* to be noted : 2 x 18 V and 2 x 24 non safety transformer approved,
conform to EN 61558-2-6 (Isolating transformer).
PRIMARY VOLTAGE
Protection Reference
Secondary
voltage
V
Secondary
Current
m A
No-load
voltage
V
Ambient
Temperature
°C
Rating
VA
44085 6 250 9,7 T 70 B 1,5
44086 9 167 14,5 T 70 B 1,5
44087 12 125 19,3 T 70 B 1,5
44088 15 100 24,2 T 70 B 1,5
44089 18 83 29,8 T 70 B 1,5
44090 24 63 38,6 T 70 B 1,5
44091 2 x 6 2 x 125 2 x 9,7 T 70 B 1,5
44092 2 x 9 2 x 83 2 x 15 T 70 B 1,5
44093 2 x 12 2 x 63 2 x 19,3 T 70 B 1,5
44094 2 x 15 2 x 50 2 x 24,2 T 70 B 1,5
44095* 2 x 18 2 x 42 2 x 29 T 70 B 1,5
44096* 2 x 24 2 x 31 2 x 38,6 T 70 B 1,5
lVacuum filling
lTwo compartments bobbins
lSelf-extinguishing plastics UL 94
VO
lDegree of protection IP 00
l80 grams weight
lResin class B CEI 85 (20 000 h
testing to CEI 126)
lInherently short-circuits proof
transformer
l30 V model is VDE EN 61558-2-6
certified (production on request)
lInsulation voltage 4 KV (6 KV
MYRRA test)
l100% tested production
lCertification : CCA procedure on
request