1201-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
RTW Series
Features
u 5 Year Warranty
u Ultra Thin Package
u SEMI F47 Compliant (high line AC)
u Universal Input (85 - 265VAC)
u High Effi ciency
u Wide range AC Input
Key Market Segments & Applications
Single Output Industrial Power Supplies
Model 50W 100W 150W 300W
Input Voltage range (1) 85 - 265VAC (47 - 440Hz), 120-370VDC
Input Current (100/200VAC) (Typ) A 0.7 / 0.4 1.5 / 0.75 1.9 / 1.0 2.0 / 4.0
Inrush Current (100/200VAC) A 14 / 28 15 / 30
Power Factor - Meets EN61000-3-2
Overcurrent Protection - Yes, typically 105 - 125% (100 & 150W hiccup style)
Overvoltage Protection V Yes, typically 120-140%. Cycle input to reset
Hold Up Time (100/200VAC) ms >20
Leakage Current (max at 240VAC) mA 0.6 0.45 0.65 0.75
Load Regulation % 0.4% (0-100% load change)
Line Regulation % 0.2% (85-132 or 170-265VAC line change)
Remote Sense - Yes
Current Share - No Yes
Remote On/Off - Yes, see instruction manual on website
DC Fail Signal - No Yes
Indicator - Green LED = ON
Operating Temperature - -10°C to +71°C, -20°C start up. See derating curves on website technical downloads
Storage Temperature °C -30 to +75°C
Humidity (non condensing) - 10 - 95%RH
Cooling - Convection
Withstand Voltage - Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
Isolation Resistance - >100M at 25C & 70%RH, Output to Ground 500VDC
Vibration (non operating) - 5 - 200Hz (10 min sweep), 19.6m/s2, 1 hour (Amplitude 10mm)
Shock (Vertical mounting) (3) - 196m/s2 588m/s2
Safety Agency Approvals - UL60950-1, CSA60950-1 (cUL), EN60950-1, CE Mark
Line Dip - Complies with SEMI F47 (200VAC line only)
Conducted & Radiated EMI - EN55011 / EN55022-B, FCC-B
Immunity - IEC61000-4-2 (Level 4), -3, -4 (Level 3), -5 (Level 4)
Weight (Typ) g 290 450 600 1300
Size (WxHxD) in 0.87x3.23x4.88 0.98x3.23x6.3 1.18x3.62x7.09 1.57x4.72x9.84
Warranty yr Five Years
Specifi cations
(1) Safety approvals do not cover DC input
(2) 100/200VAC
(3) Non operating, 11 ±5ms, 3 directions, 3 times each.