ACDC
Specification
150/180 Watts
•Convection/Forcedcooled Ratings
•IT & Medical Safey Approvals (Class I & II)
•< 0.5W Standby Power
•40° C to +70° C Operation
•Remote On/Off (R Models)
•Class B Emissions
•3 Year Warranty
GCS Series
Input
Input Voltage • 85-264 VAC, derate output power
<90 VAC by 10%
Input Frequency • 47-63 Hz
Input Current • 1.5/1.8 A typical at 115 VAC, full load
(150/180 W)
0.7/0.8 A typical at 230 VAC, full load
(150/180 W)
Inrush Current • 80 A typical at 230 VAC, cold start at 25 °C
Power Factor • EN61000-3-2, class A & C
Earth Leakage Current • 200 µA max at 264 VAC/60 Hz
No Load Input Power • <0.5 W
Input Protection • Internal T3.15 A/250 V fuse in line
and neutral
Output
Output Voltage • 12-48 VDC (see Models & Ratings table)
Output Voltage Trim • ±2%, fan output will track by
same percentage
Initial Set Accuracy • ±1% V1, ±5% V Fan
Minimum Load • None
Start Up Delay • 0.5 s max
Hold Up Time • 18 ms typical
Drift • ±0.2% after 20 min warm up
Line Regulation • ±0.5% max
Load Regulation • ±0.5% V1, ±5% V Fan
Over/Undershoot • 12 - 28 V models none,
48 V models typically 5%
Transient Response • 4% max. deviation, recovery to within
1% in 500 µs for a 50-75-50% load
change
Ripple & Noise • 1% pk-pk V1, 12 V models 1.5%,
20 MHz bandwidth
Overvoltage Protection • 115-140% Vnom, recycle input to reset
Overload Protection • 110-150% V1 only
Short Circuit Protection • Continuous
Temperature • 0.05%/˚C
Coefficient
Remote Sense • Compensates for 0.5 V total voltage drop
Remote On/Off • Optional, -R models (see longform
datasheet for full details)
xppower.com
General
Efficiency • 93% typical
Isolation • 4000 VAC Input to Output 2 x MOPP,
1500 VAC Input to Ground 1 x MOPP,
500 VDC Output to Ground
Switching Frequency • 65/100 KHz PFC/Main Converter
MTBF • 569 kHrs to MIL-HDBK-217F at 25 °C, GB
Power Density • 8.5 W/in3
Environmental
Operating Temperature • -40 ˚C to +70 ˚C derate linearly from +50
°C at 2.5%/˚C to 50% load at +70 °C
Cooling • Convection & Fan cooled ratings (see
Models & Ratings tables)
Operating Humidity • 95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Operating Altitude • 3048 m
Shock • ±3 x 30g shocks in each plane, total 18
shocks. 30g = 11ms (+/-0.5msec), half
sine, conforms to EN60068-2-27 &
EN60068-2-47
Vibration • Single axis 10 - 500 Hz at 2g sweep and
endurance at resonance in all 3 planes.
Conforms to EN60068-2-6
EMC & Safety
Low Voltage PSU EMC • EN61204-3, high severity level
Emissions • EN55011/22 level B conducted
EN55011/22 level B radiated (GCS180
level A)
Harmonic Currents • EN61000-3-2, class A & C
Voltage Flicker • EN61000-3-3
Radiated Immunity • EN61000-4-3, level 3 Perf Criteria A
EFT/Burst • EN61000-4-4, level 3 Perf Criteria A
Surge • EN61000-4-5, installation class 3
Perf Criteria A
Conducted Immunity • EN61000-4-6, level 3 Perf Criteria A
Dips & Interruptions • EN55024 & EN60601-1-2 (see longform
datasheet for details)
Safety Approvals • EN60601-1, ANSI/AAMI ES60601-1,
CSA22.2 No. 60601-1 per cUL, Including
Risk Management, EN60950, UL60950