CE Marked - LVD & EMC
•
Din Rail Mounting
•
Power Factor Corrected Versions
•
Adjustable Outputs
•
Low Noise
•
High Efficiency
•
Parallelable Units
(All specifications are typical at nominal input voltage; full load and 25 °C unless stated otherwise)
Input Voltage • 93-264 V AC - TSL30 & TSL60
93-132 V AC/187-264 auto-ranging TSL120, TSL240 & TSL480
Input Frequency • 47-63 Hz
Inrush Current • See Table
Input Current • See Table
Hold Up Time • Minimum 15 ms at 115 V AC, minimum 25 ms at 230 V AC
Output Voltage • See Table
Output Adjustment • 12 V models: 12-14 V DC, 24 V models: 24-28 V DC & 48 V models: 48-52 V DC
Line Regulation • ±0.2%
Load Regulation • ±0.3% for load variation 10-90%
Ripple & Noise • <50 mV pk-pk 20 MHz bandwidth
Overload Protection • 110%
Overvoltage Protection • 140% of V out typically
Efficiency • 85% minimum
Operating Temperature • -25 °C to 70 °C, derating above 50 °C at 2%/°C
Storage Temperature • -25 °C to 85 °C
Relative Humidity • 95%
Isolation • 3000 V AC - input to output, 1 minute
2000 V AC - input to case, 1 minute
500 V AC - output to case, 1 minute
EMI/RFI • EN55011, EN55022, FCC class B
TSL120, TSL240 & TSL480 (P version) with PFC-EN61000-3-2
Safety Approvals • EN60950, IEC950, cUL/UL 1950, UL508
Immunity • EN61000-4-4 2 kV
MTBF • 200,000 hours
Switching Frequency • 80 kHz typical
Industrial Power Supplies
TSL SERIES 30-480 Watts
Specification
Tel: +44 (0)118 984 5515 Tel: +49 (0)700 9977 1000
UK D