DC/DC CONVERTERS 30W Wide Input DC/DC Converters 1
2 YEAR WARRANTY
BXA30 Series
Triple output
•Pin-compatible with BXA15 series
•Designed to meet telecom power supply interface
standard ETS300-132-2
•UL, CSA and VDE approvals
•VDE0878 and EN55022 conducted emissions level A
•EN61000-4-2, -3, -4, -5, -6 immunity compliant
•Fixed frequency operation at 350kHz
•MTBF in excess of 7,005,000 hours (demonstrated)
•Basic insulation system
The BXA30 triple output Series, comprising 2 different models, has been conceived as an
applications-specific range of DC/DC converters, specifically addressing telecommunications,
industrial electronics, test equipment, mobile telecommunications and distributed power
applications. The series offers two wide input voltage ranges, 18-36VDC and 36-75VDC.
Designed to meet ETSI telecoms interface standards ETS300-132-2 and BTR2511, together
with internal filtering to EN55022 level A, safety approval to EN60950 and UL1950, and basic
insulation of 1500VDC, the 48VDC model is ideal for telecommunications applications.
The 24V model is particularly suited to industrial, mobile telecom and test equipment
applications, featuring EN61000-4-2, -3, -4, -5 and -6 immunity compliant. Other features
include low output ripple, overvoltage protection, short circuit protection, remote enable.
All specifications are typical at nominal input, full load at 25°C unless otherwise stated
EMC CHARACTERISTICS
Conducted emissions EN55022, FCC part 15 (Note 3) Level A
EN55022, FCC part 15 (Note 4) Level B
VDE0878 (Note 3) (48V) Level A
Radiated emissions EN55022, FCC part 15 Level A
ESD air EN61000-4-2, level 3 Perf. criteria 2
ESD contact EN61000-4-2, level 4 Perf. criteria 2
Surge EN61000-4-5, level 3 Perf. criteria 2
Fast transients EN61000-4-4, level 3 Perf. criteria 2
Radiated immunity EN61000-4-3, level 3 Perf. criteria 2
Conducted immunity EN61000-4-6, level 3 Perf. criteria 2
GENERAL SPECIFICATIONS
Efficiency See table
Isolation voltage Input/output 1500VDC
Basic insulation Input/case, 48V models 1500VDC
Switching frequency Fixed 350kHz, nom.
Approvals and VDE0805, EN60950
standards EN41003, IEC950, UL1950
(See Note 11) CSA C22.2 No. 950
Case material Aluminum substrate
with plastic case
Material flammability UL94V-0
Weight 130g (4.6oz)
MTBF (See Note 9)
Demonstrated @ 25°C
7,005,000 hours
ENVIRONMENTAL SPECIFICATIONS
Thermal performance Baseplate operating -25°C to +100°C
temperature,
(See Notes 5, 7)
Non-operating -55°C to +100°C
Thermal impedance Free air convection, 6.5°C/W
baseplate to air
With heatsink (See Note 7) 5.2°C/W
OUTPUT SPECIFICATIONS
Output power 30W
Line regulation Main output ±0.5%
(See Note 1) Auxiliary output ±2.0%
Load regulation Main output ±1.0%
(See Note 2) Auxiliary output ±3.0%
Ripple and noise Main output 75mV pk-pk
(20MHz bandwidth) 15mV rms
Auxiliary outputs 100mV pk-pk
20mV rms
Temperature coefficient ±0.02%/°C
Overvoltage protection Transient, all outputs 135% Vout init.
Short circuit protection All outputs Yes
(See BXA15/30 Design Note 101)
Transient response 25% to 100% load, all outputs 10%
Voltage accuracy Main output ±1.5%
Auxiliary output ±3.0%
Load cross regulation 20% to 100% load
Main: output 1.0%
Auxiliary: output 10%
50% to 100% load, main, >20% aux.
Main output 1.0%
Auxiliary output 4.0%
Minimum load Main output for auxiliary >10%
(See Note 10) regulation
INPUT SPECIFICATIONS
Input voltage range 24Vin nominal 18 to 36VDC
48Vin nominal 36 to 75VDC
Reverse voltage prot. (See Note 6) Yes
Max. input rise and 48V 5V/ms
fall time ETS300-132
Remote ON/OFF
Logic compatibility CMOS/TTL
ON Open circuit
OFF <1VDC
SPECIFICATIONS
File Name: BXA30T.PDF Rev: 02 Oct 2002