Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
6 |B-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Agency
Approval
4
Circuit
B A B 1 13 0 B C10 450
1 SERIES
B
2 ACTUATOR
A Handle, one per pole
B Handle, one per multipole unit
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
10 MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 x 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm yes
Rectangular Adapter Plate with mounting centers of 2.062
inches [52.37mm] and Threaded insert, 2 per pole
3 14 6-32 x 0.225 inches no
C 14 6-32 X 0.225 inches (multi-pole units only) yes
4 14 ISO M3 x 6.5mm no
D 14 ISO M3 x 6.5mm yes
Front panel Snap-In, 0.75” [19.05mm] wide bezel
5 without Handleguard no
6 without Handleguard (multipole only) yes
Front panel Snap-In, 0.96” wide bezel
7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides
8 without Handleguard, 1-pole 0.96” wide; yes
(multipole only) .105” bezel overhang on all sides
3 POLES
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
9 ACTUATOR COLOR & LEGEND
Actuator Color I-O ON-OFF Dual Legend Color
White A B 1 Black
Black C D 2 White
Red F G 3 White
Green H J 4 White
Blue K L 5 White
Yellow M N 6 Black
Gray P Q 7 Black
Orange R S 8 Black
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units.
B: Handle location as viewed from front of breaker:
2 pole - left pole 3 pole - center pole
4 pole - two handles at center poles 5 pole - three handles at center poles
6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit
codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE
Certication when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps,
select Current Code 630. For 35 - 50 amps, select Current Code 650.
3 Available with Terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required. With
Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require
30VA minimum power to trip and are rated for intermittent duty only.
5 Auxiliary Switch breakers with Series Trip and Switch Only circuits. On multi-pole breakers,
one auxiliary switch is supplied, mounted in the extreme right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with delay
codes 10 and 20.
7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized and
CSA Accepted to 50 amps.
8 VDE Certication available with single pole breakers with DC Delay only. UL Recognition
and CSA Accepted available in one and two pole breakers.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps
are only available with Terminal Codes 5, 9, G, H, J, K, M and Q.
10 VDE Certication up to 25 amps and UL Recognition and CSA Acceptance up to 30 amps,
but not recommended over 20 amps.
11 Terminal Codes 3, 5 E and H (Bus Type) with VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only VDE Certied when the washers are used.
12 VDE Cert. available up to 12 amps. UL Rec. & CSA Acceptance available up to 30 amps.
13 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30
amps with VDE Certication and 50 amps with UL Recognition and CSA Acceptance, with
Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board)
are available up to 40 amps with UL Recognition and CSA Acceptance with Circuit Codes
A, B and C.
14 Available with Actuator Codes A, S and T.
15 Available with voltage coils only.
16 Terminal Code Q not available with VDE approvals.
4 CIRCUIT
A 2 Switch Only (No Coil)
B Series Trip (Current)
C Series Trip (Voltage)
D 3 Shunt Trip (Current)
E 3 Shunt Trip (Voltage)
F 3 Relay Trip (Current)
G 3 Relay Trip (Voltage)
H 3,4 Dual Coil with Shunt Trip
Voltage Coil
K 3,4 Dual Coil with Relay Trip
Voltage Coil
11 AGENCY APPROVAL
C UL Recognized & CSA Accepted
D VDE Certied, UL Recognized & CSA Accepted
E TUV Certied, UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
8 TERMINAL 9 F Screw M5 with upturned lugs
1 10 Push-On 0.250 Tab (Q.C.) & 30° bend
2 Screw 8-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
3 11 Screw 8-32 (Bus Type) H Screw M5 (Bus Type)
4 Screw 10-32 with upturned lugs J Screw M5 Back Connect
5 11 Screw 10-32 (Bus Type) K Screw 10-32 Back Connect
6 Screw 8-32 with upturned lugs L 12 0.250 Q.C./ Solder Lug
& 30° bend M 11 M6 Threaded Stud
7 Screw 8-32 (Bus Type) N Screw M4 Back Connect
& 30° bend P 13 Printed Circuit Board Terminals
8 Screw 10-32 with upturned lugs Q 16 Push-In Stud
& 30° bend R Screw M4 with upturned lugs
9 Screw 10-32 (Bus Type) & 30° bend
& 30° bend S 15 Push-On 0.110 Tab (Q.C.)
B Screw M5 with upturned lugs & 30° bend
C Screw M4 with upturned lugs T Screw M4 (Bus Type) & 30° bend
E 11 Screw M4 (Bus Type) Y Screw 8-32 Back Connect
5 AUXILIARY / ALARM SWITCH 5 5 S.P.S.T., 0.093 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 7 S.P.S.T., 0.110 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts)
4 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
(Gold Contacts) 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
03 2 DC 50/60Hz, Switch Only
10 6 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 6 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
42 7 50/60Hz Short, Hi-Inrush
44 7 50/60Hz Medium, Hi-Inrush
46 7 50/60Hz Long, Hi-Inrush
52 7 DC, Short,Hi-Inrush
54 7 DC, Medium, Hi-Inrush
56 7 DC, Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE AMPERES
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 6
CODE AMPERES
A06 6 DC A32 32 DC J12 12 AC J65 65 AC
A12 12 DC A48 48 DC J18 18 AC K20 120 AC
A18 18 DC A65 65 DC J24 24 AC L40 240 AC
A24 24 DC J06 6 AC J48 48 AC
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 8 35.000
640 8 40.000
645 8 45.000
650 8 50.000