CSMMYDSE92
1
Miniature Power Relays
MY
New Latching Levers for Circuit Checking
Added to Our Best-selling
MY General-purpose Relays
Reduces wiring work by 60% when combined
with the PYF-PU Push-In Plus Socket
(according to actual OMRON measurements).
Now lead-free to protect the environment.
VDE certification (Germany).
Different colors of coil tape for AC and
DC models to more easily distinguish them.
MY(S) models with latching levers added for
easier circuit checking.
Refer to the Common Relay Precautions.
Model Number Structure
Note: 1. The models in this table are UL/CSA certified. This is indicated with a certification mark on the products.
(This does not include models with high contact reliability or plastic sealed, latching, or hermetically sealed models.)
2. Models with an asterisk (*) next to them are new versions.
3. The standard models with plug-in terminals, models with coil surge absorption diodes, and models with coil surge absorption CR circuits were used in
combination with the PYF@A-E, PYF@-S and PYF-@-PU for the EC Declaration of Conformity. These products display the CE Marking.
4. Products cannot be manufactured for the cells with a diagonal line. Ask your OMRON representative for details on manufacturing products for cells containing
“---” in the above table.
Structure
Relays with Plug-in Terminals PCB terminals Case-surface
mounting
Classification Number of
poles
With operation
indicator
Without operation
indicator With latching lever
Standard models (compliant with
Electrical Appliances and
Material Safety Act)
2
Bifurcated
MY2N*
MY2ZN
MY2*
MY2Z
MY2IN(S)* MY2-02 MY2F
3 MY3N MY3 MY3-02 MY3F
4
Bifurcated
MY4N*
MY4ZN*
MY4*
MY4Z*
MY4IN(S)*
MY4ZIN(S)*
MY4-02
MY4Z-02
MY4F
MY4ZF
Models with diode for coil surge
absorption (DC coil specification
only)
2
Bifurcated
MY2N-D2*
MY2ZN-D2
MY2-D*
MY2Z-D
MY2IN-D2(S)*
--- ---
3 MY3N-D2 MY3-D
4
Bifurcated
MY4N-D2*
MY4ZN-D2*
MY4-D*
MY4Z-D*
MY4IN-D2(S)*
MY4ZIN-D2(S)*
Models with CR circuit for coil
surge absorption (AC coil
specification only)
2 MY2N-CR* MY2-CR*
---
4
Bifurcated
MY4N-CR*
MY4ZN-CR*
MY4-CR*
MY4Z-CR*
MY4IN-CR(S)*
MY4ZIN-CR(S)*
Models with high contact
reliability 4 Bifurcated --- MY4Z-CBG
Plastic sealed models
4
Bifurcated
MYQ4N MYQ4
MYQ4Z
MYQ4-02
MYQ4Z-02
Latching models (coil latching) 2MY2K MY2K-02
Hermetic models
4
Bifurcated
MY4H
MY4ZH
MY4H-0
MY4ZH-0
Refer to Connection Socket and Mounting Bracket Selection Table on page 33 in Options for information on
the possible combinations of Models with Plug-in Terminals and Sockets.
MY
2
Miniature Power Relays: MY2
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than
the above coil specifications.
3. The above models and specifications are new versions in the MY Series.
4. Except for MY2(N)-CR Relays with the above voltage specifications, all Relays have a height of 53 mm or less.
If Mounting Brackets are required, refer to page 33 for selection information.
Ratings and Specifications
Ratings
Operating Coils (Standard Models)
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value (at a coil temperature of +23° C).
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings
*1. With no icing or condensation.
*2. This limitation is due to the diode junction temperature and elements used.
Classification Model Rated voltage (V)
Standard products Made-to-order items
Standard models MY2 12, 24, 100/110, or 200/220 VAC 110/120 or 220/240 VAC
12, 24, 48, or 100/110 VDC
Models with built-in operation indicators MY2N 12, 24, 100/110, 110/120, 200/220, or 220/240 VAC
12, 24, 48, or 100/110 VDC
Models with built-in diodes MY2-D 12, 24, or 100/110 VDC 48 VDC
Models with built-in diodes and operation
indicators MY2N-D2 12, 24, 48, or 100/110 VDC
Models with built-in CR circuits MY2-CR 100/110 or 200/220 VAC 110/120 or 220/240 VAC
Models with built-in CR circuits and operation
indicators MY2N-CR 100/110 or 200/220 VAC 110/120 or 220/240 VAC
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Item Rated current (mA) Coil resistance
(Ω)
Coil inductance (H) Must-
operate
voltage (V)
Must-
release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated
voltage (V) 50 Hz 60 Hz Armature
OFF
Armature
ON
AC
12 106.5 91 46 0.17 0.33
80% max. *1
30% min. *2
110% of rated
voltage
Approx. 0.9 to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 72.7 165 0.73 1.37
10% min. *2Approx. 0.9
24 36.3 662 3.2 5.72
48 17.6 2,725 10.6 21.0
100/110
8.7/9.6 11,440 45.6 86.2
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 5 A at 220 VAC
5 A at 24 VDC
2 A at 220 VAC
2 A at 24 VDC
Rated carry current 5 A
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 5 A
Contact configuration DPDT
Contact structure Single
Contact materials Ag
Type
Item
Standard
models
Model with built-in operation
indicator, diode, or CR circuit
Ambient
operating
temperature*1
55 to 70°C 55 to 60°C*2
Ambient
operating
humidity
5% to 85%
3
MY
Characteristics
Dimensions (Unit: mm)
Item Type Standard
models
Models with built-
in operation
indicators
Models with
built-in CR
circuits
Models with
built-in
diodes
Model with built-in
operation indicator
and diode
Model with built-in
operation indicator
and CR circuit
Contact resistance*150 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3100 MΩ min.
Dielectric
strength
Between coil and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of the
same polarity 1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance
Mechanical
AC: 50,000,000 operations min.
DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)
Electrical*4500,000 operations min.
(rated load, switching frequency: 1,800 operations/h)
Item Number of poles 2 poles Note: These are initial values.
Failure rate P value
(reference value)*51 mA at 5 VDC
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method.
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
measurement.
*4. Ambient temperature condition: 23°C
*5. This value was measured at a switching frequency of 120 operations per minute.
Weight Approx. 35 g
MY2-D MY2N-D2 MY2-CR MY2N-CR
(The coil has no polarity.) (The coil has no polarity.)
28 max.
2.6
0.5
21.5 max.
36 max. 6.4
Eight, 1.2-dia. × 2.2 oval holes
MY2, MY2N, MY2-D, MY2N-D2, MY2-CR,
and MY2N-CR Terminal Arrangement/In-
ternal Connections
(Bottom View)
Standard Models
(The coil has no polarity.)
Note: 1. An AC model has coil disconnection self-
diagnosis.
2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY2N
DC Models AC Models
Check the coil polarity when wiring
and wire all connections correctly.
(The coil has no polarity.)
Check the coil polarity when wiring
and wire all connections correctly. Check the coil polarity when wiring
and wire all connections correctly.
MY
4
Miniature Power Relays: MY2Z
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than
the above coil specifications.
Ratings and Specifications
Ratings
Operating Coil (Standard Models)
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings
*1. With no icing or condensation.
*2. This limitation is due to the diode junction temperature and elements used.
Classification Model Rated voltage (V)
Standard products Made-to-order items
Standard models MY2Z 100/110 or 200/220 VAC 12, 24, 100/120, or 200/240 VAC
12 or 24 VDC 48 or 100/110 VDC
Models with built-in operation indicators MY2ZN 100/110 or 200/220 VAC 12, 24, 100/120, or 200/240 VAC
24 VDC 12, 48, or 100/110 VDC
Models with built-in diodes MY2Z-D 24 VDC 12 or 100/110 VDC
Models with built-in diodes and operation
indicators MY2ZN-D2 24 or 100/110 VDC 12 VDC
Models with built-in CR circuits MY2Z-CR 100/110 or 200/220 VAC
Models with built-in CR circuits and operation
indicators MY2ZN-CR 100/110 VAC 200/220 VAC
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Item Rated current (mA) Coil resistance
(Ω)
Coil inductance (H) Must-
operate
voltage (V)
Must-
release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated
voltage (V) 50 Hz 60 Hz Armature
OFF
Armature
ON
AC
12 106.5 91 46 0.17 0.33
80% max.*1
30% min.*2
110% of rated
voltage
Approx. 0.9 to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 75 160 0.73 1.37
10% min.*2Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.2
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 5 A at 220 VAC
5 A at 24 VDC
2 A at 220 VAC
2 A at 24 VDC
Rated carry current 5 A
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 5 A
Contact configuration DPDT
Contact structure Bifurcated
Contact materials Au plating + Ag
Type
Item
Standard
models
Model with built-in operation
indicator, diode, or CR circuit
Ambient
operating
temperature*1
55 to 70° C 55 to 60° C*2
Ambient
operating
humidity
5% to 85%
5
MY
Characteristics
Dimensions (Unit: mm)
Item Type Standard
models
Models with built-
in operation
indicators
Models with
built-in
diodes
Model with built-in
operation indicator
and diode
Models with
built-in CR
circuits
Models with built-in
CR circuits and
operation indicators
Contact resistance*150 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3100 MΩ min.
Dielectric
strength
Between coil and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of the
same polarity 1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance Mechanical 50,000,000 operations min. (operating frequency: 18,000 operations/h)
Electrical*4200,000 operations min. (rated load, switching frequency: 1,800 operations/h)
Item Number of poles 2 poles Note: These are initial values.
Failure rate P value
(reference value)*5100
µ
A
at 1 VDC
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method.
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23°C
*5. This value was measured at a switching frequency of 120 operations per minute.
Weight Approx. 35 g
MY2Z-D MY2ZN-D2 MY2Z-CR MY2ZN-CR
(The coil has no polarity.) (The coil has no polarity.)
28 max.
2.6
0.5
21.5 max.
36 max. 6.4
Eight, 1.2-dia. × 2.2 oval holes
MY2Z, MY2ZN, MY2Z-D, MY2ZN-D2, MY2Z-CR,
and MY2ZN-CR
(The coil has no polarity.)
Note: 1. An AC model has coil disconnection self-
diagnosis.
2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY2ZN
DC Models AC Models
Check the coil polarity when wiring
and wire all connections correctly.
(The coil has no polarity.)
Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models
*For the MY2Z-CR and MY2ZN-CR,
this dimension is 53 mm max.
Check the coil polarity when wiring
and wire all connections correctly. Check the coil polarity when wiring
and wire all connections correctly.
1
5
9
13 14
12
8
4
MY
6
Miniature Power Relays: MY3
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
Ratings and Specifications
Ratings
Operating Coil (Standard Models)
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings
*1. With no icing or condensation.
*2. This limitation is due to the diode junction temperature and elements used.
Classification Model Rated voltage (V)
Standard products Made-to-order items
Standard models MY3 24, 100/110, 200/220, or 220/240 VAC 12, or 110/120 VAC
12, 24, or 100/110 VDC 48 VDC
Models with built-in operation indicators MY3N 24, 100/110, 200/220, or 220/240 VAC 12, or 110/120 VAC
24 VDC 12, 48, or 100/110 VDC
Models with built-in diodes MY3-D 24 VDC 12 or 100/110 VDC
Models with built-in diodes and operation
indicators MY3N-D2 24 VDC 12 or 100/110 VDC
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Item Rated current (mA) Coil resistance
(Ω)
Coil inductance (H) Must-
operate
voltage (V)
Must-
release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated
voltage (V) 50 Hz 60 Hz Armature
OFF
Armature
ON
AC
12 106.5 91 46 0.17 0.33
80% max.*1
30% min.*2
110% of rated
voltage
Approx. 0.9 to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 75 160 0.73 1.37
10% min.*2Approx. 0.9
24 36.9 650 ?3.2 5.72
48 18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.2
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 5 A at 220 VAC
5 A at 24 VDC
2 A at 220 VAC
2 A at 24 VDC
Rated carry current 5 A
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 5 A
Contact configuration 3PDT
Contact structure Single
Contact materials Ag
Type
Item
Standard
models Operation indicator and diode
Ambient
operating
temperature*1
55 to 70° C 55 to 60° C*2
Ambient
operating
humidity
5% to 85%
7
MY
Characteristics
Dimensions (Unit: mm)
Item Type Standard models Models with built-in
operation indicators
Models with built-in
diodes
Model with built-in operation
indicator and diode
Contact resistance*150 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3100 MΩ min.
Dielectric
strength
Between coil and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of the
same polarity 1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance Mechanical
AC: 50,000,000 operations min.
DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)
Electrical*4500,000 operations min. (rated load, switching frequency: 1,800 operations/h)
Item Number of poles 3 poles Note: These are initial values.
Failure rate P value
(reference value)*51 mA at 5 VDC
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23°C
*5. This value was measured at a switching frequency of 120 operations per minute.
Weight Approx. 35 g
MY3-D MY3N-D2
28 max.
6.3
2.6
0.5
21.5 max.
0.5
36 max. 6.4
Eleven, 1.2-dia. × 2.2 oval holes
MY3, MY3N, MY3-D, and MY3N-D2
(The coil has no polarity.)
Note: 1. An AC model has coil disconnection self-
diagnosis.
2. For the DC models, check the coil polarity
when wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY3N
DC Models AC Models
(The coil has no polarity.)
Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models
Check the coil polarity when wiring
and wire all connections correctly.
Check the coil polarity when wiring
and wire all connections correctly.
MY
8
Miniature Power Relays: MY4
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
3. The above models and specifications are new versions in the MY Series.
4. Except for MY4(N)-CR Relays with the above voltage specifications, all Relays have a height of 53 mm or less.
If Mounting Brackets are required, refer to page 33 for selection information.
Ratings and Specifications
Ratings
Operating Coil (Standard Models)
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings
*1. With no icing or condensation.
*2. This limitation is due to the diode junction temperature and elements used.
Classification Model Rated voltage (V)
Standard products Made-to-order items
Standard models MY4 24, 100/110, or 200/220 VAC 12, 110/120, or 220/240 VAC
12, 24, 48, or 100/110 VDC
Models with built-in operation indicators MY4N 12, 24, 100/110, 110/120, 200/220, or 220/240 VAC
12, 24, 48, or 100/110 VDC
Models with built-in diodes MY4-D 12, 24, 48, or 100/110 VDC
Models with built-in diodes and operation
indicators MY4N-D2 12, 24, or 100/110 VDC 48 VDC
Models with built-in CR circuits MY4-CR 100/110 or 200/220 VAC 110/120 or 220/240 VAC
Models with built-in CR circuits and operation
indicators MY4N-CR 100/110, 110/120, or 200/220 VAC 220/240 VAC
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Item Rated current (mA) Coil resistance
(Ω)
Coil inductance (H) Must-
operate
voltage (V)
Must-
release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated
voltage (V) 50 Hz 60 Hz Armature
OFF
Armature
ON
AC
12 106.5 91 46 0.17 0.33
80% max.*1
30% min.*2
110% of rated
voltage
Approx. 0.9 to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 72.7 165 0.73 1.37
10% min.*2Approx. 0.9
24 36.3 662 3.2 5.72
48 17.6 2,725 10.6 21.0
100/110
8.7/9.6 11,440 45.6 86.2
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry current 3 A
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 3 A
Contact configuration 4PDT
Contact structure Single
Contact materials Au cladding + Ag alloy
Type
Item
Standard
models
Model with built-in operation
indicator, diode, or CR circuit
Ambient
operating
temperature*1
55 to 70° C 55 to 60° C*2
Ambient
operating
humidity
5% to 85%
9
MY
Characteristics
Engineering Data
List of Actual Load Endurance (Refer to Engineering Data on page 20.)
Item Type Standard
models
Models with built-
in operation
indicators
Models with
built-in CR
circuits
Models with
built-in
diodes
Model with built-in
operation indicator
and diode
Model with built-in
operation indicator
and CR circuit
Contact resistance*150 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3100 MΩ min.
Dielectric
strength
Between coil and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of the
same polarity 1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance
Mechanical
AC: 50,000,000 operations min.
DC: 100,000,000 operations min.
(switching frequency:: 18,000 operations/h)
Electrical*4200,000 operations min.
(rated load, switching frequency: 1,800 operations/h)
ItemNumber of poles 4 poles Note: These are initial values.
Failure rate P value
(reference value)*51 mA at 1 VDC
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23° C
*5. This value was measured at a switching frequency of 120 operations per minute.
Weight Approx. 35 g
Model Load type Conditions Switching frequency Electrical durability
(operations min.)
MY4 DC24V
AC magnetic switch
35 VA at 100 VAC
Making current: 4 A,
Steady-state current: 0.35 A
ON: 1s
OFF: 3s 500,000
DC solenoid
40 W at 24 VDC
Steady-state current:
1.6 A, L/R = 10 ms
Surge-absorbing diode connected
ON: 0.5s
OFF: 1.5s 500,000
20 W at 24 VDC
Steady-state current:
0.8 A, L/R = 10 ms
Surge-absorbing diode connected
ON: 0.5s
OFF: 1.5s 1,000,000
MY
10
Dimensions (Unit: mm)
MY4-D MY4N-D2 MY4-CR MY4N-CR
28 max.
2.6
0.5
21.5 max.
36 max. 6.4
Fourteen, 1.2-dia. × 2.2 oval holes
MY4, MY4N, MY4-D, MY4N-D2,
MY4-CR, and MY4N-CR
Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models
(The coil has no polarity.)
Note: 1. An AC model has coil disconnection self-
diagnosis.
2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY4N
DC Models AC Models
Check the coil polarity when wiring
and wire all connections correctly.
(The coil has no polarity.)
Check the coil polarity when wiring
and wire all connections correctly.
Check the coil polarity when wiring
and wire all connections correctly.
(The coil has no polarity.)
(The coil has no polarity.)
11
MY
Miniature Power Relays: MY4Z
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
3. The above models and specifications are new versions in the MY Series.
Ratings and Specifications
Ratings
Operating Coil (Standard Models)
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings
*1. With no icing or condensation.
*2. This limitation is due to the diode junction temperature and elements used.
Classification Model Rated voltage (V)
Standard products Made-to-order items
Standard models MY4Z 100/110 or 200/220 VAC 110/120 or 220/240 VAC
12, 24, 48, or 100/110 VDC
Models with built-in operation indicators MY4ZN 100/110 or 200/220 VAC 24, 110/120, or 220/240 VAC
24 or 100/110 VDC 12 or 48 VDC
Models with built-in diodes MY4Z-D 24 or 100/110 VDC 12 or 48 VDC
Models with built-in diodes and operation
indicators MY4ZN-D2 12, 24, 48, or 100/110 VDC
Models with built-in CR circuits MY4Z-CR 100/110 or 200/220 VAC 110/120 or 220/240 VAC
Models with built-in CR circuits and operation
indicators MY4ZN-CR 100/110 or 200/220 VAC 110/120 or 220/240 VAC
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Item Rated current (mA) Coil resistance
(Ω)
Coil inductance (H) Must-
operate
voltage (V)
Release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated
voltage (V) 50 Hz 60 Hz Armature
OFF
Armature
ON
AC
12 106.5 91 46 0.17 0.33
80% max.*1
30% min.*2
110% of rated
voltage
Approx. 0.9 to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 72.7 165 0.73 1.37
10% min.*2Approx. 0.9
24 36.3 662 3.2 5.72
48 17.6 2,725 10.6 21.0
100/110
8.7/9.6 11,440 45.6 86.2
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry current 3 A
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 3 A
Contact configuration 4PDT
Contact structure Bifurcated
Contact materials Au cladding + Ag alloy
Type
Item
Standard
models
Model with built-in operation
indicator, diode, or CR circuit
Ambient
operating
temperature*1
55 to 70° C 55 to 60° C
Ambient
operating
humidity
5% to 85%
MY
12
Characteristics
Dimensions (Unit: mm)
Item Type Standard
models
Models with built-
in operation
indicators
Models with
built-in CR
circuits
Models with
built-in
diodes
Model with built-in
operation indicator
and diode
Model with built-in
operation indicator
and CR circuit
Contact resistance*150 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3100 MΩ min.
Dielectric
strength
Between coil and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of the
same polarity 1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance
Mechanical 20,000,000 operations min.
(switching frequency: 18,000 operations/h)
Electrical*4100,000 operations min.
(rated load, switching frequency: 1,800 operations/h)
Item Number of poles 4 poles Note: These are initial values.
Failure rate P value
(reference value)*5100 µA at 1 VDC
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
measurement.
*4. Ambient temperature condition: 23° C
*5. This value was measured at a switching frequency of 120 operations per minute.
Weight Approx. 35 g
MY4Z-D MY4ZN-D2 MY4Z-CR MY4ZN-CR
28 max.
2.6
0.5
21.5 max.
36 max. 6.4
Fourteen, 1.2-dia. × 2.2 oval holes
MY4Z, MY4ZN, MY4Z-D, MY4ZN-D2,
MY4Z-CR, and MY4ZN-CR
Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models
(The coil has no polarity.)
Note: 1. An AC model has coil disconnection self-
diagnosis.
2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY4ZN
DC Models AC Models
Check the coil polarity when wiring
and wire all connections correctly.
(The coil has no polarity.)
Check the coil polarity when wiring
and wire all connections correctly.
Check the coil polarity when wiring
and wire all connections correctly.
(The coil has no polarity.)
(The coil has no polarity.)
13
MY
Miniature Power Relays with Latching Levers: MY(S)
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
Ratings and Specifications
Ratings
Operating Coil
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value.
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings
*If you use a Socket, do not exceed the rated carry current of the Socket.
*1. With no icing or condensation.
*2. This limitation is due to the diode junction temperature and elements used.
Classification Contact configuration Model Rated voltage (V)
Standard products Made-to-order items
Models with built-in operation
indicators
2MY2IN (S) --- 100/110 or 200/220 VAC
12, 24, or 48 VDC ---
4MY4IN (S) --- 100/110 or 200/220 VAC
12, 24, or 48 VDC ---
4 bifurcated MY4ZIN (S) --- 100/110 or 200/220 VAC
--- 12, 24, or 48 VDC
Models with built-in diode for
coil surge absorption
2MY2IN-D2 (S) 12 or 24 VDC 48 VDC
4MY4IN-D2 (S) 24 VDC 12 or 48 VDC
4 bifurcated MY4ZIN-D2 (S) 24 VDC 12 or 48 VDC
Models with built-in CR circuit
for coil surge absorption
4MY4IN-CR (S) --- 100/110 or 200/220 VAC
4 bifurcated MY4ZIN-CR (S) --- 100/110 or 200/220 VAC
Item Rated current (mA) Coil resistance
(Ω)
Coil inductance (H) Must-operate
voltage (V)
Must-release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated voltage (V) 50 Hz 60 Hz Armature OFF Armature ON
AC
?
100/110 11.7/12.9 10/11 3,750 14.54 24.6
80% max.*1
30% min.*2
110% of
rated
voltage
Approx. 0.9 to
1.3 (at 60 Hz)
200/220 6.2/6.8 5.3/5.8 12,950 54.75 94.07
DC
?
12 75 160 0.73 1.37
10% min.*2Approx. 0.924 37.7 636 3.2 5.72
48 18.8 2,560 10.6 21
Number of poles 2 poles 4 poles 4 poles (bifurcated)
Load
Item
Resistive load
(cos φ = 1)
Inductive load (cos
φ = 0.4, L/R = 7 ms)
Resistive load
(cos φ = 1)
Inductive load (cos
φ = 0.4, L/R = 7 ms)
Resistive load
(cos φ = 1)
Inductive load (cos
φ = 0.4, L/R = 7 ms)
Rated load 5 A at 250 VAC
5 A at 30 VDC
2 A at 250 VAC
2 A at 30 VDC
3 A at 250 VAC
3 A at 30 VDC
0.8 A at 250 VAC
1.5 A at 30 VDC
3 A at 250 VAC
3 A at 30 VDC
0.8 A at 250 VAC
1.5 A at 30 VDC
Rated carry current 10 A*5 A*
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 10 A 5 A
Contact configuration Single Single Bifurcated
Contact materials Ag Au cladding + Ag alloy Au cladding + Ag alloy
Type
Item Model with built-in operation indicator, diode, or CR circuit
Ambient operating temperature*155 to 70° C*2
Ambient operating humidity 5% to 85%
LR
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Besuretoclearlyindicatetheratedvoltageandadd(S)whenyouplaceyourorder.
Example:MY2IN110/110VAC(S)
MY
14
Characteristics
Note: These are initial values.
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: When rated operating power is applied and ambient temperature is 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23° C
*5. This value was measured at a switching frequency of 120 operations per minute.
Item Type 2 poles 4 poles 4 poles (bifurcated)
Contact resistance*1100 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*31,000 MΩ min.
Dielectric
strength
Between coil
and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between
contacts of
different
polarity
Between
contacts of the
same polarity
1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance
Mechanical AC: 50,000,000 operations min., DC: 100,000,000 operations min. (switching
frequency: 18,000 operations/h)
20,000,000 operations min. (switching
frequency: 18,000 operations/h)
Electrical*4
500,000 operations min.
(rated load, switching frequency: 1,800
operations/h)
200,000 operations min.
(rated load, switching frequency: 1,800
operations/h)
100,000 operations min.
(rated load, switching frequency: 1,800
operations/h)
Failure rate P value
(reference value)*51 mA at 5 VDC 1 mA at 1 VDC 100 µA at 1 VDC
Weight Approx. 35 g
15
MY
Dimensions (Unit: mm)
List of Models
Terminal Arrangement/Internal Connections (Bottom View)
Eight, 1.2-dia. × 2.2 oval holes
2.6
5
8.05
6.3
14.2
8
36 max.
28 max.
21.5 max.
0.5
6.4
MY2IN (S)
MY2IN-D2 (S)
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
MY2IN(S)
(AC Model)
MY2IN(S)
(DC Models)
MY2IN-D2(S)
(DC Models Only)
− + − +
Note: For the DC models, check the coil polarity when wiring and wire all connections correctly.
Fourteen, 1.2-dia. × 2.2 oval holes
2.6
5
8.05
6.3
14.2
8
0.5
36 max. 6.4
28 max.
21.5 max.
MY4 (Z) IN (S)
MY4 (Z) IN-D2 (S)
MY4 (Z) IN-CR (S)
1
5
4
8
2
6
3
7
1
5
9
4
8
12
2
6
10
3
7
11
13 14 13 14
1
5
9
4
8
12
2
6
10
3
7
11
13 14
MY4(Z)IN(S)
(AC Models)
MY4(Z)IN-D2(S)
(DC Models Only)
MY4(Z)IN-CR(S)
(AC Models Only)
1
5
4
8
2
6
3
7
13 14
MY4(Z)IN(S)
(DC Models)
−+ −+
91210 11 91210 11
Terminal Arrangement/Internal Connections (Bottom View)
Note: For the DC models, check the coil polarity when wiring and wire all connections correctly.
MY
16
Relays with PCB Terminals: MY@-02
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
Ratings and Specifications
Ratings
Operating Coil (Standard Models)
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/
20% for the AC rated current and ±15% for the DC coil resistance.
2.
The AC coil resistance and inductance values are reference values only (at 60 Hz).
3.
Operating characteristics were measured at a coil temperature of 23°C.
4.
The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.
There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value.
*2.
There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the specified value.
Contact Ratings
*With no icing or condensation.
Number
of poles Classification Model Rated voltage (V)
Standard products Made-to-order items
2 poles Models with single
contacts MY2-02 100/110, 200/220, or 200/240 VAC 12, 24, 100, or 110/120 VAC
12, 24 or 48 VDC 100/110 VDC
3 poles Models with single
contacts MY3-02 100/110 or 200/220 VAC 12, 24, 110/120, or 220/240 VAC
24 VDC 12, 48, or 100/110 VDC
4 poles
Models with single
contacts MY4-02 100/110 or 200/220 VAC 12, 24, 110/120, or 220/240 VAC
12, 24 or 100/110 VDC 48 VDC
Bifurcated contacts MY4Z-02 --- 100/110, 110/120, or 200/220 VAC
100/110 VDC 12, 24, or 48 VDC
Item Rated current (mA) Coil
resistance (Ω)
Coil inductance (H) Must-operate
voltage (V)
Must-release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated voltage (V) 50 Hz 60 Hz Armature OFF Armature ON
AC
12 106.5 91 46 0.17 0.33
80% max.*1
30% min.*2
110% of
rated
voltage
Approx. 0.9 to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 75 160 0.73 1.37
10% min.*2Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.2
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Number of poles 2 or 3 poles 4 poles 4 poles, bifurcated contacts
Load
Item Resistive load
Inductive load
(cos
φ
= 0.4, L/R = 7 ms)
Resistive load
Inductive load
(cos
φ
= 0.4, L/R = 7 ms)
Resistive load
Inductive load
(cos
φ
= 0.4, L/R = 7 ms)
Rated load 5 A at 220 VAC
5 A at 24 VDC
2 A at 220 VAC
2 A at 24 VDC
3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry current 5 A 3 A 3 A
Maximum contact voltage 250 VAC, 125 VDC 250 VAC, 125 VDC 250 VAC, 125 VDC
Maximum contact current 5 A 3 A 3 A
Contact configuration DPDT, 3PDT 4PDT 4PDT
Contact structure Single Single Bifurcated
Contact materials Ag Au plating + Ag Au plating + Ag
Type
Item Standard models
Ambient operating temperature*55 to 70° C
Ambient operating humidity 5% to 85%
17
MY
Characteristics
Note: These are initial values.
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23° C
*5. This value was measured at a switching frequency of 120 operations per minute.
Dimensions (Unit: mm)
Item Number of poles 2 or 3 poles 4 poles 4 poles, bifurcated contacts
Contact resistance*150 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3100 MΩ min.
Dielectric
strength
Between coil and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of the
same polarity 1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock resistance Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance
Mechanical
AC: 50,000,000 operations min.
DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)
AC: 20,000,000 operations min.
(switching frequency: 18,000
operations/h)
Electrical*4
500,000 operations min.
(rated load, switching frequency:
1,800 operations/h)
200,000 operations min.
(rated load, switching frequency:
1,800 operations/h)
100,000 operations min.
(rated load, switching frequency:
1,800 operations/h)
Item Number of poles 2 or 3 poles 4 poles 4 poles, bifurcated contacts
Failure rate P value (reference value)*51 mA at 5 VDC 1 mA at 1 VDC 100 µA at 1 VDC
Weight Approx. 35 g
36 max.
21.5 max.
28 max.
*Dimensions in parentheses are for the MY4-02.
3.5
13.3 (2.6)*
0.5
0.5
4
6.3
2 poles 3 poles 4 poles
13.2 13.2
13.2
4.4
4.3
4.1
6.3
6.35
12.65
3.75
Eight, 1.3-dia. ±0.1 holes
Eleven, 1.3-dia. ±0.1 holes
Fourteen, 1.3-dia. ±0.1 holes
Relays with PCB Terminals
MY@-02 PCB Processing Dimensions (Bottom View)
Note: 1. The dimensional tolerance is ±0.1.
2. Refer to the terminal arrangement and
internal connections diagrams for the
MY2, MY3, MY4, and MY4Z.
The figures and dimensions given
here are for the MY4-02.
The 2-pole and 3-pole models
conform to these dimensions.
MY
18
Case-surface-mounting Relays: MY@F
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
Ratings and Specifications
Ratings
Operating Coil (Standard Models)
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/
20% for the AC rated current and ±15% for the DC coil resistance.
2.
The AC coil resistance and inductance values are reference values only (at 60 Hz).
3.
Operating characteristics were measured at a coil temperature of 23°C.
4.
The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.
There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2.
There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the specified value.
Contact Ratings
*With no icing or condensation.
Number of poles Classification Model Rated voltage (V)
Standard products Made-to-order items
2 poles Models with single
contacts MY2F 24, 110/110, 100/120 or 200/220 VAC 220/240 VAC
12 or 24 VDC 48 or 100/110 VDC
3 poles Models with single
contacts MY3F 100/110 VAC 24 or 200/220 VAC
--- 24 or 100/110 VDC
4 poles
Models with single
contacts MY4F 100/110 or 200/220 VAC 24 or 110/120 VAC
12 or 24 VDC 48 or 100/110 VDC
Bifurcated contacts MY4ZF 200/220 VAC ---
--- 12 or 24 VDC
Item Rated current (mA) Coil
resistance (Ω)
Coil inductance (H) Must-operate
voltage (V)
Release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated voltage (V) 50 Hz 60 Hz Armature OFF Armature ON
AC
24 53.8 46 180 0.69 1.3
80% max.*1
30% min.*2
110% of
rated voltage
Approx. 0.9 to 1.3
(at 60 Hz)
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 75 160 0.73 1.37
10% min.*2Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.2
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Number of poles 2 or 3 poles 4 poles
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms) Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 5 A at 220 VAC
5 A at 24 VDC
2 A at 220 VAC
2 A at 24 VDC
3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry current 5 A 3 A
Maximum contact voltage 250 VAC, 125 VDC 250 VAC, 125 VDC
Maximum contact current 5 A 3 A
Contact configuration DPDT, 3PDT 4PDT
Contact structure Single Single
Contact materials Ag Au plating + Ag
Type
Item Standard models
Ambient operating temperature*55 to 70° C
Ambient operating humidity 5% to 85%
19
MY
Characteristics
Note: These are initial values.
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23° C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23° C
*5. This value was measured at a switching frequency of 120 operations per minute.
Dimensions (Unit: mm)
Item Number of poles 2 or 3 poles 4 poles
Contact resistance*150 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3100 MΩ min.
Dielectric
strength
Between coil and contacts
2,000 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of the
same polarity 1,000 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance
Mechanical
AC: 50,000,000 operations min.
DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)
Electrical*4
500,000 operations min.
(rated load, switching
frequency: 1,800 operations/h)
200,000 operations min.
(rated load, switching
frequency: 1,800 operations/h)
Item Number of poles 2 or 3 poles 4 poles
Failure rate P value
(reference value) 1 mA at 5 VDC 1 mA at 1 VDC
Weight Approx. 35 g
4 poles, bifurcated contacts
The 1-pole, 2-pole, and 3-pole models
conform to these dimensions.
Fourteen, 1.2-dia. × 2.2 oval holes
2.6
2
0.5
0.5
6.4
36 max.
4.35
3.5
29 max. 38 44 max.
22.5 max.
Two, 3.5-dia. holes
or M3 screw holes
38 ±0.2
Case-surface mounting
MY@F
Mounting Hole Dimensions
The above figure is for the MY4F. Note: Refer to the terminal arrangement and
internal connections diagrams for the MY2,
MY3, MY4, and MY4Z.
MY
20
Engineering Data MY2, MY3, MY4, MY4Z, MY@-02, and MY@F
Engineering Data
Maximum Switching Capacity
MY2 and MY3
Endurance Curve
MY2 and MY3 MY2 and MY3
MY4 and MY4Z MY4 MY4
MY4Z MY4Z
DC inductive load
(L/R = 7 ms)
DC resistive load
AC resistive load
AC inductive load
(cos φ = 0.4)
10
0.1
0.5
1
5
5 10 50 100 500
Contact voltage (V)
Contact current (A)
10
50
100
500
01234567
24 VDC resistive load
110 VAC resistive load
220 VAC resistive load
10
50
100
500
01234567
Contact current (A)
Number of operations (×104 operations)
10
50
100
500
01 2 3
10
50
100
500
01 2 3
24 VDC inductive load
(L/R = 7 ms)
110 VAC inductive load
(cos φ = 0.4)
10
50
100
500
01 2 3
Contact current (A)
Number of operations (×104 operations)
220 VAC inductive load
(cos φ = 0.4)
Contact current (A)
AC inductive load
(cos φ = 0.4)
10
0.1
0.5
1
5
5 10 50 100 500
Contact voltage (V)
DC inductive load
(L/R = 7 ms)
DC resistive load
AC resistive load
30 VDC
resistive load
110 VAC resistive load
220 VAC resistive load
10
50
100
500
01 2 3
Contact current (A)
Number of operations (×104 operations)
10
50
100
500
0 0.5 1.5
30 VDC inductive load
(L/R = 7 ms)
110 VAC inductive load (cos φ = 0.4)
220 VAC inductive load
(cos φ = 0.4)
10
50
100
500
0 1.0 1.5
Contact current (A)
Number of operations (×104 operations)
24 VDC resistive load
220 VAC resistive load
10
50
100
500
01 2 3
Contact current (A)
Number of operations (×104 operations)
24 VDC inductive load (L/R = 7 ms)
10
50
100
500
0 0.5 1.5
110 VAC inductive load (cos φ = 0.4)
220 VAC inductive load (cos φ = 0.4)
10
50
100
500
0 0.5 1.0 1.5
Contact current (A)
Number of operations (×10
4
operations)
21
MY
Ambient Temperature vs.
Must-operate and Must-release Voltage
Ambient Temperature vs. Coil Temperature Rise
MY2 AC Models MY2 AC Models, 50 Hz MY2 DC Models
MY2 DC Models MY4 AC Models, 50 Hz MY4 DC Models
MY4 AC Models
MY4 DC Models
Models with built-in diodes
The diode absorbs surge from the coil. This type is best suited for applications with semiconductor circuits.
With Diode Without Diode
Note: 1. Make sure that the polarity is correct.
2. The release time will increase, but the 20-ms specification for standard models is satisfied.
3. Diode properties:The diode has a reversed dielectric strength of 1,000 V.
Forward current: 1 A
Models with Built-in CR Circuits
With CR Without CR
100
80
60
40
20
0
60 30 0 30 60 90
Ambient temperature (°C)
Must-operate/must-release voltage (%)
Must-operate voltage
Must-release voltage
Number of Relays: 10
(average value)
120
100
110
80
90
70
60
50
40
10
20
30
0
10 20 30 40 50 60 70 80
Ambient temperature (°C)
Temperature rise (°C)
When rated voltage is applied
5 A contact current × 2 circuits
2.5 A contact current × 2 circuits
No contact current
Operating temperature limit value
(E-class insulation, 120° C)
120
100
110
80
90
70
60
50
40
10
20
30
0
10 20 30 40 50 60 70 80
Ambient temperature (°C)
Temperature rise (°C)
When rated voltage is applied
5 A contact current × 2 circuits
2.5 A contact current × 2 circuits
No contact current
Operating temperature limit value
(E-class insulation, 120° C)
60 30 0 30 60 90
100
80
60
40
20
0
Ambient temperature (°C)
Must-operate/must-release voltage (%)
Must-operate voltage
Must-release voltage
Number of Relays: 10
(average value)
10 20 30 40 50 60 70 80
Ambient temperature (°C)
When rated voltage is applied
3 A contact current × 4 circuits
1.5 A contact current × 4 circuits
No contact current
Operating temperature limit value
(E-class insulation, 120° C)
120
100
110
80
90
70
60
50
40
10
20
30
0
Temperature rise (°C)
120
100
110
80
90
70
60
50
40
10
20
30
0
10 20 30 40 50 60 70 80
Ambient temperature (°C)
Temperature rise (°C)
When rated voltage is applied
3 A contact current × 4 circuits
No contact current
Operating temperature limit value
(E-class insulation, 120° C)
1.5 A contact current × 4 circuits
60 30 0 30 60 90
80
60
40
20
0
100
Ambient temperature (°C)
Must-operate/must-release voltage (%)
Must-operate voltage
Must-release voltage
Number of Relays: 10
(average value)
60 30 0 30 60 90
100
80
60
40
20
0
Ambient temperature (°C)
Must-operate/must-release voltage (%)
Must-operate voltage
Must-release voltage
Number of Relays: 10
(average value)
OFFON
A
A’
Di To digital
memory
24 VDC
OFFON
A
A’
To digital
memory
24 VDC
140 V
A
A’
C = 0.033 μF
R = 6.8 kΩ
282 V
80 V
4.12 ms
9.4 ms
200 AC
A
A’
A
A’
To digital
memory
scope
msec
2.5
600 V
282 V
ms
2.5
200 AC
MY
22
Engineering Data MY(S)
Engineering Data
Maximum Switching Capacity
MY2(S)
Endurance Curve
MY2(S) MY2(S)
MY4(S) and MY4Z(S) MY4(S) MY4(S)
MY4Z(S) MY4Z(S)
100
10
1
0.1
0.5
0.3
5
3
50
30
Contact current (A)
1 3 5 10 30 50 100 500250
Contact voltage (V)
AC resistive load AC inductive load
(cos φ = 0.4)
DC resistive load
DC inductive load
(L/R = 7)
10,000
1,000
100
10
50
30
500
300
5,000
3,000
Number of operations (×103 operations)
0246810
Contact current (A)
30 VDC
resistive load
30 VDC
resistive load
250 VAC
resistive load
250 VAC
resistive load
10,000
1,000
100
10
50
30
500
300
5,000
3,000
Number of operations (×103 operations)
012345
Contact current (A)
30 VDC
inductive load
30 VDC
inductive load
250 VAC
inductive load
250 VAC
inductive load
100
10
1
0.1
0.5
0.3
5
3
50
30
Contact current (A)
1 3 5 10 30 50 100 500250
Contact voltage (V)
AC resistive load
AC inductive load
(cos φ = 0.4)
DC resistive load
DC inductive load
(L/R = 7)
10,000
1,000
100
10
50
30
500
300
5,000
3,000
Number of operations (×103 operations)
012345
Contact current (A)
30 VDC
resistive load
30 VDC
resistive load
250 VAC
resistive load
250 VAC
resistive load
10,000
1,000
100
10
50
30
500
300
5,000
3,000
Number of operations (×103 operations)
0 0.5 1 1.5 2
Contact current (A)
30 VDC
inductive load
30 VDC
inductive load
250 VAC
inductive load
250 VAC
inductive load
10,000
1,000
100
10
50
30
500
300
5,000
3,000
Number of operations (×103 operations)
012345
Contact current (A)
30 VDC
resistive load
30 VDC
resistive load
250 VAC
resistive load
250 VAC
resistive load
10,000
1,000
100
10
50
30
500
300
5,000
3,000
Number of operations (×103 operations)
0 0.5 1 1.5 2
Contact current (A)
30 VDC
inductive load
30 VDC
inductive load
250 VAC
inductive load
250 VAC
inductive load
Energized
Y
X
ZX'
Z'
Y'
550
400
600
300
550
600 400
600
600
250
600
700
Unit: m/s2
Not energized
Common Specifications for MY2, MY3, MY4, MY4Z, MY@-02, MY@F, and MY(S)
Malfunctioning Shock
N = 20
Measurement: Shock was applied 3 times each in 6 directions along 3 axes with
the Relay energized and not energized to check the shock values that cause the
Relay to malfunction.
Criteria: Non-energized: 200 m/s2 ,
Energized: 200 m/s2
Shock direction
23
MY
Detailed Information on Models Certified for Safety Standards, MY2Z, MY3, MY
@
-02, and MY
@
F
Refer to Model Number Structure on page 1 for a list of applicable models.
The standard models are certified for UL and CSA standards.
The rated values for safety standard certification are not the same as individually defined performance values. Always check the specifications before use.
TUV-certified Models (File No. R50030059)
UL-certified Models (File No. E41515)
CSA-certified Models (File No. LR31928)
When ordering models that are certified for Lloyd’s Register (LR) Standards,
be sure to specify “LR-certified Model” with your order.
LR-certified Models (File No. 90/10270)
Model
Coil
ratings
Number
of poles
Contact ratings Certified number
of operations
MY
@
6 to 125
VDC
6 to 240
VDC
2 5 A, 250 VAC (cos φ = 1.0)
10,000 operations
3
5 A, 250 VAC (cos φ = 1.0)
0.8 A, 250 VAC (cos φ =
0.4)
4
3 A, 120 VAC (cos φ = 1.0)
0.8 A, 120 VAC (cos φ =
0.4)
Model
Coil
ratings
Number
of poles
Contact ratings Certified number
of operations
MY
6 to 240
VAC
6 to 125
VDC
2
7A, 240 VAC (General Use)
6,000
7A, 24 VDC (Resistive)
5A, 240 VAC (General Use)
5A, 250 VAC (Resistive)
5A, 30 VDC (Resistive)
3A, 265 VAC (Resistive)
1/6HP, 250 VAC
1,0001/8HP, 265 VAC
1/10HP, 120 VAC
B300 Pilot Duty 6,000
3
5A, 28 VDC (Resistive) 6,000
5A, 240 VAC (General Use)
1/6 HP, 250 VAC 1,000
4
5A, 28 VDC (General Use)
(Same polarity)
6,000
5A, 240 VAC (General Use)
(Same polarity)
5A, 30 VDC (Resistive)
(Same polarity)
5A, 250 VAC (Resistive)
(Same polarity)
0.2A, 120 VDC (Resistive)
(Same polarity)
1/6HP, 250 VAC
(Same polarity) 1,000
1/10HP, 120 VAC
(Same polarity)
B300 Pilot Duty
(Same polarity) 6,000
Model
Coil
ratings
Number
of poles
Contact ratings Certified number
of operations
MY
6 to 240
VAC
6 to 125
VDC
2
7A, 240 VAC (Resistive)
6,000
7A, 24 VDC (Resistive)
5A, 240 VAC (General Use)
5A, 250 VAC (Resistive)
5A, 30 VDC (Resistive)
1/6HP, 250 VAC 1,000
1/10HP, 120 VAC
3
5A, 28 VDC (Resistive)
6,000
7A, 240 VAC (General Use)
7A, 24 VDC (Resistive)
5A, 240 VAC (General Use)
1/6HP, 250 VAC 1,000
4
7A, 240 VAC (General Use)
(Same polarity)
6,000
7A, 24 VDC (Resistive)
(Same polarity)
5A, 240 VAC (General Use)
(Same polarity)
5A, 30 VDC (Resistive)
5A, 250 VAC (Resistive)
(Same polarity)
0.2A, 120 VDC (Resistive)
1/6HP, 250 VAC 1,000
1/10HP, 120 VAC
Model
Coil ratings
Number
of poles
Contact ratings
MY@
6 to 240
VAC
6 to 125
VDC
22 A, 30 VDC inductive load
2 A, 200 VAC inductive load
4
1.5 A, 30 VDC inductive load
0.8 A, 200 VAC inductive load
1.5 A, 115 VAC inductive load
MY
24
Detailed Information on Models Certified for Safety Standards, MY2, MY4, MY4Z, and
MY(S) Newly Released Models
Refer to Model Number Structure on page 1 for a list of applicable models.
VDE-certified Models (Certificate No. 112467UG, EN 61810-1)
UL508-certified Models (File E41515)
CSA 22.2 No. 14-certified Models (File No. LR31928)
LR-certified Models (File No. 98/10014)
Model Coil ratings Number of poles Contact ratings Certified number of operations
MY@
(New model)
6, 12, 24, 48/50, 100/
110, 110/120, 200/
220, and 220/240 VAC
6, 12, 24, 48, 100/
110, and 125 VDC
210 A, 250 VAC (cos φ = 1)
10 A, 30 VDC (L/R = 0 ms) MY2: 10,000 operations
MY4: 100,000 operations
MY4Z: 50,000 operations (AC)
45 A, 250 VAC (cos φ = 1)
5 A, 30 VDC (L/R = 0 ms)
Model Coil ratings Number of poles Contact ratings Certified number of operations
MY@
(New model)
6 to 240 VAC
6 to 125 VDC
2
10A, 250 VAC (General Use)
6,000
10A, 30 VDC (General Use)
7A, 240 VAC (General Use)
7A, 24 VDC (Resistive)
5A, 240 VAC (General Use)
5A, 250 VAC (Resistive)
5A, 30 VDC (Resistive)
3A, 265 VAC (Resistive)
1/6HP, 250 VAC
1,0001/8HP, 265 VAC
1/10HP, 120 VAC
B300 Pilot Duty (Same polarity) 6,000
4
5A, 28 VDC (General Use) (Same polarity)
6,000
5A, 240 VAC (General Use) (Same polarity)
5A, 30 VDC (Resistive) (Same polarity)
5A, 250 VAC (Resistive) (Same polarity)
0.2A, 120 VDC (Resistive) (Same polarity)
1/6HP, 250 VAC (Same polarity) 1,000
1/10HP, 120 VAC (Same polarity)
B300 Pilot Duty (Same polarity) 6,000
Model Coil ratings Number of poles Contact ratings Certified number of operations
MY@
(New model)
6 to 240 VAC
6 to 125 VDC
2
7A, 240 VAC (General Use)
6,000
7A, 24 VDC (Resistive)
5A, 240 VAC (General Use)
5A, 250 VAC (Resistive)
5A, 30 VDC (Resistive)
3A, 265 VAC (Resistive)
1/6HP, 250 VAC
1,0001/8HP, 265 VAC
1/10HP, 120 VAC
B300 Pilot Duty (Same polarity) 6,000
4
5A, 240 VAC (General Use) (Same polarity)
6,000
5A, 28 VDC (General Use) (Same polarity)
5A, 250 VAC (Resistive) (Same polarity)
5A, 30 VDC (Resistive) (Same polarity)
0.2A, 120 VDC (Resistive) (Same polarity)
1/6HP, 250 VAC (Same polarity) 1,000
1/10HP, 120 VAC (Same polarity)
B300 Pilot Duty (Same polarity) 6,000
Model Coil ratings Number of poles Contact ratings Certified number of operations
MY@
(New model)
6 to 240 VAC
6 to 125 VDC
2
10 A, 250 VAC (resistive)
2 A, 250 VAC (PF0.4)
10 A, 30 VDC (resistive)
2 A, 30 VDC (L/R = 7 ms) MY2: 50,000 operations
MY4: 50,000 operations
4
5 A, 250 VAC (resistive)
0.8 A, 250 VAC (PF0.4)
5 A, 30 VDC (resistive)
1.5 A, 30 VDC (L/R = 7 ms)
25
MY
Miniature Power Relays: MY4Z-CBG
Ordering Information
Note: Ask your OMRON representative for details on the time required to deliver made-to-order products.
Ratings and Specifications
Ratings
Operating Coil
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings Characteristics
Note:
The above values are initial values.
*1.
Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2.
Measurement conditions: With rated operating power applied, not including contact bounce.
Ambient temperature condition: 23° C
*3.
Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
measurement.
*4.
Ambient temperature condition: 23° C
*5.
This value was measured at a switching frequency of 120 operations per minute.
Classification Model Rated voltage (V)
Standard products Made-to-order items
Standard models MY4Z-CBG 100/110 or 200/220 VAC 110/120 VAC
24 or 100/110 VDC 12 or 48 VDC
Models with built-in
operation indicators MY4ZN-CBG --- 100/110 or 200/220 VAC
--- 24 VDC
Whenyourorder,specifytheratedvoltage.
Item Rated current (mA) Coil
resistance (Ω)
Coil inductance (H) Must-operate
voltage (V)
Must-release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated voltage (V) 50 Hz 60 Hz Armature OFF Armature ON
AC
100/110
11.7/12.9 10/11 3,750 14.54 24.6
80% max.*1
30% min.*2
110% of
rated
voltage
Approx. 0.9 to 1.3
(at 60 Hz)
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
DC
12 75 160 0.73 1.37
10% min.*2Approx. 0.924 36.9 650 3.2 5.72
100/110
9.1/10 11,000 45.60 86.20
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 1 A at 220 VAC
1 A at 24 VDC
0.3 A at 220 VAC
0.5 A at 24 VDC
Rated carry
current 1 A
Maximum contact
voltage 250 VAC, 125 VDC
Maximum contact
current 1 A 1 A
Contact structure Crossbar bifurcated
Contact materials Au cladding + AgPd
Contact resistance*1100 mΩ max.
Operation time*220 ms max.
Release time*220 ms max.
Maximum
operating
frequency
Mechanical 18,000 operations/h
Electrical 1,800 operations/h
Insulation resistance*3100 MΩ
Dielectric
strength
Between coil
and contacts 2,000 VAC at 50/60 Hz for 1 min.
Between contacts
of different polarity
Between contacts
of the same polarity
700 VAC at 50/60 Hz for 1 min.
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance
Mechanical 5,000,000 operations min. (operating
frequency: 18,000 operations/hr)
Electrical*450,000 operations min. (switching
frequency: 1,800 operations/h) at rated load
Failure rate P value (reference value)
*
5
100 µA at 1 VDC
Ambient operating temperature
25 to 70°C (with no icing or condensation)
Ambient operating humidity 5% to 85%
Weight Approx. 35 g
MY
26
Engineering Data
Engineering Data
Dimensions (Unit: mm)
Safety Precautions
Refer to the Common Relay Precautions.
Applicable Sockets
Use only combinations of OMRON Relays and Sockets.
Maximum Switching Capacity Contact Reliability Test
(Modified Allen Bradley Circuit)
MY4Z-CBG Contact load: 5 VDC, 1 mA resistive load
Malfunction criteria level: Contact resistance of 100 Ω
10
0.01
0.05
0.1
0.5
1
5
1 5 10 50 100 500
Contact voltage (V)
Contact current (A)
DC inductive load
(L/R = 7 ms)
DC resistive load
AC resistive load
AC inductive load
(cos φ = 0.4)
0
20
22
24
26
28
30
1 5 10 50 100 500 1,000
Number of operations (×104 operations)
Contact resistance (mΩ)
Number of Relays: 10 (average value)
Current-carrying contact
Open contacts
Self-latching contacts
Closed contacts
Malfunction rate: λ60 = 0.0046 × 10-6 per operation
(switching frequency: 200 operations/ min.)
28 max.
6.3
2.6
0.5
21.5 max.
0.5
36 max.
6.4
Fourteen, 1.2-dia. × 2.2 oval holes
MY4Z-CBG Terminal Arrangement/Internal
Connections (Bottom View)
Standard Models
(The coil has no polarity.)
27
MY
Plastic Sealed Relays: MYQ
Characteristics
Contact resistance
*
1
50 m
Ω
max.
Note: The values at the left are initial
values.
*1. Measurement conditions: 1 A at 5
VDC using the voltage drop
method
*2. Measurement conditions: With
rated operating power applied, not
including contact bounce.
Ambient temperature condition:
23° C
*3. Measurement conditions: For 500
VDC applied to the same location
as for dielectric strength
measurement.
*4. This value is for bifurcated
contacts.
*5. Ambient temperature condition:
23° C
Operation time
*
2
20 ms max.
Release time
*
2
20 ms max.
Maximum
operating
frequency
Mechanical
18,000 operations/h
Rated load
1,800 operations/h
Dielectric
strength
Between coil and contacts
1,500 VAC at 50/60 Hz for 1 min.
Between contacts of different polarity
1,500 VAC at 50/60 Hz for 1 min.
Between contacts of the same polarity
1,000 VAC at 50/60 Hz for 1 min.
Insulation resistance
*
3
100 M
Ω
min.
Vibration
resistance
Destruction
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction
1,000 m/s
2
Malfunction
200 m/s
2
Endurance
Mechanical
AC: 50,000,000 operations (5,000,000
*
4
) min., DC: 100,000,000 operations
(5,000,000
*4
) min. (switching frequency: 18,000 operations/h)
Electrical
*
5
200,000 operations min. (100,000 operations
*4
) (rated load, switching
frequency: 1,800 operations/h)
Weight
Approx. 35 g
Ratings and Specifications
Ratings
Operating Coil
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of
+15%/
20% for AC rated current and ±15% for DC coil resistance.
2.
The AC coil resistance and coil inductance values are reference values only.
3.
Operating characteristics were measured at a coil temperature of 23°C.
4.
The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.
There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2.
There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC.
To ensure release, use a value that is lower than the specified value.
Contact Ratings
*This value was measured at a switching frequency of 120 operations per minute.
*With no icing or condensation.
Item
Rated current (mA) Coil resis-
tance (
Ω
)
Coil inductance (H)
Must-
operate
voltage (V)
Must-
release
voltage (V)
Maximum
voltage (V)
Power
consumpti
on (VA, W)
Rated voltage (V)
50 Hz 60 Hz
Armature OFF
Armature ON
AC
24
53.8 46 180 0.69 1.3
80%
max.
*
1
30%
min.
*
2
110% of
rated
voltage
Approx.
0.9 to 1.3
(at 60 Hz)
100/110
11.7/12.9
10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 91.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12
75 160 0.734 1.37
10%
min.
*
2
Approx.
0.9
24
36.9 650 3.2 5.72
48
18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.0
Type
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 1 A at 220 VAC, 1 A at 24 VDC 0.5 A at 220 VAC, 0.5 A at 24 VDC
Rated carry current 1 A
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 1 A
Maximum switching capacity
(reference value) 220 VAC, 24 W 110 VAC, 12 W
Failure rate P value
(reference value) Single contacts: 1 mA at 1 VDC, Bifurcated contacts: 100 µA at 1 VDC
Contact structure Single/bifurcated
Contact materials Au plating + Ag
Ambient operating temperature 55 to 60° C*
Ambient operating humidity 5% to 85%
Ordering Information
Relays with Plug-in or Soldered
Terminals
Relays with PCB Terminals
Type 4 poles
Classification Model
Rated voltage (V)
Models
with single
contacts
Standard
models
MYQ4
100/110, 110/
120, 200/220, or
220/240 VAC
24 VDC
Models
with built-
in
operation
indicators
MYQ4N
24, 100/110,
110/120,
200/220, or
220/240 VAC
12, 24, 48, or
100/110 VDC
Bifurcated
contacts
Standard
models
MYQ4Z
100/110,
110/120, or
200/220 VAC
12 or 24 VDC
Type 4 poles
Classification Model Rated voltage
(V)
Models with
single contacts MYQ4-02
50, 200/220, or
220/240 VAC
24 VDC
Bifurcated
contacts
MYQ4Z-02
100/110 VAC
24 or 48 VDC
Whenyourorder,specifytheratedvoltage.
MY
28
Engineering Data
Engineering Data
Dimensions (Unit: mm)
Safety Precautions
For models with built-in operation indicators, check the coil polarity when
wiring and wire all connections correctly (DC operation).
Use only combinations of OMRON Relays and Sockets.
The UL and CSA certifications for this model are the same as for the MY4-
02.
Relay Replacement
To replace the Relay, turn OFF the power supply to the load and Relay coil
sides to prevent unintended operation and possible electrical shock.
Maximum Switching Capacity Endurance Curve H
2
S Gas Data Malfunctioning Shock
MYQ4(Z) MYQ4 MYQ4
Energized
Y
X
ZX’
Z’
Y’
550
400
600
300
550
600 400
600
600
250
600 700
Unit: m/s2
Not energized
N = 20
Measurement: Shock was applied
3 times each in 6 directions along
3 axes with the Relay energized
and not energized to check the
shock values that cause the Relay
to malfunction.
Criteria: Non-energized: 200 m/s
2
Energized: 200 m/s
2
Shock
direction
DC inductive load
(L/R = 7 ms)
DC resistive load
AC resistive load
AC inductive load
(cos φ = 0.4)
10
0.01
0.03
0.05
0.07
0.1
0.5
0.3
0.7
1
3
7
5
15310 5030 100 500 1,000300
Contact voltage (V)
Contact current (A)
24 VDC resistive load
24 VDC inductive load (L/R = 7 ms)
220 VAC resistive load
220 VAC inductive load (cos φ = 0.4)
1
3
5
7
10
30
50
70
100
300
500
700
1,000
0 0.4 0.6 0.8 1.00.2 1.2
Contact current (A)
Number of operations (×10
4
operations)
Note: The durability of bifurcated
contacts is one-half that of
single contacts.
max.
N=10
min.
Measurements: Temperature: 40° C, Humidity: 60% to 70%,
H
2
S concentration: 5 ±3 ppm
The change in contact resistance was measured after
leaving the Relay in the above environment for a fixed
amount of time, then removing it to a constant-temperature
and constant-humidity environment for at least 30 minutes.
80
70
60
50
40
30
20
10
115310 5030 100 500 1,000300
Standing time (h)
Contact resistance (mΩ)
Note: 1. An AC model has coil disconnection self-
diagnosis.
2. For the DC models, check the coil polarity
when wiring and wire all connections
correctly.
MYQ4(Z)N
DC Models AC Models
(The coil has no polarity.)
Relays with Plug-in Terminals
or Soldered Terminals
MYQ4(Z)(N)
Relays with PCB Terminals
MYQ4(Z)-02
21.5 max.
28 max. 28.5 max.
0.5
4.1
0.6
2.6
1.0
35.5 max. 21.5 max.
3.75 Fourteen, 1.3-dia. holes
6.35 12.65
4.1
4.4
13.2
4.3
6.3
PCB Processing Dimensions
(Bottom View)
Terminal Arrangement/Internal
Connections (Bottom View)
Standard Models
Note:
The dimensional tolerance is ±0.1.
(The coil has no polarity.)
21.5 max.
28 max. 28 max.
6.4
2.6
Fourteen, 1.2-dia. × 2.2 oval holes
35.5 max. 21.5 max.
29
MY
Latching Relays MYK
Ordering information
Relays with Plug-in or Soldered Terminals Relays with PCB Terminals
Ratings and Specifications
Ratings
Operating Coil
Note: 1. The rated current for AC is the value measured with a DC ammeter in half-wave rectification.
2. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
3. The AC coil resistance is a reference value only.
4. Operating characteristics were measured at a coil temperature of 23°C.
5. The maximum voltage capacity was measured at an ambient temperature of 23°C.
Contact Ratings
*With no icing or condensation.
Characteristics
Note:
The above values are initial values.
*1.
Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2.
Measurement conditions: With rated operating power applied, not including contact bounce.
*3.
Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
measurement.
*4.
Ambient temperature condition: 23° C
*5.
This value was measured at a switching frequency of 120 operations per minute.
Whenyourorder,specifytheratedvoltage.
Number of poles 2 poles
Classification Model Rated voltage (V)
Standard models MY2K
12 VAC
24 VAC
100 VAC
100/110 VAC
12 VDC
24 VDC
48 VDC
Number of poles 2 poles
Classification Model Rated voltage (V)
Standard models MY2K-02
24 VAC
100 VAC
12 VDC
24 VDC
Item Set coil Reset coil
Set voltage
(V)
Reset
voltage (V)
Maximum
voltage (V)
Power consumption (VA, W)
Rated current (mA)
Coil
resistance (
Ω
)
Rated current (mA)
Coil
resistance (
Ω
)
Set coil Reset coil
Rated voltage (V)
50 Hz 60 Hz 50 Hz 60 Hz
AC
12 57 56 72 39 38.2 130
80% max. 80% max. 110% max. of
rated voltage
Approx. 0.6
to 0.9
(at 60 Hz)
Approx. 0.2
to 0.5
(at 60 Hz)
24 27.4 26.4 320 18.6 18.1 550
100 7.1 6.9 5,400 3.5 3.4 3,000
DC
12 110 110 50 235
Approx. 1.3 Approx. 0.6
24 52 470 25 940
48 27 1,800 16 3,000
Load
Item Resistive load Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry
current 3 A
Maximum contact
voltage 250 VAC, 125 VDC
Maximum contact
current 3 A 3 A
Contact structure Single
Contact materials Au plating + Ag
Ambient operating
temperature
55 to 60° C*
Ambient operating
humidity
5% to 85%
Contact resistance
*
1
50 mΩ max.
Set Time
*
2
AC: 30 ms max., DC: 15 ms max.
Minimum pulse width
AC: 60 ms, DC: 30 ms
Reset Time
*
2
AC: 30 ms max., DC: 15 ms max.
Minimum pulse width
AC: 60 ms, DC: 30 ms
Maximum
operating
frequency
Mechanical
18,000 operations/h
Rated load
1,800 operations/h
Insulation resistance
*
3
100 MΩ
Dielectric
strength
Between coil
and contacts
1,500 VAC at 50/60 Hz for 1 min.
Between contacts of
different polarity
Between contacts of
the same polarity
1,000 VAC at 50/60 Hz for 1 min.
Between set/
reset coils
Vibration
resistance
Destruction
10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Shock
resistance
Destruction
1,000 m/s2
Malfunction
200 m/s2
Endurance
Mechanical
100,000,000 operations min.
(switching frequency: 18,000 operations/h)
Electrical
*
4
200,000 operations min.
(at 1,800 operations/hr, rated load)
Failure rate P value (reference value)
*
5
1 mA at 1 VDC
Weight
Approx. 30 g
MY
30
Engineering Data
Engineering Data
MY2K(-02)
Maximum Switching Capacity Endurance Curve
MY2K 100 VAC MY2K 24 VDC
Malfunctioning Shock Magnetic Interference
(External Magnetic Field)
Latching Deterioration Over
Time
DC inductive load
(L/R = 7 ms)
DC resistive load
AC resistive load
AC inductive load
(cos φ = 0.4)
10
0.1
0.5
1
5
5 10 50 100 500
Contact voltage (V)
Contact current (A)
30 VDC resistive load
110 VAC resistive load
220 VAC resistive load
10
50
100
500
01 2 3
Contact current (A)
Number of operations (×10
4
operations)
30 VDC inductive load
(L/R = 7 ms)
110 VAC inductive load
(cos φ = 0.4)
220 VAC
inductive load
(cos φ = 0.4)
10
1
50
100
500
0 0.5 1.5
Contact current (A)
Number of operations (×10
4
operations)
Energized
Not energized Y
X
Z’ X’
Z
Y’
900
1000
1000
400
400
800
700
400
400
1000
350
900
1000
300
1000
Unit: m/s
2
Armature deviation
when set
N = 20
Measurement: Shock was applied 2
times each in 6 directions along 3
axes with the Relay energized and not
energized to check the shock values
that cause the Relay to malfunction.
Criteria: Non-energized: 200 m/s2
Energized: 200 m/s2
Reset voltage
Set voltage
Uniform magnetic field strength (0e)
(Average values)
SNSN
Percentage
change (%)
80
80
60
60
40
20
20
40
60
40
8060
80
N = 5
Measurement: The percentage of change in the operating and
release voltages in a uniform external magnetic field
were measured (worst magnetic field direction).
40
Average value
60
90
80
70
100
0 50 100
300 500 1,000 5,000 10,000
Elapsed time (h)
Latching deterioration over time (%)
N = 24
Measurement: The rate of deterioration in latching ability was
measured over time with the Relay left at a normal temperature
(20 to 30°C) after latching by applying the rated voltage.
Dimensions (Unit: mm)
28 max.
6.3
2.6
0.5
21.5 max.
0.5
36 max. 6.4
Ten, 1.2-dia. × 2.2 oval holes
Relays with Plug-in Terminals
or Soldered Terminals
MY2K
Terminal Arrangement/Internal
Connections (Bottom View)
For AC
Note: R is a resistor for ampere-
turn correction. This resistor
is built-in to 50-VAC and
higher models.
(The coil has no polarity.)
Note: Pay close attention to the set
coil and reset coil polarities. If
the connections are not
correct, unintended operation
may occur.
For DC
28 max.
6.3
2.6
1
0.5
21.5 max.
36 max. 4
3.5
Ten, 1.3-dia. holes
Relays with PCB Terminals
MY2K-02
PCB Processing Dimensions
(Bottom View)
Note: The dimensional
tolerance is ±0.1.
Safety Precautions
For applications that use a 200 VAC power
supply, connect external resistors Rs and Rr to
a 100 VAC Relay.
Do not apply a voltage to the set and reset coils at the
same time. If you apply the rated voltage to both coils
simultaneously, the Relay will be set.
The minimum pulse width in the performance column is
the value for the following measurement conditions: an
ambient temperature of 23° C with the rated operating
voltage applied to the coil. The performance values
given here may not be satisfied due to use over time
and a reduction in latching performance due to
changes in the ambient temperature or in the
conditions of the application circuit.
For actual use, apply the rated operating voltage with a
pulse width based on the actual load and reset the
Relay at least once per year to prevent degradation
over time.
If the Relay is used in an environment with strong
magnetic fields, the surrounding magnetic field can
demagnetize the magnetic body and cause unintended
operation. Therefore, do not use these Relays in
environments with strong magnetic fields.
Relay Replacement
To replace the Relay, turn OFF the power supply
to the load and Relay coil sides to prevent
unintended operation and possible electrical
shock.
Applicable Sockets
Use only combinations of OMRON Relays and
Sockets.
14
Rr
Rs Rs: 7.3 kΩ, 3 W min.
Rr: 14.3 kΩ, 1 W min.
Reset power supply
Set power supply
13
9101112
58
14
31
MY
Hermetically Sealed Relays: MYH
Ordering Information
Relays with Plug-in or Soldered Terminals Relays with PCB Terminals
Ratings and Specifications
Ratings
Operating Coil
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for the AC rated current and ±15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.
Contact Ratings
*With no icing or condensation.
Characteristics
Note:
The above values are initial values.
*1.
Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2.
Measurement conditions: With rated operating power applied, not including contact
bounce.
Ambient temperature condition: 23° C
*3.
Measurement conditions: For 500 VDC applied to the same location as for dielectric
strength measurement.
*4.
This value is for bifurcated contacts.
*5.
Ambient temperature condition: 23° C
*6.
This value was measured at a switching frequency of 120 operations per minute.
Whenyourorder,specifytheratedvoltage.
Type 4 poles
Classification Model Rated voltage (V)
Models with single
contacts MY4H 24, 100/110, or 110/120 VAC
12, 24, 48, or 100/110 VDC
Bifurcated contacts MY4ZH 24, 100/110, or 110/120 VAC
12, 24, 48, or 100/110 VDC
Type 4 poles
Classification Model Rated voltage (V)
Models with single
contacts MY4H-0 110/120 VAC
24 VDC
Bifurcated
contacts MY4ZH-0 24 or 100/110 VDC
Item Rated current (mA) Coil
resistance (Ω)
Coil inductance (H) Must-operate
voltage (V)
Must-release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated voltage (V) 50 Hz 60 Hz Armature OFF Armature ON
AC
24 53.8 46 180 0.69 1.3
80% max.*1
30% min.*2
110% of
rated voltage
Approx. 0.9 to 1.3
(at 60 Hz)
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
DC
12 75 160 0.73 1.37
10% min.*2Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.2
Load Models with single
contacts Bifurcated contacts
Item Resistive
load
Inductive load
cos
φ
= 0.4
L/R = 7 ms
Resistive
load
Inductive load
cos
φ
= 0.4
L/R = 7 ms
Rated load
3 A at 110 VAC
3 A at 24 VDC
0.8 A at 110 VAC
1.5 A at 24 VDC
3 A at 110 VAC
3 A at 24 VDC
0.8 A at 110 VAC
1.5 A at 24 VDC
Rated carry
current 3 A 3 A
Maximum contact
voltage
125 VAC
125 VDC
125 VAC
125 VDC
Maximum contact
current 3 A 3 A
Contact structure Single Bifurcated
Contact materials Au plating + Ag
Ambient operating
temperature
25 to 60° C*
Ambient operating
humidity
5% to 85%
Contact resistance
*
1
50 m
Ω
max.
Operation time
*
2
20 ms max.
Release time
*
2
20 ms max.
Maximum
operating
frequency
Mechanical
18,000 operations/h
Rated load
1,800 operations/h
Insulation resistance
*
4
100 M
Ω
min.
Dielectric
strength
Between coil
and contacts
1,000 VAC at 50/60 Hz for 1 min.
(700 VAC between contacts of the same polarity.)
Between contacts
of different polarity
Vibration
resistance
Destruction
10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.5-mm single amplitude
(1.0-mm double amplitude)
Shock
resistance
Destruction
1,000 m/s
2
Malfunction
200 m/s
2
Endurance
Mechanical
50,000,000 operations (5,000,000 operations
*
4
) min.
(operating frequency: 18,000 operations/h)
Electrical
*
5
100,000 operations (50,000 operations
*
4
) min. rated
load, switching frequency: 1,800 operations/h)
Failure rate P value
(reference value)
*
6
Single contacts: 100
µ
A at 1 VDC
Bifurcated contacts: 100
µ
A at 100 mVDC
Weight
Approx. 50 g
MY
32
Engineering Data
Engineering Data
Dimensions (Unit: mm)
Safety Precautions
PCB Design for Hermetically Sealed Relays
When a Relay with PCB Terminals is mounted, a short-circuit can occur
depending on the design of the PCB pattern because the Relay itself is made
out of metal.
Solution
Refer to the external dimensions of the Relay and design the PCB pattern with
enough space to prevent this problem.
Applicable Sockets
Use only combinations of OMRON Relays and Sockets.
Application Environment for Hermetically Sealed
Relays
Humid environments can cause insulation problems, which may result in short-
circuiting or unintended operation.
Solution
Do not use these Relays in any environment where the Relay will come into
contact with water vapor, condensation, or water droplets. This can reduce the
surface tension of the insulating beads and cause short-circuiting or unintended
operation due to poor insulation.
Relay Replacement
To replace the Relay, turn OFF the power supply to the load and Relay coil
sides to prevent unintended operation and possible electrical shock.
Maximum Switching Capacity Endurance Curve
MY4(Z)H MY4H
Note: The durability of bifurcated contacts is one-half that of single contacts.
DC inductive load
(L/R = 7 ms)
DC contact load
AC contact load
AC inductive load
(cos φ = 0.4)
0.1
0.5
1
5
5 10 50 100 500
Contact voltage (V)
Contact current (A)
110 VAC resistive load
24 VDC resistive load
10
50
100
500
01 2 3
Contact current (A)
24 VDC inductive load (L/R = 7 ms)
110 VAC inductive load
(cos φ = 0.4)
Number of operations (×104 operations)
28.5 max.
2.6
Fourteen, 1.2-dia. × 3 oval holes
35 max. 6.4
22 max.
0.5
Relays with Plug-in Terminals
or Soldered Terminals
MY4(Z)H
Terminal Arrangement/
Internal Connections
(Bottom View)
(The coil has no polarity.)
28.5 max.
1.3 dia.
7
35 max.
5.5 22 max.
1.3 dia.
3.9
Fourteen, 2-dia. holes
6.35 11.85
4.9
4.4
13.2
3.95
6.8
Relays with PCB Terminals
MY4(Z)H-0 PCB Processing Dimensions
(Bottom View)
33
MY
Options (Order Separately)
Connection Socket and Mounting Bracket Selection Table
(The possible combinations of models with plug-in terminals and sockets)
Note: Refer to Common Socket and DIN Track Products for the external dimensions of the Socket Relays and details on Hold-down Clips.
*1. The information in parentheses is the model number of the applicable Mounting Bracket. Mounting Brackets are sold in sets of two. However, the PYC-P is just
one Mounting Bracket.
*2. The PYF@A-E has a terminal cover with finger protection. The Socket and Terminal Cover are integrated into one unit. Round terminals cannot be used.
Use forked terminals or ferrules instead.
*3. A Push-In Plus Terminal Block Socket functions as a release lever to hold or remove a Relay. Refer to PYF-
@@
-PU/P2RF-
@@
-PU for details.
*4. If an MY@I(S) Relay with a Latching Lever is used in combination with a PY@-02 Socket for Relays with PCB Terminal Socket and PYC-P Mounting Brackets, the
lever will not operate.
*5. We recommends using the PYC-E1 Mounting Bracket for a MY2I(S) Relay with Latching Lever. (If the PYC-A1 is used with the MY2I(S), the latching lever will be
blocked by the Mounting Bracket and the lever will not operate.)
*6. The Mounting Brackets are applicable for Relays with a height of 36 mm or less. If the Relay height is greater than 53 mm, use Y92H-3 for the Front-mounting
Socket and PYC-1 for the Back-mounting Socket. (The Y92H-3 is a set of two Brackets and the PYC-1 is just one Bracket.)
Mounting Heights with Sockets (Unit: mm)
Connecting
method Front-mounting Sockets (PYF
@
)
Back-mounting Sockets (PY
@
)
Mounting
method Track or screw mounting
Screw
mounting
only
Track or
screw
mounting
Screw terminals
Push-In Plus
Terminal
Block *3
Solder terminals
Wrapping terminals
Relays with
PCB
Terminals
*4
Terminal Type
Screw
terminal
size: M3
Screw terminal
size: M3
(finger
protection
structure) *2
Screw terminal size:
M3.5
Terminal length:
25 mm
Terminal length:
20 mm
Number
of pins
(Sold separately: Hold-down Clips) *1
With
Release
Lever
Without
Mounting
Brackets *1
With
Mounting
Brackets
Without
Mounting
Brackets *1
With
Mounting
Brackets
Without
Mounting
Brackets *1
With
Mounting
Brackets
(Sold
separately:
Hold-down
Clips)
*1
8
MY2
@ (except
for MY2K@ and
MY2Z@-CR)
PYF08A
(PYC-A1)
PYF08A-E
(PYC-A1)
---
PYF08M
(PYC-P) PYF-08-PU
PY08
(PYC-P) PY08-Y1 PY08QN
(PYC-P)
PY08QN-Y1
PY08QN2
(PYC-P)
PY08QN2-Y1
PY08-02
(PYC-P)
MY2I(S) *5 PYF08A
(PYC-E1)
PYF08A-E
(PYC-E1)
MY2Z
@
-CR *6 PYF08A
(Y92H-3)
PYF08A-E
(Y92H-3) --- PY08
(PYC-1) PY08-Y3 PY08QN
(PYC-1) --- PY08QN2
(PYC-1) --- PY08-02
(PYC-1)
11 MY3
@
PYF11A
(PYC-A1) --- --- --- --- PY11
(PYC-P) PY11-Y1 PY11QN
(PYC-P)
PY11QN-Y1
PY11QN2
(PYC-P)
PY11QN2-Y1
PY11-02
(PYC-P)
14
MY4
@
MY4H
MYQ4
MY4(S)
MY2K
PYF14A
(PYC-A1)
PYF14A-E
(PYC-A1)
PYF14T
(PYC-A1) --- PYF-14-PU PY14
(PYC-P) PY14-Y1 PY14QN
(PYC-P)
PY14QN-Y1
PY14QN2
(PYC-P)
PY14QN2-Y1
PY14-02
(PYC-P)
Front-mounting Sockets
Screw terminal
(PYF
@
A (-E), PYF14T, PYF08M)
Push-In Plus Terminal Block Sockets
(PYF-
@
-PU)
Back-mounting Sockets
Solder terminals/Wrapping terminals
(PY
@
)
Relays with PCB Terminals
(PY
@
-02)
MY
MY
PYF@A or PYF14T PYF08M
54 (71)
66 (83)70 (87)
Note: 1.
The PYF
@
A can be mounted on a track or with screws.
2.
The heights given in parentheses are the measurements
for 53-mm-high Relays.
3.
Use the PYC-P Mounting Bracket for the PYF08M.
3.9
28.1
67.5 64.1
MY
PYF-@-PU
39 (56) MY
PY@
MY
48.2
PY@-02
MY
34
Socket Mounting Plate (t = 1.6) (Unit: mm)
Use a Socket Mounting Plate to mount multiple connection Back-mounting Sockets in a row.
Compliance with Electrical Appliances and Material Safety Act
All standard models comply with the Electrical Appliances and Material
Safety Act.
Always protect any exposed terminals (including Socket terminals) after
wiring with insulation tubes or resin coating on PCBs.
*Under the Electrical Appliances and Material Safety Act, do not use any 4-
pole models with a voltage that exceeds 150 VAC. However, this restriction
can be ignored if compliance with the Electrical Appliances and Material
Safety Act is not required.
Safety Precautions
Refer to the Common Relay Precautions.
Handling
For models with a built-in operation indicator, models with a built-in diode, or
high-sensitivity models, check the coil polarity when wiring and wire all
connections correctly (DC operation).
Installation
There is no specifically required installation orientation, but make sure that
the Relays are installed so that the contacts are not subjected to vibration or
shock in their movement direction.
Use two M3 screws to attach case-surface-mounted models (MY@F) and
tighten the screws securely (tightening torque: 0.98 Nm).
Using MY-series Relays with Microloads with
Infrequent Operation
If any standard MY-series Relays (e.g., MY4) are used infrequently to switch
microloads, the contacts may become unstable and eventually result in poor
contact. In this case, we recommend using the MY4Z-CBG Series, which has
high contact reliability for microloads (Refer to page 25.)
About the Built-in Diode and CR Elements
The diode or CR element that are built into the Relay are designed to absorb
the reverse voltage from the Relay coil. If a large surge in voltage is applied to
the diode or CR element from an external source, the element will be destroyed.
If there is the possibility of large voltage surges that could be applied to the
elements from an external source, take any necessary surge absorption
measures.
Latching Levers
Turn OFF the power supply when operating the latching lever. After you use
the latching lever always return it to its original state.
Do not use the latching lever as a switch.
The latching lever can be used for 100 operations min.
Relay Replacement
To replace the Relay, turn OFF the power supply to the load and Relay coil
sides to prevent unintended operation and possible electrical shock.
Attaching and Removing Relay Hold-down Clips
When you attach a Hold-down Clip to or remove it from a Socket, wear gloves
or take other measures to prevent injuring your fingers on the Hold-down Clip.
Item Type
Applicable Sockets
For mounting
1 Socket
For mounting
8 Sockets
For mounting
36 Sockets
Without Mounting Brackets
PY08, PY08QN(2), PY11, PY11QN(2), PY14, and PY14QN(2)
PYP-1 PYP-18 PYP-36 Note: You can cut the PYP-18
and PYP-36 to any required
length.
With Mounting Brackets
PY08-Y1, PY08QN(2)-Y1, PY11-Y1, PY11QN(2)-Y1, PY14-Y1,
and PY14QN(2)-Y1
PYP-1 PYP-18 PYP-36
Square
hole
28
42±0.1
5.1
49
Two, 3.4-dia. holes
The minimum order for the PYP-1 is 10 pieces.
27.4×17 = 465.8±0.6
492
49
42±0.1
5.1
21.6 13.1
4.5
3.4 R1.7
27.4
72, oval holes
t = 1.6
±0.15
27.4×17 = 465.8±0.6
27.4×17 = 465.8±0.6
492
86.4
39.7±0.2
39.7±0.2
5.1
21.6
21.6
13.1
4.5
3.4 R1.7
13.1
27.4
72, oval holes
t = 1.6
±0.15
21.4 +0.2
0
Model Number of
poles Coil ratings Contact ratings
MY
1
2
3
6 to 220 VAC
6 to 120 VDC 5 A, 200 VAC
4 * 6 to 110 VAC
6 to 120 VDC 3 A, 115 VAC
Precautions for Correct Use
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omrons analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2017.4
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2017 All Right Reserved.