SPECIFICATION
MODEL
HLG-240-12
HLG-240-15
HLG-240-20
HLG-240-24
HLG-240-30
HLG-240-36
HLG-240-48
DCVOLTAGE
RATEDCURRENT
RATEDPOWER
OUTPUT
VOLTAGE ADJ.RANGE Note.6
CURRENT ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME Note.8
HOLDUP TIME (Typ.)
VOLTAGERANGE Note.5
FREQUENCY RANGE
POWERFACTOR (Typ.)
EFFICIENCY (Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT(Typ.)
LEAKAGECURRENT
SAFETY STANDARDS Note.7
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERCURRENT Note.4
OVERVOLTAGE
OVERTEMPERATURE
12V
6~12V
15V
7.5~15V
20V
10~20V
24V
12~24V
30V
15~30V
36V
18~36V
48V
24~48V
16A 15A 12A 10A 8A 6.7A 5A
192W 225W 240W 240W 240W 241.2W 240W
150mVp-p 150mVp-p
14~16V
150mVp-p
18.6~21.4V
150mVp-p
22.4~25.6V
200mVp-p
28~32V
250mVp-p
33.5~38.5V
250mVp-p
44.8~51.2V
2.5%
8~16A
2.0%
7.5~15A
1.0%
6~12A
1.0%
5~10A
1.0%
4~8A
1.0%
3.3~6.7A
1.0%
2.5~5A
11.2~12.8V
Canbeadjusted byinternalpotentiometerorthroughoutputcable
0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5%
2.0% 1.5% 1.0% 0.5% 0.5% 0.5% 0.5%
2500ms,80ms atfullload230VAC/115VAC
15ms atfullload230VAC/115VAC
90~264VAC127~373VDC
47~63Hz
PF>0.98/115VAC,PF>0.95/230VACatfullload(Pleasereferto"PowerFactorCharacteristic"curve)
90% 90% 92% 93% 93% 93.5% 94%
13.5~18V 17.5~21.5V 23.5~27.5V
95 5 (TSW1)
27~34V 33~39V 43~49V 55~63V
4A /115VAC2A /230VAC
COLDSTART 75A/230VAC
<0.75mA /240VAC
95~108%
Protectiontype:Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
Complianceto EN55015,EN55022(CISPR22)ClassB,EN61000-3-2ClassC( 50%load);EN61000-3-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,EN61547,EN55024,lightindustrylevel(surge4KV),criteria A
-40~+70 (Referto"DeratingCurve")
20~95%RH non-condensing
-40~+80 ,10~95%RH
0.03%/ (0~50 )
10~500Hz,5G12min./1cycle,periodfor72min.eachalongX, Y,Zaxes
207.9Khrsmin.MIL-HDBK-217F(25 )
244.2*68*38.8mm(L*W*H)(HLG-240-Blank/A/B)251*68*38.8mm(L*W*H)(HLG-240-C)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Constant current operation region is within 50% ~100% rated output voltage. This is the suitable operation region for LED related applications, but please
reconfirm special electrical requirements for some specific system design.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Type A and type C only.
7. Safety and EMC design refer to EN60598-1, subject 8750(UL), CNS15233, GB7000.1, FCC part18.
8. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
9. The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the
complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.
10. Refer to warranty statement.
1.3Kg;12pcs/16.6Kg/0.84CUFT(HLG-240-Blank/A/B) 1.23Kg;12pcs/15.8Kg/1.16CUFT(HLG-240-C)
Protectiontype: Shutdownandlatchoffo/pvoltage,re-powerontorecover
240WSingleOutputSwitchingPowerSupply
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Over current / Over voltage / Over temperature
Cooling by free air convection
OCP point adjustable through output cable or internal
IP67 / IP65 design for indoor or outdoor installations
potentiometer
Three in one dimming function (1~10Vdc or PWM signal or resistance)
Suitable for LED lighting and street lighting applications
Compliance to worldwide safety regulations for lighting
5 years warranty (Note.10)
Suitable for dry / damp / wet locations
Features :
HLG-240 series
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
SAFETY &
EMC
PROTECTION
105 5 (TSW1)
Protectiontype:Shutdowno/pvoltage,recoversautomaticallyaftertemperaturegoesdown
F110 SELV
IP65 IP67
SHORTCIRCUIT
Hiccupmode,recoversautomaticallyafterfaultconditionisremoved
Blank : IP67 rated. Cable for I/O connection.
HLG-240-54
54V
27~54V
4.45A
240.3W
350mVp-p
50~57V
1.0%
2.23~4.45A
0.5%
0.5%
HLG-240-42
42V
21~42V
5.72A
240.24W
250mVp-p
39~45V
1.0%
2.86~5.72A
0.5%
0.5%
94% 94%
48~54V 60~67V
UL1012,CAN/CSA-C22.2No.107.1-01,UL8750,CSA C22.2No.250.0-08, TUVEN61347-1,EN61347-2-13independent
(exceptforHLG-240Ctype),UL60950-1,UL8750, TUVEN60950-1,IP65orIP67,J61347-1,J61347-2-13approved
EMCIMMUNITY
EMCEMISSION
B : IP67 rated. Constant current level adjustable through output cable with 1~10Vdc or 10V PWM signal or resistance.
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3.75KVACI/P-FG:1.88KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC/25 /70%RH
CONSTANTCURRENTREGION Note.4
HLG-240-12 A
A : IP65 rated. Output voltage and constant current level can be adjusted through internal potentiometer.
C : Terminal block for I/O connection. Output voltage and constant current level can be adjusted through internal
potentiometer.
D(option) : IP67 rated. Timer dimming function, contact MEAN WELL for details.