C77 TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-PROX Fax: (763) 553-0708 www.turck.com
TURCK
Inductive Sensors - Barrels
3-Wire DC
10-30 VDC, Short-Circuit and Overload Protected
Normally Open*, NPN (Sinking) or PNP (Sourcing)
Barrel, Metal with Potted-In Cable - Standard, Stainless Steel
Full Threading
G and EG Barrel
Accessories and mounting devices can be found in Section J.
Accessories
Cable: PVC Jacket; 2 and 7 meter standard length
Copper Conductor: G12: 24 AWG
(PVC insulated) G18/G30: 21AWG
Cable/Conductor
GBarrel/Locknuts: Chrome Plated Brass
EG Barrel/Locknuts: Stainless Steel
Sensing Face: PA 12-GF30 Plastic
End Cap: PUR Plastic
Material
Part Number
Embeddable
Rated Operating
Distance (mm)
Barrel
Diameter (mm)
Sinking
Sourcing
Drawing #
Wiring Diagram
# of LEDs
FM Approved
Division 2
Switching
Frequency (Hz)
ID Number
Bi 2-G12-AN6X
Bi 5-G18-AN6X
Bi10-G30-AN6X
Ni 5-G12-AN6X
Ni10-G18-AN6X
Ni15-G30-AN6X
·
·
·
2
5
10
5
10
15
12
18
30
12
18
30
·
·
·
·
·
·
1
3
5
2
4
6
A
A
A
A
A
A
1
1
1
1
1
1
·
·
·
·
·
·
2000
1000
500
1500
1000
500
T4635500
T4641500
T4647500
T4635700
T4641700
T4647700
Bi 2-G12-AP6X
Bi 5-G18-AP6X
Bi10-G30-AP6X
Ni 5-G12-AP6X
Ni10-G18-AP6X
Ni15-G30-AP6X
·
·
·
2
5
10
5
10
15
12
18
30
12
18
30
·
·
·
·
·
·
1
3
5
2
4
6
B
B
B
B
B
B
1
1
1
1
1
1
·
·
·
·
·
·
2000
1000
500
1500
1000
500
T4635400
T4641400
T4647400
T4635600
T4641600
T4647600
Bi 2-EG12-AN6X
Bi 5-EG18-AN6X
·
·
2
5
12
18
·
·
1
3
A
A
1
1
·
·
2000
1000
T4605101
T4611101
Bi 2-EG12-AP6X
Bi 5-EG18-AP6X
·
·
2
5
12
18
·
·
1
3
B
B
1
1
·
·
2000
1000
T4605001
T4611001
Sensor Selection
* Normally Closed versions available upon request, consult factory.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-PROX Fax: (763) 553-0708 www.turck.comC78
Barrels
Ripple . . . . . . . . . . . . . . . . . . . . £10%
Differential Travel (Hysteresis) . . . . . . . . 3-15% (5% typical)
Voltage Drop Across Conducting Sensor . . . £1.8 V at 200 mA
Trigger Current for Overload Protection . . . ³220 mA
Continuous Load Current . . . . . . . . . . £200 mA
Off-State (Leakage) Current . . . . . . . . . <10 mA
No-Load Current . . . . . . . . . . . . . . 5.5-9.5 mA
Time Delay Before Availability . . . . . . . . £8 ms
Power-On Effect . . . . . . . . . . . . . . . Per IEC 947-5-2
Reverse Polarity Protection . . . . . . . . . Incorporated
Wire-Break Protection . . . . . . . . . . . . Incorporated
Transient Protection . . . . . . . . . . . . . Per EN 60947-5-2
Operating Temperature . . . . . . . . . . . -25°C to +70°C (-13°F to +158°F)
Enclosure . . . . . . . . . . . . . . . . . . Meets NEMA 1,3,4,6,13 and IEC IP 67
Shock . . . . . . . . . . . . . . . . . . . . 30 g, 11 ms
Vibration . . . . . . . . . . . . . . . . . . 55 Hz, 1 mm Amplitude in all 3 Planes
Repeatability. . . . . . . . . . . . . . . . . £2% of Rated Operating Distance
LED On . . . . . . . . . . . . . . . . . . . Output Energized
Specifications
3 4
5 6
1 2
B PNP (Sourcing)
A NPN (Sinking)
Wiring Diagrams
Dimensions