Trip Time (sec)
ORDERING EXAMPLE:
2 Mounting Bushing
A Plastic 3/8”-27
C Plastic M11
W Wing Clip
7 Mounting Nut
N None or Wing Clip
A Plastic Knurled
B Metal Knurled
C Metal Hex Nut
D Sealing Knurled Boot
9 Indicator Plate
0 None
1 Embossed Aluminium
2 Silver Letters on Black
4 Terminal Options
S Straight
L 90° Bend, Left Side
R 90° Bend, Right Side
5 Button Color
B Black
WB White with
trip indication
8 Std.Current Rating
2.5, 3.0, 4.0, 5.0, 6.0,
7.0, 8.0, 10.0, 12.0,
15.0, 16.0, 20.0
6 Button Marking
0 None
1 White, Vertical
2 Black, Vertical
3 White, Horizontal
4 Black, Horizontal
ATR20 - C - 63 S - B 1 - A - 7.0A - 2
Product Type
The ATR20 circuit protector is a single pole, thermally operated,
snap-action overload protector, with a manual, push-to-reset
mechanism providing reliable ‘trip-free’ operation on overloads
and short-circuits within the maximum capacity specified. A high
contact force is maintained until the contacts break due to
overload through the snap-action bimetal disc.
OPERATION:
The entire mechanism of the circuit protector is based on the
use of a snap-action cantilevered, thermo-bimetal disc profile
with silver alloy contacts, designed to open in the event of a
current flow in excess of the rated current, according to the
time/current characteristics of the device. The contacts open
and close with a positive snap action and the tripped state is
clearly indicated by the extended projection of the reset button.
TIME & CURRENT CHARACTERISTICS:
The standard characteristic is valid for ambient temperature
of 25°C. If the device is to be used in an ambient temperature
other than 25°C, allowance must be made when selecting the
current rating according to the following guidelines:
Example:
Normal continuous current 5.0A
Ambient temperature 40°C
Multiplication factor 1.1
Selected rated current at 40°C
ambient temperature 5.0 x 1.1 = 5.5
Select 6.0A (nearest)
Operating Characteristics:
Technical Data
Function SPST
Standard Ratings (Amps) 2.5, 3, 4, 5, 6, 7, 8, 10, 12, 15, 16, 20
AC - inductive DC - resistive
Rated Voltage 125 / 250 VAC 50/60 Hz, 50VDC
Method of Tripping Thermal TO, Cycling trip-free
Type of Actuation Reset button, type “R”
Initial Insulation Resistance >100MΩ (DC 500V)
Dielectric Strength 1500 VAC for 1 minute
Housing Material Thermoplastic / Thermoset
Button Material Thermoset
Contact Material Silver Alloy
Terminal Material Copper Alloy
Resettable Overload Capacity 10 X Rated Current
Overload Capacity 2X Rated Current for min. 50 switching cycles,
per UL 1077
Rated Conditional Short Circuit 1000A 125 / 250VAC, 50VDC,
Current Capacity Inc1 (PC1) SC:1kA, C1, 125 / 250VAC, 50VDC,
Ref. EN 60934 Ref. CSA 22.2 No. 235-04, UL 1077
Weight Approximately 17g
Applicable Approvals UL 1077, CSA 22.2 No. 235-04, TÜV EN 60934
Supplementary Circuit Protector
ATR20
CURRENT (%)
0.1
1
10
100
1000
0 100
135
200 300 400 500 600 700 800 900 1000
MULTIPLIER
MULTIPLIER
Ambient
temp.
(C°)
Ambient
temp.
(C°)
-20°C -10°C 0°C 10°C 25°C 30°C 35°C
2.5A
3A to 4A
0.58 0.6 0.7 0.8 1 1
0.8 0.85 0.9 0.9 1 1 1.1
-20°C -10°C 0°C 10°C 25°C 40°C 50°C 60°C
5A to 20A 0.8 0.85 0.88 0.9 1 1.1 1.3 1.4
Tripping Current Code (TC) TC 2, ref. CSA 22.2 No. 235-04
Overload Rating OL0 240VAC, 50VDC,
ref. CSA 22.2 No. 235-04
3 Terminal Size
63 .250
Application Type General Industrial Ref. CSA 22.2 No. 235-04
Impulse Withstand Voltage 2.5kV Ref. EN60934
Contact Gap Micro Disconnection (µ) Ref. EN60934
Rated Short Circuit Capacity Icn Min. 6 X Rated Current (6 X In), 250VAC inductive
Ref. EN 60934 Min. 4 X Rated Current (4 X In), 50VDC resistive