PM4H-F DIN48 SIZE ANALOG MULTIRANGE POWER OFF-DELAY TIMERS PM4H-F UL File No.: E122222 CSA File No.: LR39291 Features 1. Switch operation times between three types of time ranges of 1 s to 10 s and 1 min to 10 min. 2. Instantaneous reset available. 3. The shorter body makes it easier to use. 4. Compliant with UL, CSA, CE and LLOYD. 48 1.890 48 1.890 62.5 2.461 mm inch RoHS Directive compatibility information http://www.nais-e.com/ Specifications Type Item Rated operating voltage Rated frequency Rating Time accuracy *1 Contact Life Rated power consumption Rated control capacity Operation mode Time range Operation time fluctuation Setting error Voltage error Temperature error Contact arrangement Contact resistance (Initial value) Contact material Mechanical (contact) Electrical (contact) Allowable operating voltage range Insulation resistance (Initial value) Electrical function Breakdown voltage (Initial value) Min. power supply width Min. reset time Max. temperature rise Vibration resistance Mechanical function Operating condition Others Shock resistance Functional Destructive Functional Destructive Ambient temperature Ambient humidity Atmospheric pressure Ripple factor (DC type) Protective construction Weight PM4H-F8R PM4H-F11R 100 to 120V AC, 200 to 240V AC, 24V AC, 12V DC, 24V DC 50/60Hz common (AC operating type) Approx. 1.6VA (100 to 120V AC, 200 to 240V AC), Approx. 2.3VA (24V AC) Approx. 1.1W (12V DC, 24V DC) 3A 250V AC (resistive load) Power OFF-delay Power OFF-delay (with reset) 1s to 10s: 3 range switchable 1 min to 10 min: 3 range selectable 0.3% 5% (Full-scale value) 0.5% (at the operating voltage changes between 85 to 110%) 2% (at 20C ambient temp. at the range of -10 to +50C +14 to +122F) Timed-out 2 Form C Timed-out 1 Form C Timed-out 2 Form C Max. 100m (at 1A 6V DC) Au flash on Silver alloy 107 5 10 (at rated control capacity) 85 to 110% of rated operating voltage (at 20C coil temp.), 90 to 110% (DC Type) Between live and dead metal parts Between input and output Min. 100M (At 500V DC) Between contacts of different poles (*3) Between contacts of same pole 1,500Vrms for 1 min Between live and dead metal parts 1,500Vrms for 1 min Between input and output 1,000Vrms for 1 min Between contacts of different poles (*3) 750Vrms for 1 min Between contacts of same pole s range type: 100ms min range type: 2s 50ms 55C 131F 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes) 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1hr on 3 axes) Min. 98m/s2 (4 times on 3 axes) Min. 980m/s2 (5 times on 3 axes) -10 to +50C +14 to +122F 30 to 85%RH (non-condensing) 860 to 1,060hPa 20% IP65 on front panel (using rubber gasket ATC18002) 100g 3.527 oz (Pin type), 110g 3.880 oz (Screw terminal type) PM4H-F8 *Notes: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20C 68F ambient temperature. 2) For the 1s range, the tolerance for each specification becomes 10ms. When the power goes on, in rush current (0.3A) flows. Cautions should be taken. The minimum power supplying time after forced reset input is 2s or more. 3) Between contacts of different pools for PM4H-F8, PM4H-F11R types only. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-F Time range Time range unit Time range 1 5 10 s range type min range type 0.04s to 1s 0.2s to 5s 0.4s to 10s 0.04 min to 1 min 0.2 min to 5 min 0.4 min to 10 min Product types Type Operation mode Contact arrangement Time range 3 selectable time ranges over 1s to 10s 3 selectable time ranges over 1 min to 10 min PM4H-F8 Power OFF-delay (without reset) Relay Timed-out 2 Form C 3 selectable time ranges over 1s to 10s 3 selectable time ranges over 1 min to 10 min 3 selectable time ranges over 1s to 10s PM4H-F8R Power OFF-delay (with instantaneous reset) 3 selectable time ranges over 1 min to 10 min Relay Timed-out 1 Form C 3 selectable time ranges over 1s to 10s 3 selectable time ranges over 1 min to 10 min Protective Rated operating construction voltage 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP65 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP50 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP65 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP50 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC Terminal type 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. Part number PM4HF8-S-AC120VW PM4HF8-S-AC240VW PM4HF8-S-AC24VW PM4HF8-S-DC12VW PM4HF8-S-DC24VW PM4HF8-M-AC120VW PM4HF8-M-AC240VW PM4HF8-M-AC24VW PM4HF8-M-DC12VW PM4HF8-M-DC24VW PM4HF8-S-AC120V PM4HF8-S-AC240V PM4HF8-S-AC24V PM4HF8-S-DC12V PM4HF8-S-DC24V PM4HF8-M-AC120V PM4HF8-M-AC240V PM4HF8-M-AC24V PM4HF8-M-DC12V PM4HF8-M-DC24V PM4HF8R-S-AC120VW PM4HF8R-S-AC240VW PM4HF8R-S-AC24VW PM4HF8R-S-DC12VW PM4HF8R-S-DC24VW PM4HF8R-M-AC120VW PM4HF8R-M-AC240VW PM4HF8R-M-AC24VW PM4HF8R-M-DC12VW PM4HF8R-M-DC24VW PM4HF8R-S-AC120V PM4HF8R-S-AC240V PM4HF8R-S-AC24V PM4HF8R-S-DC12V PM4HF8R-S-DC24V PM4HF8R-M-AC120V PM4HF8R-M-AC240V PM4HF8R-M-AC24V PM4HF8R-M-DC12V PM4HF8R-M-DC24V PM4H-F Type Operation mode Contact arrangement Protective Rated operating construction voltage Time range 100 to 120V AC 200 to 240V AC 24V AC IP65 12V DC 24V DC 3 selectable time ranges over 1s to 10s 100 to 120V AC 200 to 240V AC 24V AC IP50 12V DC PM4H-F11R Power OFF-delay (with instantaneous reset) 24V DC Relay Timed-out 2 Form C 100 to 120V AC 200 to 240V AC 24V AC IP65 12V DC 24V DC 3 selectable time ranges over 1 min to 10 min 100 to 120V AC 200 to 240V AC 24V AC IP50 12V DC 24V DC Terminal type 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 6.0 .236 * Pin type (Flush mount/surface mount) 62.5 2.461 48 1.890 44.5 1.752 48 1.890 12.0 .472 6.0 .236 66.5 2.618 41 dia. 1.614 dia. 48 1.890 12.0 .472 41 dia. 1.614 dia. 48 1.890 All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4HF11R-S-AC120VW PM4HF11R-S-AC120VSW PM4HF11R-S-AC240VW PM4HF11R-S-AC240VSW PM4HF11R-S-AC24VW PM4HF11R-S-AC24VSW PM4HF11R-S-DC12VW PM4HF11R-S-DC12VSW PM4HF11R-S-DC24VW PM4HF11R-S-DC24VSW PM4HF11R-S-AC120V PM4HF11R-S-AC120VS PM4HF11R-S-AC240V PM4HF11R-S-AC240VS PM4HF11R-S-AC24V PM4HF11R-S-AC24VS PM4HF11R-S-DC12V PM4HF11R-S-DC12VS PM4HF11R-S-DC24V PM4HF11R-S-DC24VS PM4HF11R-M-AC120VW PM4HF11R-M-AC120VSW PM4HF11R-M-AC240VW PM4HF11R-M-AC240VSW PM4HF11R-M-AC24VW PM4HF11R-M-AC24VSW PM4HF11R-M-DC12VW PM4HF11R-M-DC12VSW PM4HF11R-M-DC24VW PM4HF11R-M-DC24VSW PM4HF11R-M-AC120V PM4HF11R-M-AC120VS PM4HF11R-M-AC240V PM4HF11R-M-AC240VS PM4HF11R-M-AC24V PM4HF11R-M-AC24VS PM4HF11R-M-DC12V PM4HF11R-M-DC12VS PM4HF11R-M-DC24V PM4HF11R-M-DC24VS mm inch Toletance: 0.5 .020 Dimensions * Screw terminal type (Flush mount) Part number 14.5 .571 44.5 1.752 PM4H-F Terminal layouts and Wiring diagrams * PM4H-F8 (without reset input) Pin type Time-out 2 Form C N.C. N.C. N.O. 4 5 3 2 (-) * PM4H-F8R (with reset input) Pin type Time-out 1 Form C, with reset input N.C. N.O. 4 5 6 7 3 2 Reset input 1 8 Operating voltage * PM4H-F11R (with reset input) Pin type Time-out 2 Form C, with reset input (+) (-) Screw-tightening pin type The PM4H-F11R should be used for the timelimit 2C. Reset input N.O. N.C. N.C. 6 7 5 6 7 N.O. 4 3 2 1 8 Operating voltage 1 11 N.O. 8 9 10 Operating voltage (+) (-) Screw-tightening pin type The PM4H-F11R should be used for the timelimit 1C and to connect reset input. (+) Screw terminal type Time-out 2 Form C, with reset input N.C. N.O. 6 7 8 9 10 N.C. N.O. 11 1 (+) 2 3 Operating voltage 4 5 Reset input (-) PM4H-F (with reset) input conditions 1. Contact input (pin type example) PM4H-F8R 2. Non-contact input (pin type example) PM4H-F11R PM4H-F11R Reset input Reset input PM4H-F8R Use a contact with good contact reliability for the input. Contact bounce can lead to erroneous operation of the timer, so use a contact with short bounce time. Make the resistance between terminals for a short circuit less than 1k-ohms. Make the resistance between terminals for an open circuit greater than 100k-ohms. Photo-coupler Reset input Reset input Check that Vce = 0.6V Max. when ON. Photo-coupler Operation * PM4H-F8 (without reset input) * PM4H-F8R/F11R (with reset input) Note: Tr Tr Note: Ts Tr Ts Power supply Power supply T Time-delay contact N.O. Reset input Time-delay contact N.C. Time-delay contact N.O. T Be sure to use a photocoupler for non-contact input. t Time-delay contact N.C. t