CSM_LG2_DS_E_2_1
1
Voltage Sensor
LG2
Compact, Economical Plug-in Type Voltage
Sensing Relay
DPDT output contacts expand the application of the Sensor to
wide-ranging fields including control, alarms, and indication.
Voltage control is possible in the same easy manner as electro-
magnetic relays, as the output relay of the sensor can be driven
directly with a detection signal.
Wide voltage setting range with fine setting capability.
Model Number Structure
Model Number Legend
1. Voltage sensor
2, 3. Operating Voltage
AB: 100, 110, 200 VAC
DB: 12, 24, 48, 100 VDC
Ordering Information
List of Models
Connecting Socket
Note: Use the above sockets to mount the Voltage Sensor securely
and prevent problems, such as faulty contact.
132
LG2-@@
Detected voltage Model
AC LG2-AB (100 VAC)
LG2-AB (200 VAC)
LG2-AB (110 VAC)
DC LG2-DB (12 VDC)
LG2-DB (24 VDC)
LG2-DB (48 VDC)
LG2-DB (100 VDC)
Socket Bracket
Type Model Model
Front-mounting socket PF083A PFC-A7
Back-mounting socket PL08 PLC-8
LG2
2
Specifications
Ratings
Note: 1. Set the must-operate voltage higher than the must-release voltage by at least 5% of the rated value.
2. Smoothing is required for the detected DC voltage.
3. The maximum applied voltage is 120% of the rated value.
4. Special models enabling a rated voltage of 220 V are available. The setting range for these models is 80% to 110%.
Characteristics
Item Detected voltage Load Setting range Control output
Model
Rated voltage Power/VA
consumption
Must-operate
(SET) voltage
(percentage
of rated
value)
Must-release
(RESET)
voltage
(percentage
of rated
value)
Rated carry
current
Switching capacity
Rated
operating
voltage
Rated operating current
Resistive
load
(cosφ = 1)
Inductive
load
(cosφ = 0.4,
L/R = 7 ms)
LG2-AB 100 VAC
200 VAC
50/60 Hz
5 VA max. 75% to 120% 70% to 115% 5 A 100 VAC
200 VAC
28 VDC
110 VDC
5A
2A
5A
0.2 A
3A
1.2 A
2A
0.1 A
110 VAC
50/60 Hz
80% to 110% 75% to 105%
LG2-DB 12 VDC
24 VDC
48 VDC
100 VDC
3 W max. 75% to 120% 70% to 115%
Repeat accuracy ±3% max. (with voltage fluctuations at the rate
of 1 V/s)
Variation due to
temperature
change
±5% max. (within the range 20 °C +20/30 °C)
Operate time 0.5 s max. (when input changes from 0 V to
120% must-operate voltage)
Release time 0.5 s max. (when input changes from 120% of
the must-release voltage to 0 V)
Insulation
resistance
10 M min. at 500 VDC (between electric
circuitry and mounting panel)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between electric
circuitry and mounting panel)
Vibration Malfunction: 16.7 Hz, 1-mm double amplitude
Shock Destruction: 294 m/s2 (approx. 30 G)
Service life Mechanically:
10,000,000 operations min.
Electrically:
50,000 operations min. (at max. applicable
load)
Weight Approx. 100 g
Ambient
operating
temperature
10 to 40°C (with no condensation)
LG2
3
Connections
Terminal Arrangement
Note: 1. *Type LG2-DB is not equipped with the rectifier circuit.
2. With type LG2-DB, care should be taken to the polarity of
the power supply.
Nomenclature
Setting Method
Operate Value
Input the actual voltage to be set, and set the SET knob to the point
at which the Relay operates.
Release Value
With the Relay operating, turn the RESET knob counterclockwise
as far as it will go, and adjust the voltage to the value to be set.
Then, gradually turn the RESET knob clockwise until it reaches the
point where the Relay is released.
Note: After completing the settings, check the settings for the operate
and release values by increasing/decreasing the input voltage.
The LG2 can be used for undervoltage detection by using the
RESET knob for the operate value and the SET knob for the
release value. The Relay will normally be ON, however, and so the
internal temperature will rise, and this will affect the product service
life.
4 5
1
2
3
7
6
8
4 5
1
2
3
7
6
8
(+) ()
The polarity indication for
terminals and applies
to the DC model (LG2-DB).
(The above diagram shows
the rear side of the Relay.)
(The above diagram shows
the rear side of the Relay.)
LG2-DB
12VDC
VOLTAGE SENSOR
VOLTAGE
RESET
70to115%
SET
70to120%
RESET knob SET knob
LG2
4
Dimensions
Note: All units are in millimeters unless otherwise indicated.
LG2-AB, LG2-DB
Accessories (Order Separately)
Connecting Socket
Socket Mounting Track (for PF083A) Hold-down Clip
Use the Hold-down Clip to secure the Voltage Sensor on the Con-
necting Socket, as well as to prevent faulty contact.
50.5 max.
38.5 max. 13.6
86
(101)
PF083A (order separately)
PF08 (order separately)
108.4
LG2 92.4
16
LG2
Mounting Height of
Sensor with Socket
4
35.4
23.5
21 max.
Two, 4.2-dia.
holes
7
41 max.
52 max.
33
4
Eight, M3.5 × 7
sems screws
2 1 8 7
3 4 5 6
Two, M4 or 4.5-dia. holes
33±0.2
Applicable Models
APR-S
LG2
PF083A Front Connecting Socket Terminal
Arrangement
(Top View)
Mounting
Holes
Note: Mount sockets to applicable models
so that points downwards.
Applicable Models
SE
APR-S
SDV
LG2
SAO
3.5
50.5 max.
40
35 max.
Approx. 20.5
41
Two, 2-dia. holes
3.9
30 dia.
45
6
7
8
1
2
3
31-dia. hole
40±
0.3
Two, 3.5-dia. or two, M3
socket mounting holes
PL08 Back Connecting Socket (Solder Terminals)
Terminal
Arrangement
Mounting
Holes
(Top View)
4.5
15 15 (5)*
7.3±0.15
35±0.3 27±0.15
1
10 1025 25 2525
1,000 (500)*
PFP-100N/PFP-50N Socket Mounting Track
* The dimensions given in parentheses are for the PFP-50N Socket Mounting Track.
Type of Socket Applicable type of
Hold-down Clip
PF083A PFC-A7
PL08 PLC-8
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2012.2
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2012 All Right Reserved.