FA Wireless SS Terminals WT30 1
FA Wireless SS Terminals
WT30
Construct a Wireless System for ON/OFF
Data Collection That Is Ideal for Monitoring
Production Site Equipment
Wireless Slave Station equipped with I/O.
Height of 90 mm and DIN Rail mounting enables installation in
control panels.
Easily check wireless communications status from indicator
display.
I/O Slave Stations can also be used as Slave Stations in WD30
systems.
Conforms to radio wave standards for Japan, China (pending),
USA, and Europe.
Ordering Information
List of Models
Note: An Antenna and Mounting Brackets are not included with the Wireless SS Terminal.
Accessories
Antennas
Communications Cables
Other
Applicable Standards
FCC part 15.247 (USA)
EN 300 440-2 (Europe)
ARIB STD-T66 (Japan)
(China) (approval pending)
Main Class 2 Power Supplies
OMRON Switching Power Supplies
S8VS (15 W, 30 W, 60 W type)
S82K (15 W, 30 W, 50 W, 90 W type)
Applicable Countries
Wireless standards have been met for the following countries. The
product cannot be used in any other countries.
Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungry, Iceland, Ireland, Italy,
Japan, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland,
UK, USA
Wireless Unit model Type Specifications/No. of I/O points
WT30-M01-FLK Serial master RS-232C
WT30-SID16 I/O slaves 16 DC inputs (NPN/PNP)
WT30-SMD16 8 DC inputs (NPN/PNP) + 8 transistor outputs (NPN)
WT30-SMD16-1 8 DC inputs (NPN/PNP) + 8 transistor outputs (PNP)
Model Type
WT30-AT001 Magnet-base Antenna (2 antennas per set)
WT30-AT002 Flat Diversity Antenna (1 antenna)
WT30-AT003 Pencil Antenna (2 antennas per set)
Model Length Application
XW2Z-0100U-3 1 m For personal computer
XW2Z-0200U-3 2 m
XW2Z-0500U-3 5 m
XW2Z-0200U-5 2 m Cross cable for PLC
XW2Z-0500U-5 5 m
Model Type
WT30-FT001 DIN Rail Mounting Bracket (for TH35-7.5)
WT30-FT002 DIN Rail Mounting Bracket (for TH35-15)
WT30-FT003 Surface Mounting Bracket (screw-mounting)
(2 brackets per set)
WT30-FT011 Flat Diversity Antenna Mounting Brackets
(with magnets)
WT30-CA2M Antenna Extension Cable (1 cable, 2 m)
Conformity to Safety Standards
Always use a Class 2 power supply to conform to UL standards.
Conformity to EN Standards
Use a DC power line less than 3 m to conform to EN standards. If a
power line of 3 m or longer is required, extend the length at the
Switching Power Supply’s primary side (i.e., the AC power line).
2FA Wireless SS Terminals WT30
Specifications
Ratings
Note: 1. Provide a power supply of at least 15 W, considering the inrush current generated at startup.
2. Use the WT30-FT003 Surface Mounting Bracket when installing the WT30 in environments subject to vibration.
Wireless Interface Specifications
Note: Varies according to the installation environment.
Package Contents
WT30 FA Wireless SS Terminal Terminal labels (I/O Slaves only)
Instruction Sheet Adhesive non-slip feet (Serial Master only)
Item WT30-M01-FLK Serial Master WT30-SID16/SMD16/SMD16-1 I/O Slaves
Power supply
(wireless
communications
power supply)
Rated voltage 24 V DC
Allowable voltage
range
20.4 to 26.4 V DC
Power consumption 3 W max. (See note 1.)
Error output/output
power supply
(for output circuits)
Rated voltage --- 24 V DC
Allowable voltage
range
--- 20.4 to 26.4 V DC
Insulation resistance 20 M min. (at 100 V DC) between the power
supply and chassis
20 M min. (at 100 V DC) between the power
supply and all I/O and I/O power supply and
between the power supply and chassis
Dielectric strength 1,500 V AC for 1 min between power supply
and chassis
1,500 V AC for 1 min between the power supply
and all I/O and I/O power supply and between
the power supply and chassis
Noise immunity IEC61000-4-4. 1 kV (power supply line)
Vibration resistance (See note 2.) JIS C0040
Frequency: 10 to 55 Hz; Amplitude of 0.35 mm or acceleration of 50 m/s2, whichever is smaller
(DIN Rail mounting: single amplitude of 0.1 mm or acceleration of 15 m/s2)
10 sweeps of 8 min each (i.e., 80 min in total) in X, Y, Z directions
Shock resistance Conforms to JIS C0041: 300 m/s2 3 times each in X, Y, and Z directions
Ambient operating temperature 10 to 55°C (with no condensation or icing)
(with the Terminal mounted with the dust-proof
label facing up)
Number of simultaneously ON I/O points
10 max.: 10 to 55°C (with no condensation or
icing)
16 max.: 10 to 50°C (with no condensation or
icing)
(with the Terminal mounted with the dust-proof
label facing up)
Ambient operating humidity 25% to 85% (with no condensation or icing)
Ambient environment No corrosive gases
Storage temperature 25 to 65°C (with no condensation or icing)
Protective structure IP20
Terminal construction Power supply and I/O Screwless terminal block (Phoenix Contact FFKDS/V1-5.08 or equivalent)
Serial D-sub, 9-pin (female) Inch screws (OMRON
XM2F-0910-132 or equivalent), Master station
only
---
Safety standards UL: UL508 (Listing)
Weight 330 g max.
Item Specifications
Wave type Spread Spectrum (direct sequence; DS-SS)
Communication method Simplex
Frequency band 2,401 to 2,480.2 MHz
Number of channels 67 channels (based on switching)
Transmitter output power 10 mW/MHz
Baud rate between wireless stations 100 kbps
Communications distance (See note.) Indoors: 60 m min. (approx. 50 m min. with Magnet-base Antennas and Flat Diversity Antennas)
Outdoors: Approx. 300 m min. (anticipated distances)
(without using relay stations)
Error detection method CRC-CCITT (16 bits)
Relay functions One stage using I/O slave for the serial master configuration.
Number of stations per area (See note.) 10 sets max. (recommended)
Number of I/O Slaves connected 64 max.
FA Wireless SS Terminals WT30 3
Nomenclature
Serial Master Station
I/O Slave Station
Unit No. Switch
Set the unit number of the Serial Master Station
Default: 00
Node Setting Switch (WNODE)
Set the number of connected I/O Slave Stations.
Set the node number of the Slave Stations being used as I/O Slave
Stations. The Slave Station functions as a relay station when the
node number is set to 99.
Default: 01
Channel Setting Switch (WCH)
Set the communications frequency.
Default: 02
Function Setting Switch
Serial Master Station
I/O Slave Station
Antenna terminal (ANT1)
Status
indicators
RS-232C Terminal
Connect the PLC, personal computer, etc.
Power supply terminal
Supply power to the WT30.
Unit No. switch
Set the unit number of the Serial Master Station.
Node setting switch (WNODE)
Set the number of connected I/O Slave Stations.
Channel setting switch (WCH)
Set the communications frequency
channel.
Antenna terminal (ANT2)
Received
signal
strength
indicator
Special
function
switch
Function setting switch
Make the detailed settings
for RUN/TEST/SET mode.
Mode selection switch
Switch between RUN,
TEST, and SET mode.
Serial communications
setting switch
Set the baud rate.
Status
indicators
Power supply terminal
Supply power to the WT30
and output circuits.
Mode selection switch
Switch between RUN,
TEST, and SET mode.
Node setting switch (WNODE)
Set the unit number of the I/O Slave Station.
I/O terminal status indicators (0 to 7 or 8 to 15)
The contact status is displayed.
Channel setting switch (WCH)
Set the communications frequency.
Antenna terminal (ANT2)
Received
signal
strength
indicator
Special function switch
Antenna terminal (ANT1)
Function setting switch
Make the detailed settings
for RUN/TEST mode.
I/O terminals
Connect the contact
signals.
No. Applicable
mode
ON functions OFF functions
1RUN mode Holds I/O status data
when a
communications error
occurs.
Clears I/O status data
when a
communications error
occurs.
2Enable scan list Disable scan list
3Relays used Relays not used
4TEST mode Signal strength monitor
disabled
Signal strength monitor
enabled
5All channels
automatically switched
Specified channels
6--- ---
7SET mode Scan list recognition Nothing done
8Registers specified I/O
slave
Registers all I/O slaves
automatically
9Recognizes serial
numbers
Ignores serial numbers
10 Not used --- ---
No. Applicable
mode
ON functions OFF functions
1RUN mode Holds I/O status data
when a
communications error
occurs.
Clears I/O status data
when a
communications error
occurs.
2Input hold Normal mode
3Input filter: 100 ms Input filter: 10 ms
4TEST mode Signal strength monitor
disabled
Signal strength monitor
enabled
5All channels
automatically switched
Specified channels
6Installation test
function
Nothing done
7 to
10
Not used --- ---
4FA Wireless SS Terminals WT30
Serial Communications Setting
Switch
Note: For example, if pins number 2, 3, and 4 are all ON, the total is
7, which corresponds to a baud rate of 115,200 bps.
Display
Note: When using the WD30 as the Serial Master Station, the ERR
indicator will light if normal I/O communications are not
possible due to an error in the host network.
No. Function ON OFF
1Communications setting
selection
Detailed
settings
(settings for
No. 2 to 8
used)
Default settings
(baud rate: 9,600 bps;
data length: 7 bits;
parity: even; stop bits:
2)
Settings for No. 2 to 8
are ignored.
2Baud rate (bps)
(See note.)
Total value = 0: 1,200
= 1: 2,400
= 2: 4,800
= 3: 9,600
= 4: 19,200
= 5: 38,400
= 6: 57,600
= 7: 115,200
10
320
440
5Data length 8 bits 7 bits
6Parity None Yes
7Odd Even
8Stop bits 1 bit 2 bits
Indicator Color Status Meaning (primary error)
PWR Green Lit Power is being supplied.
Not lit Power is not being supplied.
ERR
(Slave Station)
Red Lit Error output is ON:
Wireless device error or
wireless communications
error. (See note)
Not lit No wireless device error or
wireless communications
error.
COMM
(Master Station)
Yellow Lit Serial communications in
progress.
Not lit No serial communications.
0 to 15
(Slave Station)
Yellow Lit/Not lit ON/OFF status for input or
output signals
RSSI Red/
Yellow/
Green
Lit/
All not lit
Receiving Signal Strength
Indicator monitor: Number of
indicators lit (receiving signal
strength 1 to 9)
Receiving signal strength less
than 0 to 1.
MS
(Module Status)
Green Lit Communications are normal.
Flashing TEST mode or SET mode has
been activated.
Red Lit A fatal error has occurred that
cannot be recovered from.
Replace the Unit
Flashing A non-fatal error has occurred
that can be recovered from by
resetting the system.
--- Not lit Power is not being supplied or
the system is resetting.
WS
(Wireless
Status)
Green Lit The station has joined the
wireless network.
Flashing Permission to join wireless
network received from Serial
Master Station (Slave Station)
Red Lit A fatal error has occurred that
cannot be recovered from.
Flashing Error from which recovery is
possible
--- Not lit Wireless communications are
not in progress.
FA Wireless SS Terminals WT30 5
Wiring
Serial Master Station (WT30-M01-FLK)
I/O Characteristics
I/O Slave Station
RS-232C Connector
WT30 Power supply terminal
Supply power to the Unit
54321
9876
D-sub, 9-pin, Female End at WT30
Pin No. Signal I/O direction
1 --- ---
2RDOutput
3 SD Input
4 --- ---
5 SG ---
6 --- ---
7 --- ---
8 --- ---
9 --- ---
VG 01 2 3
COM
IN
IN
4567
COM ERRP
24 V DC
0 V 8 9 10 11
COM
12 13 14 15
COM ERRN
Power supply Inputs Inputs
Inputs Inputs
Error output
(
NPN
)
Error output
power supply
Error output
(PNP)
Error output
(NPN)
OUT
24 V DC
0 V 0 1 2 3
COM
4567
COM ERRN
Power supply Outputs Outputs
VG0 1 2 3
COM
IN
4567
COM ERRP
Inputs Inputs
Error output/output
power supply
Error output
(PNP)
WT30-SID16
WT30-SMD16
WT30-SMD-16-1
Item Specifications
Input Characteristics
Input voltage 24 V DC
Allowable
voltage range
20.4 to 26.4 V DC
Input
impedance
4.7 k (typical)
Input current 5 mA (typical)
ON voltage/
current
characteristics
17.4 V DC, 3.0 mA min.
OFF voltage/
current
characteristics
5.0 V DC, 1.0 mA max.
Input filter 10 ms/100 ms (Selected using switch.)
Output/Error Output
Characteristics
Input voltage 24 V DC
Allowable
voltage
20.4 to 26.4 V DC
Max.
switching
current
100 mA max. per output (at 20.4 to 26.4 V DC)
Simultaneous usage of error output NPN/PNP
is not possible.
Leakage
current
0.1 mA max.
Residual
voltage
1.0 V max.
Fuse One for every two outputs except for error
output circuits, which have one for every NPN/
PNP output. (No fuses can be replaced by the
user.)
6FA Wireless SS Terminals WT30
Input Circuit Diagram
Error Output Circuit Diagram
Output Circuit Diagram (NPN)
Output Circuit Diagram (PNP)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Serial Master Station
WT30-M01-FLK
I/O Slave Station
WT30-SID16
WT30-SMD16
WT30-SMD16-1
IN 0
IN 1
IN 2
IN 15
COM (IN)
Secondary internal circuit
V
G
ERRN
ERRP
Fuse
Secondary internal circuit
Fuse
V
G
OUT 0
OUT 1
OUT 2
OUT 7
Secondary internal circuit
Fuse
Fuse
Fuse
V
G
OUT 0
OUT 1
OUT 2
OUT 7
Fuse
OUT
3
Secondary internal circuit
Fuse
Four, 5 dia.
(15)
(15)
60 40
13.3 105 13.3
120
Surface mounting bracket
WT30-FT003
105
90
7.3
DIN rail mounting bracket
WT30-FT001 or WT30-FT002
FA Wireless SS Terminals WT30 7
With Magnet-base
Antenna
WT30-AT001
With Flat Diversity
Antenna
WT30-AT002
With Pencil Antenna
WT30-AT003
Magnet-base Antenna
WT30-AT001
Flat Diversity Antenna
WT30-AT002
Pencil Antenna
WT30-AT003
DIN Rail Mounting
Bracket
WT30-FT001
WT30-FT002
Surface Mounting
Bracket
WT30-FT003
Flat Diversity Antenna Mounting
Brackets (with magnets)
WT30-FT011
(34)
(32)
(38)
4.6
R38
R40
I/O Slave Station
DIN Rail mounting bracket
WT30-FT001 or
WT30-FT002
(23)
R50
20
I/O Slave Station DIN Rail mounting bracke
t
WT30-FT001 or
WT30-FT002
150 40
(46)
(46)
Surface Mounting Bracket
WT30-FT003
Serial Master Station
115
2010
39
35.8 dia.
10.5 dia.
57.5
2010
57.5
Three, 3 dia.
52
26
10.5 dia
.
75
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. N139-E1-01
OMRON Corporation
Industrial Automation Company
Industrial Devices and Components Division H.Q.
Wireless Components Department
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)75-344-7116/Fax: (81)75-344-7189
Printed in Japan
0105