DIN Rail Mount DataSheet DRH Series * Ratings up to 18 & 20 Amps at 600VAC * Fits standard 35mm DIN Rail * Integrated over-temperature protection * Alarm output in case of over-temperature * Multicolor LED with input status and alarm indicator * AC or DC control * Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output * C-UL-US Listed, IEC Rated, CE & RoHS Compliant, Horsepower Rated * Built-in Overvoltage Protection * Fan controlled through thermistor and microprocessor to optimize fan operation PRODUCT SELECTION Control Voltage 90-280 VAC/VDC 4-32 VDC 18A 20A DRH3P60A18 DRH3P60D18 DRH3P60A20 DRH3P60D20 AVAILABLE OPTIONS Series DRH Control Voltage A: 90-280 VAC/VDC D: 4-32 VDC Function 3P: Contactor 3P Required for valid part number For options only and not required for valid part number 60 18 U A Operating Voltage 60: 48-600 VAC Switching Type Blank: Zero Voltage Turn-On R: Instantaneous Turn-On R Rated Load Current 18: 18 Amps (3 Controlled legs) 20: 20 Amps (2 Controlled legs) OUTPUT SPECIFICATIONS (1) 18A 20A 48-600 1200 3 500 18 7.6 0.15 750 716 2330 2560 1.35 per channel 0.5 2/1.5 3/2.2 5/3.7 48-600 1200 3 500 20 7.6 0.15 750 716 2330 2560 1.35 per channel 0.5 2/1.5 3/2.2 5/3.7 Description Operating Voltage (47-63Hz) [VRMS] Transient Overvoltage [Vpk] (2) Maximum Off-State Leakage Current @ Rated Voltage [mARMS] Minimum Off-State dV/dt @ Maximum Rated Voltage [V/sec] Load Current, General Use UL508/IEC62314 @ 40C [ARMS] (3) Load Current, Motor Starting UL508 FLA/IEC62314 @ 40C [ARMS] (3) Minimum Load Current [ARMS] Maximum Surge Current [Apk] 1Cycle 60Hz Maximum Surge Current [Apk] 1Cycle 50Hz Maximum It for Fusing (8.33 msec) [Asec] Maximum It for Fusing (10 msec) [Asec] Maximum On-State Voltage Drop @ Rated Current [Vpk] Minimum Power Factor (with Maximum Load) Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :240 VAC Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :380 VAC Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :480 VAC INPUT SPECIFICATIONS (1) Description Control Voltage Range Minimum Turn-On Voltage Must Turn-Off Voltage Minimum Input Current (for on-state) Maximum Input Current Nominal Input Impedance [Ohms] Maximum Turn-On Time [msec] Maximum Turn-Off Time [msec] Do not forget to visit us at: www.crydom.com DRH3P60Dx DRH3P60Ax 4-32 VDC 4 VDC 1 VDC 2 mA 17 mA 2k 1/2 Cycle (4) 1/2 Cycle 90-280 VAC/VDC 90 VAC/VDC 10 VAC 1 mA 3 mA 100k 30 40 Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount DataSheet POWER SUPPLY SPECIFICATIONS (1) Description DRH3P60Dx Voltage Range Minimum Turn-On Voltage Must Turn-Off Voltage Maximum Source Current [mA] Maximun Start Up Time [msec] Maximun Shut Off Time [msec] ALARM OUTPUT DRH3P60Ax 90-265 VAC/VDC 90 VAC/VDC 5 VAC/VDC 40 50 500 8-32 VDC 8 VDC 3 VDC 125 20 40 (1) Description DRH3P60D18 Maximum Contact Switching Voltage [Volts] Contact Rated Current [A] Minimum Recommended Contact Load [mA] Static Contact Resistance (max. and init.)[Ohms] Turn-On / Off Condition 200 VDC, 120 VAC 0.5 10 0.2 See Status Chart GENERAL SPECIFICATIONS (1) Description Parameters Dielectric Strength, Input/Output/Base (50/60Hz) (5) Minimum Insulation Resistance (@ 500 VDC) Maximum Capacitance, Input/Output Ambient Operating Temperature Range Ambient Storage Temperature Range Weight (typical) Housing Material Housing Color LED Status Indicator (color) Short Circuit Current Rating (6) Pollution Degree Protection Degree Humidity Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/Nm) Load Terminal Screw Torque Range (in-lb/Nm) Input Terminal Wire Capacity Output Terminal Wire Capacity 3750 Vrms 109 Ohm 20 pF -10 to 70 C -40 to 70 C 2 Controlled Legs (7.4 oz [210 g]) / 3 Controlled Legs (8.5 oz [242 g]) UL94 V-0 Black and Light Gray See Status Chart 100kA 2 IP20 85% non-condensing 12 / 1.36 15 / 1.7 18-12 AWG (IEC 1-4 mm2) (stranded /solid) 18-10 AWG (IEC 1-6 mm2) (stranded /solid) THERMAL DERATE INFORMATION DRH3P60x20 DRH3P60x18 Single unit (7) Single unit (7) Multiple units 15 Load Current (Amps) Load Current (Amps) Multiple units 20 18 12 9 6 15 10 5 3 0 0 20 30 40 50 60 70 20 Ambient Temperature (C) Do not forget to visit us at: www.crydom.com 30 40 50 60 Ambient Temperature (C) Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. 70 DIN Rail Mount DataSheet WIRING AND BLOCK DIAGRAM L1 L2 L3 48-600 VAC, 50-60Hz L1 L2 L3 T2 /> L2 L3 +A3 13 +A1 DRH3P60xxx IND. CONT. EQ. -A4 T1 CONTROL INPUT INPUT STATUS XXXX Motor Controller / AC-53a Application T1 /> L1 Alarm Output (0.5 A/200 VDC, 120 VAC) Normally Open Power Supply 90-265 VAC/VDC (for A Control Voltage) 8-32 VDC (for D Control Voltage) /> 14 T2 T1 -A2 T3 T2 T3 General Use / AC-51 Application T1 T3 T2 T3 M 3 DRHP60x18 Alarm Output (DRHP60x18 & DRHP60x20) (3 controlled legs model) Main Circuit +A3 L1 L2 L3 +A1 13 -A4 T1 T2 T3 -A2 14 DRHP60x20 (2 controlled legs model) Main Circuit +A3 L1 L2 L3 +A1 -A4 T1 T2 T3 -A2 Do not forget to visit us at: www.crydom.com Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount DataSheet SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES IEC standard 60947-4-1 make a distinction between two different types of protection, (called "coordination"), which are designated types "1" and "2". Any short-circuit that occurs is cleared safely by either type of coordination. The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit. Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations, but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination, the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used. Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations, and in addition the SSR will be able to operate after the fault condition is repaired. Type of coordination 1 For resistive loads: Protection by Thermal Magnetic Circuit Breaker or by Fuse Nominal Current Class gG fuses Solid State Contactor Solid State Contactor (example from Littlefuse) 2 controlled legs 3 controlled legs 0.15-20 A CY14X51G25 DRH3P60x20 DRH3P60x18 (up to 18A) For motor loads: Protection by Thermal Magnetic Circuit Breaker or by Fuse Nominal Motor Current Thermal Magnetic Circuit Breaker (Schneider Electric) Class gG fuses (example from Littlefuse) Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs 0.40-0.63 A 0.63-1 A 1-1.6 A 1.6-2.5 A 2.5-4 A 4-6.3 A 6.3-10 A GV2ME04 / GV2P04 GV2ME05 / GV2P05 GV2ME06 / GV2P06 GV2ME07 / GV2P07 GV2ME08 / GV2P08 GV2ME10 / GV2P10 GV2ME14 / GV2P14 CY14X51G16 CY14X51G16 CY14X51G25 CY14X51G25 CY14X51G25 CY14X51G40 CY14X51G40 DRH3P60x20 DRH3P60x20 DRH3P60x20 DRH3P60x20 DRH3P60x20 DRH3P60x20 DRH3P60x20 (up to 7.6A) DRH3P60x18 DRH3P60x18 DRH3P60x18 DRH3P60x18 DRH3P60x18 DRH3P60x18 DRH3P60x18 (up to 7.6A) Type of coordination 2 For resistive loads: Protection by Fuse Nominal Current Semiconductor fuses with less than 2330 A2s Littlefuse SIBA1 (Cylindric) Ferraz (Cylindric) Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs 0.15-20 A LA50QS35-4 DRH3P60x20 DRH3P60x18 (up to 18A) Nominal Motor Semiconductor fuses with less than 2330 A2s Littlefuse SIBA1 (Cylindric) Ferraz (Cylindric) Current Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs 0.15-7.6 A DRH3P60x20 DRH3P60x18 50 058 06.32 Z093908 For motor loads: Protection by Fuse LA50QS40-4 50 058 06.40 A093909 Do not forget to visit us at: www.crydom.com Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount DataSheet STATUS CHART 1 2 3 4 5 6 50% 75% 100% 7 8 9 10 11 100% 75% 12 13 14 15 Control Input A1 Power Supply A3 Output Over Temperature Alarm Pre-alarm Alarm Output LED Color 2s 3s 0% 50% 3s 3s Fan Speed Step LED Color Description Blue 1, 15 Initial Condition 2, 14 Stand by condition. LED is blinking Blue. Fan is activated at full speed for 2 seconds after power is applied to A3 3 Green A1 is On, Output is activated, temperature rises. LED is Green 4, 12 Fan is activated at 50% speed. If A1 is disabled, LED changes to blinking Blue 5, 11 Fan is at 75% speed 6, 10 LED changes to blinking Red, fan is at full speed 7 Output is Off, Alarm Output is On, LED changes to solid Red 8 If A1 is disabled while alarm output is active, LED alternates between Blue and Red 9 LED is solid Red, temperature starts to fall 13 Fan is activated at 50% speed, temperature is steady MECHANICAL SPECIFICATIONS 3.51 [89] 0.23 [5.8] Tolerances: 0.02 in / 0.5 mm All dimensions are in: inches [millimeters] 2.91 [73.9] +A3 1.23 [31.3] 3.41 [86.7] 2.29 [58.3] 13 +A1 DRH3 2.58 [65.5] 1.68 [42.7] IND. CONT. EQ. INPUT STATUS XXXX -A4 14 -A2 3.76 [95.6] Fig. 1 1.78 [45.3] TERMINAL SCREW TYPE Top/Bottom view (Fig. 1) Do not forget to visit us at: www.crydom.com Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. Red DIN Rail Mount DataSheet ACCESSORIES ID Marker ID Marker CNLB CNLN Package of 10 plastic strip comprising 10 individual markers which can be placed for easy identification during the use of multiple units. CNL2 AGENCY APPROVALS Certification in accordance with: United States Standard for Industrial Control Equipment - UL 508 and Canadian Standard Association for Industrial Control Equipment - C22.2 No. 14. DRH series conforms to the harmonized EN standard EN/IEC 60947-4-2 Electromagnetic Compatibility: IEC 61000-4-2 : Electrostatic Discharge - Level 3 IEC 61000-4-4 : Electrically Fast Transients - Level 3 IEC 61000-4-5 : Electrical Surges - Level 3 Vibration Resistance: IEC 60068-2-6: Amplitude Range 10-55 Hz, Displacement 0.75mm Shock Resistance: IEC 60068-2-27: Peak Acceleration 15g, Duration 11msec. E116949 DRH series has Environmental Product declarations type III conforming to ISO 14025. GENERAL NOTES (1) All parameters at 25C unless otherwise specified. (2) Relay will self trigger between 900-1200V, Not suitable for capacitive loads. (3) Mounted in the Vertical position. (4) Turn-on time for Instantaneous turn-on version is 4 msec. (5) For input to alarm output the dielectric strength is 1.5kV. (6) When protected with J Class fuses rated 600 VAC, 20 A or equivalent. (7) Minimum spacing to obtain max. current is 22mm between adjacent units. Rev. 120715 Do not forget to visit us at: www.crydom.com Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount DataSheet DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH. * Disconnect all power before installing or working with this equipment. * Verify all connections and replace all covers before turning on power. Failure to follow these instructions will result in death or serious injury. RIESGO DE DESCARGA ELECTRICA O EXPLOSION. * Desconectar todos los suministros de energia a este equipo antes de trabajar con este equipo. * Verificar todas las conexiones y colocar todas las tapas antes de energizer el equipo. El incumplimiento de estas instrucciones puede provocar la muerte o lesiones serias. RISQUE DE DESCHARGE ELECTRIQUE OU EXPLOSION * Eteindre toutes les sources d'energie de cet appareil avant de travailler dessus de cet appareil * Verifier tous connections, et remettre tous couverts en olace avant de mettre sous De non-suivi de ces instructions provoquera la mort ou des lesions serieuses serieuses. GEFAHR EINES ELEKTRISCHE N SCHLAGES ODER EINER EXPLOSION. * Stellen Sie jeglichen Strom ab, der dieses Gerat versorgt, bevor Sie an dem Gerat Arbeiten durchfuhren * Vor dem Drehen auf Energie alle Anschlusse uberprufen und alle Abdeckungen ersetzen. Unterlassung dieser Anweisungen konnen zum Tode oder zu schweren Verletzungen fuhren. RISCHIO DI SCOSSA ELETTRICA O DELL'ESPLOSIONE. * Spenga tutta l'alimentazione che fornisce questa apparecchiatura prima di lavorare a questa apparecchiatura * * Verificare tutti i collegamenti e sostituire tutte le coperture prima dell'accensione L'omissione di queste istruzioni provochera la morte o lesioni serie WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER GEFAHR VON MATERIALSCHADEN UND GEHAUSEERHITZUNG * The product's side panels may be hot, allow the product to cool before touching. * Follow proper mounting instructions including torque values. * Do not allow liquids or foreign objects to enter this product. * Les panneaux lateraux du produit peuvent etre chauds. Laisser le produit refroidir avant de le toucher. * Respecter les consignes de montage, et notamment les couples de serrage. * Ne pas laisser penetrer de liquide ni de corps etrangers a l'interieur du produit. * Die Seitenwande konnen hei sein. Lassen Sie das Produkt abkuhlen, bevor Sie es beruhren. * Beachten Sie die Montageanweisungen, * Fuhren Sie keine Flussigkeiten oder Fremdkorper in das Produkt ein. Le non-respect de cette directive peut entrainer, Failure to follow these instructions can result in des lesions corporelles graves ou des serious injury, or equipment damage. dommages materiels. Die Nichtbeachtung dieser Anweisung kann Korperverletzung oder Materialschaden zur Folge haben. RIESGO DE DANOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO * Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfrie antes de tocarlo. * Respetar las instrucciones de montaje, y en particular los pares de apretado. * No dejar que penetren liquidos o cuerpos extranos en el producto. * I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo. * Seguire le istruzioni di montaggio corrette. * Non far entrare liquidi o oggetti estranei in questo apparecchio. Si no se respetan estas precauciones pueden producirse graves lesiones, danos materiales. La mancata osservanza di questa precauzione puo causare gravi rischi per l'incolumita personale o danni alle apparecchiature. Do not forget to visit us at: www.crydom.com Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. * * * DIN Rail Mount DataSheet ANNEX - ENVIROMENTAL INFORMATION The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People's Republic of China Electronic Industry Standard SJ/T11364 - 2006, Marking for Control of Pollution Caused by Electronic Information Products. Part Name Toxic or hazardous Substance and Elements Lead (Pb) Mercury (Hg) Cadmium (Cd) Hexavalent Chromium (Cr (VI)) Polybrominated biphenyls (PBB) Polybrominated diphenyl ethers (PBDE) Semiconductor die Solder - SJ/T11364 - 2006, (Pb) (Hg) (Cd) (Cr (VI)) 50 Do not forget to visit us at: www.crydom.com Copyright (c) 2015 Crydom Inc. Specifications subject to change without notice. (PBB) (PBDE)