PM1000 series power meter and
DM6000 series digital panel meter
PowerLogic®
Technical data sheet
PM1000 series power meter
Functions and characteristics
PowerLogic™ PM1000 power meter front display
(above), and rear (below).
The PowerLogic PM1000 series power meters are easy-to-use,
cost-effective meters that offer the basic measurement capabilities
required to monitor an electrical installation.
Characterized by their rugged construction, compact size and low
installation costs, these state-of-the-art multi-function meters are
ideal for control panels, motor control centers and genset panels.
Applications
n Power monitoring operations
n Load studies and circuit optimization
n Equipment monitoring
n Meter’s outputs can be used by control devices
n Preventative maintenance
Main characteristics
Accurate metering
The meter conforms to accuracy class 1.0 as per IEC 62052-11 and
IEC 62053-21.
Easy-to-read display
The bright, alphanumeric, 15mm-high LED display provides three lines for
measurement values with four digits per line. The display auto-scales for
Kilo, Mega and Giga values. Auto scrolling mode allows for easy reading.
Analog load bar
The color-coded analog load bar indicates the percentage of load
through 12 LED segments.
Turbo Key access to information
The Turbo Key button lets you access the most commonly viewed
parameters or enter setup mode with a single push of the button.
Quick and easy installation
Setup is done through the front panel keys. Quick entry to setup during
power up by TURBO key. Direct connection for metering voltage inputs
up to 480 Vac L-L.
Color-keyed terminal board labeling
The color-keyed label on the terminal board helps ensure accurate wiring.
Secure settings
Safeguard access to setup parameters with unique password protection.
A keypad lock lets you display a user selected page by default.
Part number
Description Part #
PM1200 power meter with basic readings, energy and demand
parameters, and summary screens with an RS485 communication port METSEPM1200
DM6000 series digital panel meter
Functions and characteristics
DM6000 series digital panel meter front display
(above), and rear (below)
The PowerLogic DM6000 series digital panel meters offer
the basic measurement capabilities required to monitor an
electrical installation.
Characterized by their rugged construction, compact size and low
installation costs, these state-of-the-art meters are ideal for control
panels, motor control centers and genset panels.
Applications
n Power monitoring operations
n Equipment monitoring
n Preventive maintenance
Main characteristics
Easy-to-read display
The bright, alphanumeric 15mm-high LED display provides three lines for
measurement values with four digits per line. This display auto-scales for
Kilo, Mega and Giga values. Auto scrolling mode allows for easy reading.
Analog load bar
The color-coded analog load bar indicates the percentage of load
through 12 LED segments.
Turbo Key access to information
The Turbo Key gives access to the most commonly viewed parameters
or enter setup mode with a single push of the button.
Quick and easy installation
Setup is done through the front panel keys. Quick entry to setup during
power up by TURBO key. Direct connection for metering voltage inputs
up to 480 Vac L-L.
Color-keyed terminal board labeling
The color-keyed label on the terminal board helps ensure accurate wiring.
Secure settings
Safeguard access to setup parameters with unique password protection.
A keypad lock lets you display a user-selected page by default.
Part number
Description Part#
DM6200 digital meter with basic readings plus an RS485
communication port METSEDM6200
Electrical characteristics PM1200 DM6200
Type of measurement True RMS up to the 15th harmonic
20 samples per cycle at 50 Hz
Measurement
accuracy*
Current and voltage 1.0 % of reading
Power Active 1.0 % of reading
Reactive 2.0 % of reading
Apparent 1.0 % of reading
Frequency 0.1 % of reading
Power factor 1.0 % of reading
Energy Active IEC 62053-21 Class 1
Reactive IEC 62053-23 Class 2
Apparent 1.0 % of reading
* Additional error of 0.05% of full scale, for meter input current below 100 mA
Data update rate 1 sec
Input-voltage
characteristics
Inputs V1, V2, V3, Vn
Measured voltage 80 - 480 V AC L-L without PTs
Up to 999 kV with external PTs
Permissible overload 1.10 Un (480 V L-L)
Burden 0.2 VA per phase max.
Impedance VLL - 4 Mohms, VLN - 2 Mohms
Frequency range 45 - 65 Hz
Input-current
characteristics
CT ratings Primary 1 A - 99.0 kA
Secondary 1 A - 5 A
Measurement range 50 mA - 6 A (5 mA is the starting)
Permissible overload 10 A continuous
Burden 0.2 VA per phase max.
Impedance < 0.1 ohm
Power supply AC 44 - 277 V AC at 50 Hz/60 Hz
DC 44 - 277 V DC
Ride-through time 100 ms at 50V
Burden 3 VA max.
Mechanical characteristics
Weight 18 oz (shipping), 1 oz (unpacked)
IP degree of protection Front: IP 51; Back: IP 40
Dimensions Bezel: 96 x 96 mm; Depth: 80 mm behind bezel; Panel cutout: 92 x 92 mm
Environmental conditions
Operating temperature 14°F to 140°F
Storage temperature -13°F to 158°F
Humidity rating 5 to 95 % RH non-condensing
Altitude 6500 ft
Measurement CAT III
Pollution degree 2
Protection class 2
Electromagnetic compatibility
Electrostatic discharge IEC 61000-4-2
Immunity to electromagnetic RF elds IEC 61000-4-3
Immunity to electrical fast transients IEC 61000-4-4
Immunity to surge waves IEC 61000-4-5
Conducted disturbance immunity IEC 61000-4-6
Damped oscillatory waves immunity IEC 61000-4-12
Impulse voltage withstand 6kV for 1.2/50 µS per IEC 60060-1
Conducted and radiated emissions CISPR11 Class A
Safety and standards
Safety construction Self extinguishable V0 plastic; UL 508
CE certication IEC 61010 Yes
Complies with Regulation (EC) 1907/2006 of Dec 18 2006 named REACH (related to the Registration, Evaluation, Authorization and
restrictions applicable to Chemical substances)
Communication
RS-485 port 2 terminals only; Baud rate up to 19,200 bps; Protocols: Modbus RTU
Display characteristics
Integrated LED display View 3 parameters together on 3-line, 4-digit-per-line display. Auto-scaling capability
for Kilo, Mega and Giga values. User-selectable default display page. Password
protection for setup parameters
Analog load bar Color-coded analog indicator provides an option to select the full scale of the load bar
based on the sanctioned power limit
PM1000 series and DM6000 series
Functions and characteristics (cont.)
Selection guide PM1200 DM6200
General
Use on LV and HV systems
Current and voltage accuracy 1.0 % 1.0 %
Power accuracy 1.0 %
Energy accuracy 1.0 %
Number of samples per cycle 20 at 50 Hz 20 at 50 Hz
Instantaneous rms values
Current Per phase & Neutral
Voltage Average, Phase to Neutral & Phase to Phase
Frequency
Active, apparent power Total & per phase
Power factor Average & per phase
Unbalance Current, voltage
Phase angle Between V & I, Ph1, Ph2, Ph3
RPM For generator only, speed calculated on generator
voltage output and number of machine poles
Energy values
Active, reactive, apparent energy
Demand values
Current Present & max.
Active apparent power Present & max.
Active apparent power settable by user*
* Client can select one parameter only: A, KW or KVA
Power quality measurements
Total harmonic distortion Current, voltage, per phase
Other measurements
Run hours Operating time for load in hours
ON hours Operating time for meter in hours
INTR Number of interruptions
Display
LED display
Communication
RS-485 port 1 1
Modbus protocol
PM1000 series and DM6000 series
Functions and characteristics (cont.)
PowerLogic™ PM1000 series power meter dimensions and
DM6000 series digital panel meter dimensions
PM1000 series and DM6000 series
Installation and connections
Dimensions
Three phase 4 wire WYE connection with 3 CTs and 3 PTs
Front-panel mounting
0.25 A
Aux supply
(Control Power)
44 to 277 VAC/DC
Communication
(PM1200)
LOAD
LINE
L1 L2 L3 N
Use PT, if
VAC LL 481 V
PT
44 to 277 Vac/dc
S/N:
RS 485- THD- DM-IE
Op t ion List :
80 t o 480 Vac LL
VER:03.04.00
COYYWWDXXXX
RS 485
mA to 6A
50
Connection representation only. Other types of connection are possible.
Refer to the PM1000 series Quick Start Guide for details.
PM1000 series and DM6000 series
Installation and connections (cont.)
Two phase 3 wire connection with 2 CTs
Single phase connection
Communication
(PM1200)
0.25A
Aux supply
(Control Power)
44 to 277 VAC/DC
LINE
LOAD
L1 L2 N
44 to 277 Vac/dc
S/N:
RS 485-T HD-DM- IE
Op t ion List :
80 t o 480 Vac LL
VER:03.04.00
COYYWWDXXXX
RS 485
mA to 6A
50
PT if VAC LL 481 V
Communication
(PM1200)
0.25 A
Aux supply
(Control Power)
44 to 277 VAC/DC
LINE
LOAD
L1 N
44 to 277 Vac/dc
S/N:
RS 485- THD-DM- IE
Op t ion List :
80 t o 480 Vac LL
VER:03.04.00
COYYWWDXXXX
RS 485
mA to 6A
50
PT if VAC LL 481 V
Connection representation only. Other types of connection are possible.
Refer to the PM1000 series Quick Start Guide for details.
Connection representation only. Other types of connection are possible.
Refer to the PM1000 series Quick Start Guide for details.
©2010 Schneider Electric. All rights reserved.
Schneider Electric USA, Inc.
295 Tech Park,
LaVergne, TN 37086
Tel: 866-466-7627 Toll Free
www.PowerLogic.com
This document has been
printed on recycled paper
Doc# 3000HO1005 March 2010
Schneider Electric, PowerLogic, Square D and Modbus are trademarks or
registered trademarks of Schneider Electric and/or its affiliates
in the United States and/or other countries. Other marks used
herein may be the property of their respective owners.