATIONAL DEFINITION
PARALLEL OPERATION
(ACTIVE CURRENT SHARE
CONFIGURATION)
REFER TO JFS SERIES APPLICATION NOTES
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 2 IMJFS07 – REV D
FEATURES:
I. DC OUTPUT, CONTROLS AND INDICATORS
DESCRIPTION OPERATIONAL DEFINITION
OUTPUT VOLTAGE ADJUST FACTORY SET AT 24VDC OR 48VDC. CONSULT FACTORY FOR
ADJUSTMENT. IT IS RECOMMENDED THAT THE VOLTAGE ADJUST
POTENTIOMETER BE SEALED WITH RTV SEALANT AFTER ADJUSTMENT TO
PREVENT OUTPUT VOLTAGE DRIFT IN THE EVENT THAT THE UNIT IS
SUBJECTED TO VIBRATION.
OVERVOLTAGE PROTECTION
ADJUST
FACTORY SET AT 30VDC OR 60VDC. CONSULT FACTORY FOR ADJUSTMENT
(NON LATCHING).
OUTPUT- GOOD INDICATOR GREEN-COLORED LED ILLUMINATES WHEN THE OUTPUT VOLTAGE IS
WITHIN THE SPECIFIED OPERATING RANGE.
II. REMOTE CONTROL FEATURES
DESCRIPTION OPERATIONAL DEFINITION
REMOTE VOLTAGE SENSING PROVIDES PRECISE REGULATION DIRECTLY AT LOAD. THE MAXIMUM
TOTAL DC VOLTAGE DROP BETWEEN THE OUTPUT TERMINALS AND THE
LOAD MUST BE LIMITED TO LESS THAN 1.0 VOLT.
REMOTE ON-OFF CONTROL DC OUTPUT IS INHIBITED VIA A CONTACT CLOSURE BETWEEN PINS 7 AND
8 OF THE TERMINAL STRIP.
SIGNAL ISOLATION REMOTE ON-OFF PINS ARE REFERENCED TO THE -V
OUT
TERMINAL.
REMOTE VOLTAGE CONTROL ALLOWS ADJUSTMENT OF OUTPUT VOLTAGE USING EXTERNAL
PROGRAMMING RESISTOR OR VOLTAGE SOURCE. REFER TO JFS SERIES
APPLICATION NOTES; SEE FIGURES 3 AND 4 FOR CONNECTION
DIAGRAMS.
III. AUXILIARY MONITORING AND ALARM SIGNALS — OPTICALLY COUPLED, CONDUCTANCE OUTPUTS.
(CONDUCT UP TO 5mA AT A VOLTAGE OF LESS THAN 1.0VDC WHEN ACTIVE.)
DESCRIPTION OPERATIONAL DEFINITION
AC FAIL SIGNAL CONDUCTANCE SIGNAL WHICH INDICATES SUFFICIENT AC INPUT IS
PRESENT TO PROVIDE A MINIMUM OF FIVE MILLISECONDS OF HOLD-UP
TIME AFTER THE REMOVAL OF INPUT.
OUTPUT GOOD SIGNAL CONDUCTANCE SIGNAL WHICH INDICATES THAT DELIVERED OUTPUT
VOLTAGE, AS MEASURED AT THE +V AND -V TERMINALS IS WITHIN THE
SPECIFIED OPERATING RANGE.
SIGNAL ISOLATION SIGNALS ARE ISOLATED FROM POWER SUPPLY OUTPUT AND EACH OTHER
FOR VOLTAGES UP TO 500VDC MAXIMUM AND 3000VAC ISOLATION FROM
AC INPUT TO AUXILIARY SIGNALS.
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 3 IMJFS07 – REV D
FEATURES (CONT’D)
IV. PROTECTION FEATURES
DESCRIPTION OPERATIONAL DEFINITION
OVERCURRENT
PROTECTION
OUTPUT CURRENT IS LIMITED TO APPROXIMATELY 110 PERCENT OF 50ºC
RATED POWER FROM V
OUTMAX
TO V
OUTNOM
. CURRENT LIMIT
CHARACTERISTICS WILL PROVIDE FOLDBACK TO APPROXIMATELY 80
PERCENT OF RATED CURRENT BELOW V
OUTNOM
.
OVERVOLTAGE PROTECTION INVERTER SHUTDOWN, NON-LATCHING. CONSULT FACTORY FOR
ADJUSTMENT.
THERMAL PROTECTION
(OVERTEMPERATURE
PROTECTION)
SELF-RESETTING INVERTER SHUTDOWN.
ISOLATION VOLTAGES 3000VAC, INPUT TO OUTPUT
500VDC, OUTPUT TO CHASSIS GROUND
1500VAC, INPUT TO CHASSIS GROUND
LEAKAGE CURRENT (AC LINE
TO CHASSIS GROUND)
LESS THAN 3.5mA WHEN OPERATED AT 250VAC (47-63Hz) OR LOWER
VOLTAGES.
REGULATORY AGENCY
COMPLIANCE
JFS SERIES POWER MODULES ARE COMPLIANT WITH THE FOLLOWING
STANDARDS:
UL1950
CSA 22.2-234
EN60950
CE MARKED FOR EUROPEAN COMMUNITY COMPLIANCE
IEC950
V. MECHANICAL FEATURES
SPECIFICATION UNITS JFS0750-24 JFS0750-48
STORAGE TEMPERATURE
(NON-OPERATING)
°C -40 TO +85
OPERATING TEMPERATURE °C -20 TO +70 WITH DERATING ABOVE +50
(-20 OPERATION REQUIRES A THIRTY
MINUTE WARM-UP PERIOD)
WEIGHT (NET) LBS 7.5
WEIGHT (SHIP) LBS 8.5
SIZE (L x W x H) INCHES 12.81 x 5.00 x 3.30 (INCLUDES MOUNTING FLANGE)
FINISH GRAY
MOUNTING SEE OUTLINE DRAWING FOR MOUNTING
VI. OTHER FEATURES
DESCRIPTION DEFINITION
COOLING FORCED AIR, FAN COOLED FROM THE FRONT OF THE POWER SUPPLY
EXITING AT THE CONNECTOR END.
FUNGUS INERT ALL JFS POWER SUPPLIES ARE INHERENTLY FUNGUS INERT.
GUARANTEE FIVE YEARS FROM THE TIME OF DELIVERY, PARTS AND LABOR.
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 4 IMJFS07 – REV D
VII. CONNECTOR INFORMATION
SENSING AND
SIGNAL
DESIGNATION DESCRIPTION
1 +S +SENSE CONNECTION. CONNECT TO +V TERMINAL OF LOAD FOR
REMOTE-SENSING. CONNECT TO +LS FOR LOCAL SENSING.
2 +LS +LOCAL SENSE CONNECTION
3 -LS -LOCAL SENSE CONNECTION
4 -S -SENSE CONNECTION. CONNECT TO -V TERMINAL OF LOAD FOR
REMOTE-SENSING. CONNECT TO -LS FOR LOCAL SENSING.
5 PROG JUMPER TO PIN 4 (-S) FOR INTERNAL PROGRAMMING. ALLOWS FOR
REMOTE, EXTERNAL PROGRAMMING VIA INSERTION OF RESISTOR
BETWEEN THE PROGRAMMING PIN AND PIN 4 (-S).
6 ISHARE CURRENT SHARE BUSS
7 INTLK 1 FUNCTIONS TO ENABLE AND DISABLE THE INVERTER OF THE POWER
SUPPLY. A DIRECT SHORT TO INTERLOCK 2 (PIN 8) THROUGH A
CONTACT CLOSURE WILL INHIBIT THE UNIT. AN OPEN CIRCUIT TO
INTERLOCK 2 WILL ENABLE POWER SUPPLY.
8 INTLK 2 (SEE DESCRIPTION, PIN 7)
9 AC FAIL 1 2 TRANSISTOR “DARLINGTON” OUTPUT SIGNAL INDICATING THAT A
FAULT CONDITION HAS OCCURRED ON THE AC LINE. THIS PIN
REPRESENTS THE COLLECTOR CAPABLE OF SINKING UP TO 5mA WITH
20 VOLTS MAXIMUM APPLIED FROM COLLECTOR TO EMITTER.
10 AC FAIL 2 REPRESENTS THE EMITTER OF THE 2 TRANSISTOR “DARLINGTON”
OUTPUT CAPABLE OF SINKING UP TO 5mA WITH 20 VOLTS MAXIMUM
APPLIED FROM COLLECTOR TO EMITTER.
11 DC GOOD 1 2 TRANSISTOR “DARLINGTON” OUTPUT SIGNAL INDICATING THE
OUTPUT IS PRESENT. THIS PIN REPRESENTS THE COLLECTOR
CAPABLE OF SINKING UP TO 5mA WITH 20 VOLTS MAXIMUM APPLIED
FROM COLLECTOR TO EMITTER.
12 DC GOOD 2 REPRESENTS THE EMITTER OF THE 2 TRANSISTOR “DARLINGTON”
OUTPUT CAPABLE OF SINKING UP TO 5mA WITH 20 VOLTS MAXIMUM
APPLIED FROM COLLECTOR TO EMITTER.
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 5 IMJFS07 – REV D
Lambda JFS Series Safety and Installation Instructions for Lambda Model JFS0750
To comply with published safety standards; the following instructions must be used in conjunction with the
Lambda JFS Series:
For earth fault protection, the unit must be protected in the final installation by suitable overcurrent
protection means. If protection relies upon building wiring, the end product installation must ensure that
the necessary protection is provided.
The internal fuse F101 may only be replaced with a Littelfuse type 324015 rated at 15A, 250VAC.
The internal fuse F102 may only be replaced with Littelfuse type 324020 rated at 20A, 250VAC.
The power supply is intended for use as a component of other equipment. When installing the power
supply, the relevant safety standards (EN60950, IEC950, UL1950 or CSA-22.2-950) must be complied
with.
In particular, creepage and clearance distances and distances through insulation between primary and
earth or primary and secondary must be maintained.
The power supply output is SELV in accordance with requirements IEC-950. The output available has
power greater than 240VA.
The CE mark on the product is applied to show conformance with the requirements outlined in the
European Union’s Low Voltage Directive [72/23/EEC] as amended by the CE Mark Directive [93/68/EEC].
The maximum ambient temperature of the operating environment must not exceed 50°C at 750W, 60°C
at 562W or 70°C at 375W.
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 6 IMJFS07 – REV D
Sicherheits und Installationsanleitung für Lambda Modell JFS0750
Die folgende Sicherheitshinweise müssen bei der Verwendung der Netzteile beachtet werden:
Gegen Isolationsfehler zum Schutzleiter muß in der Endanwendung eine angemessene Absicherung
vorgenommen werden. Falls die Absicherung durch die Gebäudeinstallation erfolgt, muß beim Einbau in
das Endgerät entsprechend darauf hingewiesen werden.
Die interne Sicherung F101 darf nur gegen den gleichen Typ mit gleichen Werten ausgetauscht werden.
Es ist die Sicherung Littelfuse Typ 324015 mit 15A und 250VAC zu verwenden.
Die interne Sicherung F102 darf nur gegen den gleichen Typ mit gleichen Werten ausgetauscht werden.
Es ist die Sicherung Littelfuse Typ 324020 mit 20A und 250VAC zu verwenden.
Das Netzteil ist nur als Baugruppe zum Einbau in Endgeräte vorgesehen und nicht zur eigenständigen
Verwendung. Beim Einbau in Endgeräte sind die entsprechenden Sicherheitsbestimmungen (z. B. EN
60950, IEC-950, UL-1950, CSA 22.2-950) zu beachten.
Im Speziellen ist auf das Einhalten ausreichender Kriech- und Luftstrecken sowie Isolationsabstaenden
zwischen dem Primaer- und Sekundaerkreis sowie zum Schutzleiter zu achten.
Das Netzteil liefert eine SELV-Spannung in Uebereinstimmung mit IEC-950. Die verfuegbare
Ausgangsleistung ist groeßer als 240VA.
Das CE-Konformitaetszeichen auf dem Produkt zeigt die Uebereinstimmung mit den Anforderungen der
EG-Niederspannungs-Richtlinie [72/23/EWG] und der Ergaenzung [93/68/EWG].
Die maximale Arbeitsumgebungstemperatur darf 50°C bei 750W, 60°C bei 562W und 70°C bei 375W
nicht ueberschreiten.
Die Sicherung muß im L-Leiter (Phase) eingefuegt werden.
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 7 IMJFS07 – REV D
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 8 IMJFS07 – REV D
FIGURE 1: TYPICAL LOCAL SENSE CONNECTION
FIGURE 2: TYPICAL REMOTE SENSE CONNECTION
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 9 IMJFS07 – REV D
FIGURE 3: REMOTE VOLTAGE CONTROL WITH AN EXTERNAL PROGRAMMING
RESISTOR OR VOLTAGE SOURCE (LOCAL SENSING)
FIGURE 4: REMOTE VOLTAGE CONTROL WITH AN EXTERNAL PROGRAMMING
RESISTOR OR VOLTAGE SOURCE (REMOTE SENSING)
JFS S
ERIES
I
NSTRUCTION
M
ANUAL
LAMBDA ELECTRONICS INCOPORATED
3055 DEL SOL BOULEVARD , SAN DIEGO , CA 92154-3474 • TEL: 619-575-4400 • FAX: 619-575-7185
P. 10 IMJFS07 – REV D
FIGURE 5: PARALLEL OPERATION