S7-200
SIMATIC
Text Display (TD) User Manual
System Manual
08/2008
A5E00765548-03
Preface
Product Overview
1
Installing your Text Display
(TD) Device
2
Using the Keypad Designer
to Create a Custom
Faceplate for your Text
Display (TD) Device
3
Using the Text Display
Wizard to Configure the S7-
200 CPU for Your Text
Display (TD) Device
4
Operating Your Text Display
(TD) Device
5
Technical Specifications and
Reference Information
A
Connecting Multiple Devices
on a Network
B
Troubleshooting
C
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
A5E00765548-03
Ⓟ 02/2013 Technical data subject to change
Copyright © Siemens AG 2007.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 3
Preface
Scope of this Manual
This manual describes the installation, configuration and operation of the TD 100C version
1.0, the TD 200 version 3.0, the TD 200C version 1.0, and the TD400C version 2.0. This
manual also describes the Text Display wizard of STEP 7-Micro/WIN (used to configure the
S7-200 CPU for the TD devices) and the Keypad Designer application (used to configure the
keypad of the TD 100C, the TD 200C and the TD400C).
To utilize these TD devices, you must use the following:
STEP 7-Micro/WIN version 4.0 SP2 or greater for TD 100C version 1.0
STEP 7-Micro/WIN version 4.0 or greater for TD 200C version 1.0 and TD 200 version
3.0
STEP 7-Micro/WIN version 4.0 SP6 or greater for the TD400C version 2.0
Purpose of the manual
The SIMATIC Text Display (TD) User Manual is a combination user and reference manual
that describes the operation of the TD devices with an S7-200 CPU.
Required Basic Knowledge
This manual is designed for engineers, programmers, and maintenance personnel who have
a general knowledge of programmable logic controllers and operator interfaces.
Recycling and Disposal
Please contact a company certified in the disposal of electronic scrap for environmentally
safe recycling and disposal of your device.
Place of this Document in the Information Environment
Table 1 Place of the Text Display User Manual in the Information Environment
Product Family Documentation Order Number
SIMATIC Text Display (TD) User Manual (resides on
the STEP 7-Micro/WIN documentation CD)
Not applicable S7-200
Simplified Chinese Character Set (resides on the
STEP 7-Micro/WIN documentation CD)
Not applicable
S7-200 S7-200 Programmable Controller System Manual 6ES7 298-8FA24-8BH0
Preface
Text Display (TD) User Manual
4 System Manual, 08/2008, A5E00765548-03
Finding Your Way
If you are a first-time (novice) user of TD devices, you should read the entire SIMATIC Text
Display (TD) User Manual. If you are an experienced user, refer to the table of contents or
index to find specific information.
The SIMATIC Text Display User Manual is organized according to the following topics:
Chapter 1 (Product Overview) provides an overview of the TD devices
Chapter 2 (Installing Your TD Device) provides installation instructions and guidelines.
Chapter 3 (Using the Keypad Designer to Create a Custom Faceplate for Your TD
Device) provides information about the Keypad Designer and the steps required for
configuring the keypad and faceplate for the TD devices that can be customized..
Chapter 4 (Using the Text Display Wizard to Configure the S7-200 CPU for Your TD
Device) provides information about using the Text Display wizard of STEP 7-Micro/WIN to
configure the S7-200 CPU for the TD device.
Chapter 5 (Operating Your TD Device) provides information about the basic operation of
the TD devices and also describes the features and capabilities.
Appendix A (Technical Specifications and Reference Information) provides the technical
information for the TD devices and also provides references for the character sets
supported.
Appendix B (Connecting Multiple Devices on a Network) provides information about using
a TD device in a network with other TD devices and S7-200 CPUs.
Appendix C (Troubleshooting) provides information to help you diagnose problems with
the TD device.
The Simplified Chinese Character Set shows the characters supported by the TD devices.
This file is an electronic file and resides on the STEP 7-Micro/WIN documentation CD.
Approvals
Agency Approvals
The SIMATIC Text Display (TD) devices meet the standards and regulations of the following
agencies.
Underwriters Laboratories, Inc. (UL): UL 60950 for the TD 200C and TD 200; and UL
508, UL 1604 for the TD 100C and TD400C
Canadian Standards Association: CSA C22.2 No. 60950 standard for the TD 200C and
TD 200; and CS22.2 No. 142 standard and CSA-213 for the TD 100C and TD400C
Refer to Appendix A for additional compliance information.
Preface
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 5
Certification
The SIMATIC Text Display devices have the following certifications:
Underwriters Laboratories (UL)
TD 200C and TD 200: Standards UL 60950 and CSA C22.2 No. 60950
TD 100C and TD400C: Standards UL 508 and CS22.2 No. 142; UL 1604 and CSA-
213
Factory Mutual Research: Standard Class Number 3611, Class I, Division 2, Group A, B,
C, D, and Class I, Zone 2, Group IIC.
Temperature class T5 is adhered to when the ambient temperature during operation does
not exceed 50 degrees C.
CE Labeling
The SIMATIC TD devices fulfil the requirements and protection guidelines of the following
EU directive:
EC Directive 2004/108/EC "EMC directive" (TD 100C, TD 200, TD 200C and TD400C)
C-Tick
The SIMATIC devices are compliant with requirements of the following standards.
AS/NZS CISPR22 (TD 100C, TD 200, TD 200C)
AS/NZS CISPR11 (TD400C)
Services and Support
Additional Support
Local Siemens Sales Office or Distributor: For assistance in answering any technical
questions, for training on the S7-200 products, or for ordering S7-200 products, contact your
Siemens distributor or sales office. Because your sales representatives are technically
trained and have the most specific knowledge about your operations, process and industry,
as well as about the individual Siemens products that you are using, they can provide the
fastest and most efficient answers to any problems that you might encounter.
Preface
Text Display (TD) User Manual
6 System Manual, 08/2008, A5E00765548-03
Service and Support on the Internet
In addition to our documentation, we offer our Know-How online on the internet at:
http://www.siemens.com/automation/service&support
where you will find the following:
Access the S7-200 Internet site to find additional S7-200 product information:
www.siemens.com/S7-200
This site includes frequently asked questions (FAQs), Programming Tips (application
examples and sample programs), information about newly released products, and
product updates or downloads
Read the newsletter, which constantly provides you with up-to-date information on your
products
Use the Search feature of the Service & Support area to find specific documentation
Share information and exchange experiences with a forum of other users and experts
from all over the world
Find your local Siemens representative for Automation & Drives
Use the "Services" link to find information on field service, repairs, spare parts and more
Contact Information and Additional Support
Service and support from your local Siemens sales office or distributor
For assistance in answering any technical questions, for training on a specific product, or for
ordering any SIMATIC products, contact your Siemens distributor or sales office. Because
the sales representatives are technically trained and have specific knowledge about your
operations, process and industry, as well as about the individual Siemens products that you
are using, they can provide the fastest and most efficient answers to any problems that you
might encounter.
Preface
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 7
Technical services
The highly trained staff of the SIMATIC Customer Support center is also available to help
you resolve any problems that you might encounter. Their services are available world-wide
24 hours a day, 7 days a week.
%HLMLQJ
1XUHPEHUJ
-RKQVRQ&LW\71
Figure 1 World-Wide SIMATIC Customer Support
Table 2 Contact Information for SIMATIC Customer Support
United States: Johnson City, TN World-wide: Nuremberg Asia and Australia: Beijing
Technical Support
24 hours a day, 365 days a year
Telephone: +49 (180) 5050-222
Fax: +49 (180) 5050-223
Mail to:
ad.support@siemens.com
GMT: +1:00
Technical Support and Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Telephone: +1 (423) 262-2522
or +1 (800) 333-7421 (USA only)
Fax: +1 (423) 262-2289
Mail to:
techsupport.sea@siemens.com
GMT: -5:00 Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Telephone: +49 (180) 5050-222
Fax: +49 (180) 5050-223
Mail to:
ad.support@siemens.com
GMT: +1:00
Technical Support and Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Telephone: +86 10 64 75 75 75
Fax: +86 10 64 74 74 74
Mail to:
ad.support.asia@siemens.com
GMT: +8:00
The languages for the SIMATIC hotlines and the Authorization hotline are generally German and English.
Preface
Text Display (TD) User Manual
8 System Manual, 08/2008, A5E00765548-03
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 9
Table of contents
Preface ...................................................................................................................................................... 3
1 Product Overview .................................................................................................................................... 13
1.1 Overview ......................................................................................................................................13
1.2 Introducing the S7-200 Text Display (TD) Device .......................................................................13
1.3 Features of the Text Display (TD) Devices..................................................................................16
1.4 Comparing the TD Devices..........................................................................................................18
1.5 Using the TD Device to Access Screens and Alarms..................................................................19
1.6 Installation and Configuration Tasks............................................................................................22
1.7 Creating a Custom Faceplate for the TD Device.........................................................................27
1.8 Printing the Custom Faceplate for the TD device........................................................................28
2 Installing your Text Display (TD) Device.................................................................................................. 31
2.1 Overview ......................................................................................................................................31
2.2 Components Shipped with the TD Devices .................................................................................31
2.3 Mounting the TD 200, TD 200C, and TD400C in a Panel or on a Surface .................................33
2.4 Mounting the TD 100C in a Panel or on a Surface......................................................................35
2.5 Customizing the Labels for the Keys of the TD 200 ....................................................................36
2.6 Installing a Faceplate for the TD 100C, TD 200C and TD400C ..................................................38
2.7 Connecting the TD/CPU Cable....................................................................................................41
2.8 Supplying Power for the TD Device.............................................................................................42
2.9 Establishing a Connection for Your TD Device............................................................................43
3 Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device ............... 45
3.1 Overview ......................................................................................................................................45
3.2 Using the Keypad Designer with Other Applications ...................................................................45
3.3 Starting the Keypad Designer......................................................................................................48
3.4 Adding Buttons to the Keypad .....................................................................................................50
3.5 Defining the Properties of the Button...........................................................................................52
3.6 Exporting the Keypad Layout to a Graphics Application .............................................................55
3.7 Adding a Panel Image to the Faceplate.......................................................................................56
3.8 Saving the Keypad to a TD Configuration File.............................................................................58
3.9 Reversing the Panel Image..........................................................................................................59
3.10 Printing the Panel Image on a Faceplate.....................................................................................60
Table of contents
Text Display (TD) User Manual
10 System Manual, 08/2008, A5E00765548-03
3.11 Installing the Printed Faceplate onto the TD device ................................................................... 64
4 Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device............ 67
4.1 Overview ..................................................................................................................................... 67
4.2 Overview of the Configuration Tasks.......................................................................................... 67
4.3 Configuring the Text Display Device........................................................................................... 70
4.4 Configuring the Screens for the Text Display Device ................................................................. 79
4.5 Configuring the Alarms................................................................................................................ 87
4.6 Configuring the Language Sets (TD 200, TD 200C, and TD400C)............................................ 95
4.7 Assigning the V Memory Address for the Parameter Block........................................................ 98
4.8 Finishing the Configuration for the TD Device ............................................................................ 98
5 Operating Your Text Display (TD) Device.............................................................................................. 101
5.1 Overview ................................................................................................................................... 101
5.2 Using the Text Display Device to Access Screens and Alarms................................................ 101
5.3 Accessing the Menus and Screens........................................................................................... 106
5.4 Entering and Releasing a Password......................................................................................... 109
5.5 Viewing the Screens and the Alarms........................................................................................ 110
5.6 Performing Typical or Routine Operator Tasks......................................................................... 119
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu) .......................................... 124
A Technical Specifications and Reference Information ............................................................................. 133
A.1 General Specifications for the Text Display Devices................................................................ 133
A.2 Technical Specifications for the TD 100C, TD 200 and TD 200C ............................................ 133
A.3 Technical Specifications for the TD400C.................................................................................. 136
A.4 Certificates, Directives and Declarations for the TD Device..................................................... 137
A.5 Approvals for USA, Canada and Australia................................................................................ 139
A.6 Standard TD Character Set (TD 200, TD 200C)....................................................................... 141
A.7 Arabic Character Set (TD 200, TD 200C, and TD400C) .......................................................... 144
A.8 Baltic Character Set .................................................................................................................. 145
A.9 Simplified Chinese Character Set............................................................................................. 146
A.10 Cyrillic Character Set ................................................................................................................ 148
A.11 Greek Character Set ................................................................................................................. 149
A.12 Hebrew Character Set (TD 200, TD 200C, and TD400C) ........................................................ 150
A.13 Latin 1 Character Set ................................................................................................................ 151
A.14 Latin 2 Character Set ................................................................................................................ 152
A.15 Turkish (Latin 5) Character Set................................................................................................. 153
Table of contents
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 11
B Connecting Multiple Devices on a Network............................................................................................ 155
B.1 Overview ....................................................................................................................................155
B.2 Communicating with Multiple CPUs...........................................................................................155
B.3 Determining the Distances, Transmission Rate, and Cable......................................................156
B.4 Selecting the Network Cable......................................................................................................157
B.5 Biasing and Terminating the Network Cable .............................................................................157
B.6 Building a TD/CPU Cable ..........................................................................................................158
B.7 CPU Grounding and Circuit Reference Point Guidelines for Using Isolated Circuits................160
C Troubleshooting..................................................................................................................................... 163
C.1 Troubleshooting Guide...............................................................................................................163
Index...................................................................................................................................................... 165
Table of contents
Text Display (TD) User Manual
12 System Manual, 08/2008, A5E00765548-03
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 13
Product Overview 1
1.1 Overview
Product Overview
The S7-200 TD devices provide a low-cost human-machine interface (HMI), allowing an
operator or user to interact with your application.
The TD devices allow you to configure a set of hierarchical user menus to provide additional
structure for the interaction with your application. You can also configure the TD device to
display alarms or messages that are enabled by specific bits in the S7-200 CPU.
Tip
The TD devices provide additional functionality, such as the hierarchical user-defined
menus. The TD 200C and the TD 200 are fully compatible with projects that were created
with earlier versions of the TD 200 (prior to TD 200 V3.0, which supported only the bit-
enabled messages from the S7-200 CPU).
You can use the TD 200C or the TD 200 device with an existing TD configuration without
having to modify the control program in the S7-200 CPU.
The TD 100C and the TD400C devices are not compatible with the TD 200 devices.
1.2 Introducing the S7-200 Text Display (TD) Device
Introducing the S7-200 Text Display (TD) Devices
Your S7-200 TD device is a 2- or 4-line text display device that can be connected to the
S7-200 CPU. The TD device allows you to view, monitor, and change the process variables
pertaining to your application.
The S7-200 product family provides four TD devices:
TD 100C: The TD 100C has a 4-line text display with 2 font choices. Your display can
have 16 characters per line for a total of 64 characters, or you can use a bold font with 12
characters per line for a total of 48 characters. The faceplate of the TD 100C offers
complete flexibility of the keypad layout and faceplate design.
You can create a custom keypad with up to 14 buttons (keys) of variable size, with
varying shapes, colors, or fonts that can be layered onto any background image.
TD 200C: The TD 200C has a 2-line text display with 20 characters per line for a total of
40 characters. The faceplate of the TD 200C offers complete flexibility of the keypad
layout and faceplate design.
You can create a custom keypad with up to 20 buttons (keys) of variable size, with
varying shapes, colors, or fonts that can be layered onto any background image.
Product Overview
1.2 Introducing the S7-200 Text Display (TD) Device
Text Display (TD) User Manual
14 System Manual, 08/2008, A5E00765548-03
TD 200: The faceplate of the TD 200 provides four keys with predefined, set-bit functions
and allows up to eight set-bit functions by using the SHIFT key.
TD400C: The TD400C can have a 2- or 4-line text display depending on your font and
character choice.The TD400C buttons (keys) are tactile and have fixed positions.
Your display can have a 4-line display with 12 small Chinese characters per line for a
total of 48 characters, or 24 small ASCII characters per line for a total of 96
characters.
Your display can have a 2-line display with 8 large Chinese characters per line for a
total of 16 characters, or 16 large ASCII characters per line for a total of 32 characters.
You can create a custom keypad with up to 15 buttons (keys) of varying colors,
functions, or fonts that can be layered onto any background image.
7'&
7'
7'&
7'&
Figure 1-1 Text Display (TD) Devices
The TD devices receive power from the S7-200 CPU through the TD/CPU cable. The
TD 200, TD 200C and TD400C devices can also receive power from a separate power
supply.
Product Overview
1.2 Introducing the S7-200 Text Display (TD) Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 15
The TD devices contain the following elements:
Text display area: The TD 200C, TD 200 and TD400C have a backlit liquid crystal display
(LCD).
The TD 200C and TD 200 displays have a resolution of 33 x 181 pixels
The TD400C display has a resolution of 192 x 64 pixels.
The TD 100C has a liquid crystal display (LCD) with a resolution of 132 x 65 pixels.
There is no backlight on the TD 100C.
Communication port: 9-pin D-connector
Power connector
The TD 200C, TD 200, and TD400C have a connector for using an optional external
power supply (power for the TD device is typically supplied by the S7-200 CPU
through the TD/CPU cable).
The TD 100C does not have the option of using an external power supply.
STEP 7-Micro/WIN provides tools to help you configure the TD devices. Using the following
tools, you can easily program your S7-200 to display text messages and other data:
Text Display wizard helps you configure messages for the TD devices.
Keypad Designer helps you to configure the custom keypad for the TD 100C, the
TD 200C, and the TD400C. The Keypad Designer includes samples and templates in the
following directories:
Sample bitmaps for buttons and backgrounds:
C:/Program Files/Siemens/TD Keypad Designer/Images
Sample projects:
C:/Program Files/Siemens/TD Keypad Designer/Samples
Sample template (for printing multiple copies of the faceplate):
C:/Program Files/Siemens/TD Keypad Designer/Templates
Each TD device functions as a network master when it is connected over a network that
contains one or more S7-200 CPUs. The TD device is also designed to operate with other
masters in a network. Multiple TD devices can be used with one or more S7-200 CPUs
connected to the same network. More than one TD device can connect to the same S7-200
CPU.
Product Overview
1.3 Features of the Text Display (TD) Devices
Text Display (TD) User Manual
16 System Manual, 08/2008, A5E00765548-03
1.3 Features of the Text Display (TD) Devices
Features of the Text Display (TD) Devices
You can use your TD device to perform the following tasks:
Viewing a hierarchy of user menus and screens that allow an operator to interact with the
application or process
You create these user menus and screens with the Text Display wizard of
STEP 7-Micro/WIN
Displaying alarms (bit-enabled messages) that are generated by the S7-200 CPU
You define these alarms with the Text Display wizard of STEP 7-Micro/WIN
Modifying designated program variables
The TD device allows you to define a variable as either a text string or a numeric string:
Text string: All characters in a variable are editable
Numeric string: Only the numeric characters are editable (the cursor skips over all
non-numeric characters)
The TD device allows you to define a variable as a word, double word, or real
Forcing or unforcing I/O points: You can force individual I/O points in the S7-200 CPU to
be on or off (TD 200C, TD 200, and TD400C only)
Setting the time and date (if the S7-200 CPU supports a real-time clock)
Viewing the CPU status (including version information)
The TD 200C and TD400C provide additional functionality for interacting with the S7-200
CPU:
You can change the operating mode (RUN or STOP) of the S7-200 CPU
You can load the user program in the S7-200 CPU to a memory cartridge
You can access and edit the data stored in the memory of the S7-200 CPU
International Languages and Characters Support
The TD 200C and TD 200 devices provide a default TD character set which supports bar
graph characters. The TD devices (as noted) support the following Windows character sets
for displaying messages:
Arabic
Baltic
Chinese (Simplified Chinese)1
Cyrillic
Greek
Hebrew
Latin 1 (with Boldface)
Product Overview
1.3 Features of the Text Display (TD) Devices
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 17
Latin 2 (with Boldface)
Turkish (Latin 5)
The TD devices provide system menus and prompts in six languages: English, German,
French, Spanish, Italian, and Simplified Chinese.
In the TD 100C, all fonts except Simplified Chinese are available in two sizes: 12 and 16
characters per row. All the 12 character fonts are bold.
The TD400C supports the character sets in two sizes.
Table 1- 1 Fonts Supported by the TD Devices
TD 100C TD 200 TD 200C TD400C V 2.0
Latin 1 Latin 1 Latin 1 Latin 1
- Latin 1 Bold Latin 1 Bold Latin 1 Bold
Latin 2 Latin 2 Latin 2 Latin 2
- Latin 2 Bold Latin 2 Latin 2 Bold
Cyrillic Cyrillic Cyrillic Cyrillic
Greek Greek Greek Greek
Turkish Turkish Turkish Turkish
Baltic Rim Baltic Rim Baltic Rim Baltic Rim
- Arabic Arabic Arabic
- Hebrew Hebrew Hebrew
- Original TD 200 Original TD 200 -
- Bar Graph Bar Graph -
Simplified Chinese1 Simplified Chinese Simplified Chinese Simplified Chinese
1 The TD 100C includes approximately 1900 out of the possible 6763 Chinese characters.
Product Overview
1.4 Comparing the TD Devices
Text Display (TD) User Manual
18 System Manual, 08/2008, A5E00765548-03
1.4 Comparing the TD Devices
Comparing the Text Display Devices
Table 1- 2 Comparing the TD Devices
Feature TD 100C V 1.0 TD 200 V3.0 TD 200C V 1.0 TD400C V 2.0
Text display area 4 lines, up to 64
characters (up to 16
characters per line)
2 lines, up to 40
characters (up to 20
characters per line)
2 lines, up to 40
characters (up to 20
characters per line)
2 lines with large font,
up to 16 Chinese or 32
ASCII characters per
line (up to 8 Chinese
or 16 ASCII characters
per line)
4 lines with small font,
up to 24 ASCII
characters (up to 12
Chinese characters
per line)
Display backlight can
be configured to
extend the life of the
TD400C device
Keypad options User-designed custom
keypad
Standard keypad
Standard keypad User-designed custom
keypad
Standard keypad
User designed custom
keypad
Standard keypad
Configurable buttons Custom keypad: Up to
14 (user-configurable)
Standard keypad: 2
Standard keypad: 4
(Up to 8 when using
SHIFT)
Custom keypad: Up to
20 (user-configurable)
Standard keypad: 4
(up to 8 when using
SHIFT)
Custom keypad: Up to
15 (user configurable)
Standard keypad: 8
(up to 16 when using
SHIFT)
System buttons
(pre-configured)
ENTER, ESC
(Escape), UP, DOWN,
LEFT and RIGHT
arrows, F1, F2
ENTER, ESC
(Escape), SHIFT, UP
and DOWN arrows
ENTER, ESC
(Escape), SHIFT, UP,
DOWN, LEFT, and
RIGHT arrows
ENTER, ESC
(Escape), SHIFT, UP,
DOWN, LEFT, and
RIGHT arrows
User-defined menus
and user screens
Maximum of 32
screens
Up to 4 user menus,
with up to 8 screens
per user menu
Maximum of 64
screens
Up to 8 user menus,
with up to 8 screens
per user menu
Maximum of 64
screens
Up to 8 user menus
with up to 8 screens
per user menu
Maximum of 64
screens
Up to 8 user menus
with up to 8 screens
per user menu
Alarms (from the
S7-200 CPU)
Up to 40 alarm
messages
Up to 80 alarm
messages
Up to 80 alarm
messages
Up to 80 alarm
messages
Alarm indicator (icon) Yes Yes Yes Yes
Variable embedded in
an alarm or screen
1 per line
(1 for one-line alarms;
2 for two-line alarms, 4
for a screen)
Up to 6 variables per
alarm or screen
Up to 6 variables per
alarm or screen
Up to 6 variables per
alarm or screen
Icons (graphics)
embedded in a
message
No No Yes Yes
Product Overview
1.5 Using the TD Device to Access Screens and Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 19
Feature TD 100C V 1.0 TD 200 V3.0 TD 200C V 1.0 TD400C V 2.0
System menu options Release the password
Set the time and date
CPU status
Clean keypad
Force I/O
Release the password
Set the time and date
CPU status
Switch languages (if
configured)
Clean keypad
Force I/O
Release the password
Set the time and date
CPU status
Switch languages (if
configured)
Change the CPU
operating mode
Clean keypad
Edit the CPU memory
Program a memory
cartridge
Force I/O
Release the password
Set the time and date
CPU status
Switch language (if
configured)
Change the CPU
operating mode
Clean keypad
Edit the CPU memory
Program a memory
cartridge
Password protection Yes Yes Yes Yes
Multiple language sets No Yes Yes Yes
Character sets
supported (for
displaying different
languages)
7 character sets:
Latin 1, Latin 2,
Chinese (Simplified)1,
Cyrillic, Baltic, Greek,
Turkish
10 character sets:
Latin 1/Bold, Latin
2/Bold, Chinese
(Simplified), Cyrillic,
Arabic, Baltic, Greek,
Hebrew, Turkish, and
Standard TD (includes
Bar Graph)
10 character sets:
Latin 1/Bold, Latin
2/Bold, Chinese
(Simplified), Cyrillic,
Arabic, Baltic, Greek,
Hebrew, Turkish, and
Standard TD (includes
Bar Graph)
9 characters sets:
Latin 1/Bold, Latin
2/Bold, Chinese
(Simplified), Cyrillic,
Arabic, Baltic, Greek,
Hebrew, Turkish
Languages for system
menus and error
messages
6 languages:
English, French,
German, Italian,
Spanish, and Chinese
6 languages:
English, French,
German, Italian,
Spanish, and Chinese
6 languages:
English, French,
German, Italian,
Spanish, and Chinese
6 languages: English,
French, German,
Italian, Spanish, and
Chinese
Feedback (when
pressing a button)
Visual indicator in the
text display area
Tactile dome over the
buttons on the keypad
and visual indicator
Visual indicator in the
text display area
Tactile dome over the
buttons on the keypad,
visual indicator, and
audio feedback
1 The TD 100C includes approximately 1900 out of the possible 6763 Chinese characters..
1.5 Using the TD Device to Access Screens and Alarms
Using the TD Device to Access Screens and Alarms
When you configure the TD device with the Text Display wizard of STEP 7-Micro/WIN, you
create the screens and alarms for the TD device. You use the buttons on the keypad of the
TD device to navigate through the screens and menus. The TD 200 device uses the
standard TD keypad. The standard faceplates for the TD devices are shown in Figure 1-2.
The TD 100C and TD 200C allow you to create your own custom-designed buttons with
specialized functions.
Product Overview
1.5 Using the TD Device to Access Screens and Alarms
Text Display (TD) User Manual
20 System Manual, 08/2008, A5E00765548-03
7'&
0
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
6WDQGDUG)DFHSODWH7'&
)
)
)
)
)
)
)
)
)
)
)
)
)
)
6+,)7
(6&
(17(5
6+,)7(17(5DQG(6&
)
)
6,(0(16
)
) )
) )
) )
)
6+,)7 (17(5
(6&
6WDQGDUG)DFHSODWH7'&
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
DQG6+,)7
(17(5
DQG(6&
6WDQGDUG)DFHSODWH7'&
6,(0(16
7'&
) )
(17(5
(6&
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV (17(5
DQG(6&
6,(0(16
6,(0(16
)
) )
) )
) )
)
6+,)7 (17(5
(6&
6WDQGDUG)DFHSODWH7'
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
DQG6+,)7
(17(5
DQG(6&
Figure 1-2 Standard Keypad Configuration for the TD Devices
Dividing Information into Screens and Bit-Enabled Alarms
As shown in Figure 1-3, you can configure the TD device to display screens (which are
initiated by operator action) and bit-enabled alarms (which are initiated by the S7-200 CPU).
Screens: You can create screens that allow the operator (using the TD device) to initiate
the interaction with the S7-200 CPU. With the TD device, you can configure a user menu
(up to 8 entries or groups for the TD 200C, TD 200, and TD400C, and up to 4 entries or
groups for the TD 100C) that provides a hierarchy for the screens. You can create up to 8
screens for each menu item or group.
Alarms: You can create alarm messages that allow the user program in the S7-200 CPU
to initiate interaction with the operator by displaying a message on the TD device.
During the configuration of the TD device, you also designate which type of message
(screens or alarms) will be the default display mode for the TD device. After power-up, the
TD device goes to the default display mode. Also, the TD device returns to the default
display mode after a period of inactivity (if no buttons have been pressed for one minute).
Product Overview
1.5 Using the TD Device to Access Screens and Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 21
Storing the Screens and Alarms in the Parameter Block
The S7-200 CPU stores the text, embedded variables, and format information for the alarms
and screens in a parameter block located in V memory. You use the Text Display wizard to
configure the starting address for the parameter block in V memory, and the Text Display
wizard allocates the memory required to store the information for the TD device.
If you configure more than one parameter block for the S7-200 CPU (with each parameter
block having a different range of addresses in V memory), you can connect several TD
devices to that one S7-200 CPU. You configure the V memory address for the specific
parameter block for each of the TD devices. The Diagnostic Menu of the TD device provides
a TD Setup command for specifying the starting address of the parameter block.
Tip
The parameter block for the TD 100C and the TD400C is not compatible with other TD
devices. The TD 100C parameter block is only compatible with a TD 100C parameter block,
and the TD400C parameter block is only compatible with a TD400C parameter block.
Displaying the Screens and Alarms on the TD Device
When the operator uses the buttons on the TD device to select a screen, the TD device
reads the screen information from the parameter block (stored in V memory of the S7-200
CPU) and displays the appropriate screen.
When you configure an alarm, you also configure an alarm bit for enabling a specific alarm.
The logic of your user program sets this alarm bit to display the alarm on the TD device.
When you create the text for the alarm, you also designate the alarm bit. If you configured an
alarm to require acknowledgement by an operator, that alarm also has an acknowledge bit.
The TD device continuously polls the alarm bits to determine which alarms have been
enabled.
To display an alarm on the TD device, your user program in the S7-200 CPU must first set
the alarm bit for the specific alarm. When your user program sets one of the alarm bits, the
TD device then reads the alarm bits in the parameter block in the S7-200 CPU and displays
the corresponding alarm message.
Product Overview
1.6 Installation and Configuration Tasks
Text Display (TD) User Manual
22 System Manual, 08/2008, A5E00765548-03
  
SVL SVL
6&38
$ODUPVDUHVRUWHGE\WKHVHTXHQWLDOSULRULW\WKDW
\RXFUHDWHGZLWKWKH7H[W'LVSOD\ZL]DUG
Ⴠ 7KHILUVWDODUPWKDW\RXFRQILJXUDWHGLVWKH
KLJKHVWSULRULW\
Ⴠ 7KHODVWDODUPWKDW\RXFRQILJXUHGLVWKH
ORZHVWSULRULW\
5HIHUWR&KDSWHUVDQGIRULQIRUPDWLRQDERXW
DODUPV
8VHU0HQX 6FUHHQV
&KDQJH
6L]H
+HLJKW /HQJWK :LGWK
&KDQJH
3UHVVXUH
0D[LPXP 0LQLPXP
7''HYLFH
$ODUPV
3UHVVXUH+LJK
&KHFN6SHHG
&DOLEUDWH6L]H
Figure 1-3 Screens and Alarms
1.6 Installation and Configuration Tasks
Installation and Configuration Tasks
As shown in Figure 1-4, you use the Text Display wizard of STEP 7-Micro/WIN to configure
the TD device. You can create a custom faceplate for the TD 100C, TD 200C, and TD400C.
The Keypad Designer creates a keypad configuration file for the Text Display wizard.
An overview of the tasks for installing your TD device is shown in the figures below. Refer to
Chapter 2.
Product Overview
1.6 Installation and Configuration Tasks
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 23
.H\SDG'HVLJQHU
6DYHWKHNH\SDGFRQILJXUDWLRQ
ILOHWGWGRUWG
67(30LFUR:,1
7H[W'LVSOD\:L]DUG
Ⴠ
&UHDWHWKHVFUHHQVDQGWKH
DODUPVIRU\RXURSHUDWRULQWHUIDFH
Ⴠ
&RQILJXUHWKHSDUDPHWHUEORFN
IRUWKH7'GHYLFH9PHPRU\LQ
WKH6&38
3DUDPHWHU%ORFN
:KHQ\RXGRZQORDG\RXUXVHUSURJUDPWKH
6&38VWRUHVWKHSDUDPHWHUEORFNLQ
WKH9PHPRU\DGGUHVV\RXVHOHFWHG
6&38
/DVHU3ULQWHU
3ULQWWKHIDFHSODWHIRUWKH7'GHYLFH
7' 7'& 7'& 7'&
Figure 1-4 Configuration Tasks for the TD Devices
Product Overview
1.6 Installation and Configuration Tasks
Text Display (TD) User Manual
24 System Manual, 08/2008, A5E00765548-03
7' 7'&
5HPRYHWKH
+RXVLQJ
2SWLRQDO
0RGLI\WKH
/DEHO,QVHUW
,QVHUWWKH
6SDFHUVDQG
0RXQWWKH7'
'HYLFH
5HPRYHWKH
+RXVLQJ
,QVHUWWKH
6SDFHUVDQG
0RXQWWKH7'
'HYLFH
7RFRQQHFW\RXU7'GHYLFHWRDQHWZRUNXVHWKH'LDJQRVWLF0HQXRI
WKH7'GHYLFHWRVHWXSWKHQHWZRUNDGGUHVVHVEDXGUDWHDQGRWKHU
SDUDPHWHUV
5HIHUWR&KDSWHU
([WHUQDO3RZHU
6XSSO\RSWLRQDO
([WHUQDO3RZHU
6XSSO\RSWLRQDO
,QVWDOOWKH
IDFHSODWH
&RQQHFWWRWKH
6&38 &RQQHFWWRWKH
6&38
7R6&38 7R6&38
6SDFHUV
6SDFHUV
/DEHO,QVHUW
0RXQWLQJ6FUHZV
0RXQWLQJ6FUHZV
7'6HWXS
9LHZ0HVVDJHV
Figure 1-5 Installing Your TD 200 and TD 200C Device
Product Overview
1.6 Installation and Configuration Tasks
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 25
7RFRQQHFW\RXU7'GHYLFHWRDQHWZRUNXVHWKH'LDJQRVWLF0HQXRI
WKH7'GHYLFHWRVHWXSWKHQHWZRUNDGGUHVVHVEDXGUDWHDQGRWKHU
SDUDPHWHUV
5HIHUWR&KDSWHU
7'6HWXS
9LHZ0HVVDJHV
7'&
5HPRYHWKH
+RXVLQJ
,QVHUWWKH
6SDFHUVDQG
0RXQWWKH7'
'HYLFH
([WHUQDO3RZHU
6XSSO\RSWLRQDO
,QVWDOOWKH
IDFHSODWH
&RQQHFWWRWKH
6&38
7R6&38
6SDFHUV
Figure 1-6 Installing Your TD400C Device
Product Overview
1.6 Installation and Configuration Tasks
Text Display (TD) User Manual
26 System Manual, 08/2008, A5E00765548-03
7'&
,QVWDOOWKH
IDFHSODWH
&OLSRQWKH
PRXQWLQJ
EUDFNHWV
7LJKWHQWKH
VFUHZVWR
VHFXUHWKH7'
WRWKHSDQHO
0RXQWLQJ
6FUHZV
0RXQWLQJEUDFNHW
7R6&38
&RQQHFWWRWKH
6&38
7RFRQQHFW\RXU7'&GHYLFHWRDQHWZRUNXVHWKH7'6HWXS
0HQXRIWKH7'&GHYLFHWRVHWXSWKHQHWZRUNDGGUHVVHVEDXG
UDWHDQGRWKHUSDUDPHWHUV5HIHUWR&KDSWHU
0RXQWLQJEUDFNHW
7'6HWXS
Figure 1-7 Installing Your TD 100C Device
Product Overview
1.7 Creating a Custom Faceplate for the TD Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 27
1.7 Creating a Custom Faceplate for the TD Device
Creating a Custom Faceplate for the TD Device
With the TD device, you can design a custom faceplate that can be layered onto any
background image. The TD 100C and the TD 200C lets you incorporate buttons (keys) of
varying size, with varying shapes, colors or fonts. The TD400C lets you incorporate buttons
(keys) of varying colors and fonts. The positions and size of the TD400C buttons (keys) are
fixed.
As shown in Figure 1-7, you use several applications to create a custom faceplate:
Keypad Designer: Creates the layout and the configuration for the keypad
Third-party graphics application: Designs the graphical appearance of the faceplate
STEP 7-Micro/WIN (Text Display wizard): Configures the parameter block for the
TD 100C, TD 200C, and the TD400C
Word-processing application (optional): Prints multiple copies of the faceplate
Siemens provides document files (in 6 languages) for Microsoft Word that help you to
align the panel images for the perforations on the A4 blank faceplate material. To open
these documents, browse to the Templates subdirectory under the Keypad Designer
application (C:/Program Files/Siemens/TD Keypad Designer/Templates) and select the
template for your TD device and language.
:RUG3URFHVVLQJ
$SSOLFDWLRQ
2SWLRQDO
3ULQWWKHIDFHSODWHRQWRWKHEODQN
ODEHOPDWHULDO
.H\SDG'HVLJQHU
Ⴠ &UHDWHWKHOD\RXWRIWKHEXWWRQV
Ⴠ &RQILJXUHWKHIXQFWLRQDOLW\IRU
HDFKEXWWRQ
Ⴠ $GGDQLPDJHIRUWKHNH\SDG
SDQHO
Ⴠ 3ULQWWKHIDFHSODWHIRUWKH7'
GHYLFH
Ⴠ &UHDWHWKHNH\SDGFRQILJXUDWLRQ
ILOHWGIRU7'&WGIRU
7'&RUWGIRU7'&
67(30LFUR:,1
7H[W'LVSOD\:L]DUG
&RQILJXUHWKH7'
GHYLFH
*UDSKLFV
$SSOLFDWLRQ
7KLUG3DUW\
Figure 1-8 Using the Keypad Designer and Other Applications to Create a Custom Faceplate
Product Overview
1.8 Printing the Custom Faceplate for the TD device
Text Display (TD) User Manual
28 System Manual, 08/2008, A5E00765548-03
1.8 Printing the Custom Faceplate for the TD device
Printing the Custom Faceplate for the TD Device
The TD 100C and the TD 200C ship with one blank faceplate (envelope-size) for printing the
faceplate. The faceplate is constructed from durable, polyester material which has been
designed especially for use on HMI faceplates.
The TD400C does not include a blank faceplate. You can either order blank faceplates, or
use the Keypad Designer to print a TD400C custom faceplate on A4 paper and take it to a
local supplier to make a custom TD400C faceplate.
You can print a single faceplate directly from the Keypad Designer on the envelope-sized
blank faceplate.
To print multiple faceplates, you can use the Microsoft Word template (provided in the
Templates subdirectory) that ensures your faceplate design is properly sized. You can
print multiple faceplates onto the perforated A4-size blank faceplate sheets.
Refer to Chapter 3 for specific information about printing the custom faceplate for your TD
device.
Tip:
The faceplate material is specially treated on one side to accommodate printing with a laser
printer. The treated surface is up (or toward you) when you are holding the material with the
cut corner in the top right of the sheet.
Ensure that the material is correctly inserted into the laser printer so that the faceplate prints
the reversed image onto the treated surface of the material. You must print a reversed-image
version of the faceplate onto the faceplate material.
Before printing your custom faceplate onto the blank faceplate sheet, first test your design by
printing the faceplate onto regular paper. You can then temporarily use the paper faceplate
to test the functionality of the design with your TD device.
Printer Requirements
To print your custom-designed image onto the blank faceplate material, you must use a laser
printer that supports the following features:
Paper size: The laser printer must be able to print on both the A4 (210 mm X 297 mm)
and envelope formats.
Color: The laser printer must support color printing.
Transparencies: The laser printer must support the printing of transparencies (or other
non-paper stock)
Ordering Additional Faceplate Material
You can order additional blank faceplates for the TD 100C, TD 200C, and TD400C device in
perforated A4-size sheets (10 sheets/package). The faceplate material is especially
designed for printing on a laser printer. The blank faceplate sheets also allow you to utilize
the services of professional printing vendors that specialize in laser printing in order to create
large quantities of high-quality faceplates.
Product Overview
1.8 Printing the Custom Faceplate for the TD device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 29
Contact your local Siemens representative or distributor to purchase additional quantities of
the faceplate material. The order numbers are shown below:
TD 200C: the order number for additional blank faceplates is 6ES7 272-1AF00-7AA0
TD 100C: the order number for additional blank faceplates is 6ES7 272-1BF00-7AA0
TD400C: the order number for additional blank faceplates is 6AV6671-0AP00-0AX0
Product Overview
1.8 Printing the Custom Faceplate for the TD device
Text Display (TD) User Manual
30 System Manual, 08/2008, A5E00765548-03
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 31
Installing your Text Display (TD) Device 2
2.1 Overview
Installing your TD Device
You can install your TD device for easy access, whether on a panel or on a door of an
enclosure.
Installed properly, the TD devices meet the following standards (as noted) for protection.
IP 65 (mounted on front of the panel)
IP 20 (mounted on casing)
UL 50 Type 4X
Refer to Appendix A for technical specification and for information about agency approvals
and other certifications.
Tip
You can use the TD 200, version 3.0 and the TD 200C, version 1.0 with an existing TD 200
configuration without having to modify the control program in the S7-200 CPU. The TD 100C
and the TD400C are not compatible with the TD 200 devices, nor with each other.
2.2 Components Shipped with the TD Devices
Components Shipped with the TD Devices
The TD devices ship with the following components:
Gasket: Protective cushion with gasket for installing the TD device in inclement
environments
TD/CPU cable: 9-pin, straight-through cable that provides both communication and power
to the TD device. The TD 200, TD 200C, and TD400C ship with a TD/CPU cable. The
TD 100C does not include a TD/CPU cable; it must be ordered separately. The order
number for the TD/CPU cable is 6ES7-901-3EB10-0XA0.
Spacers: Self-adhesive spacers for mounting the TD device in a panel (TD 200,
TD 200C, and TD400C only)
Mounting brackets: Brackets for mounting the TD device in a panel (TD 100C only)
Power connector: The TD 200, TD 200C, and the TD400C ship with a connector to power
the TD device from an external supply.
The TD 200 ships with a pull-out user label that allows you to label the function keys for your
application.
Installing your Text Display (TD) Device
2.2 Components Shipped with the TD Devices
Text Display (TD) User Manual
32 System Manual, 08/2008, A5E00765548-03
The TD 100C and TD 200C ship with a blank faceplate that you can customize. The
TD 100C, TD 200C and TD400C ship with a pre-printed faceplate for the standard TD
keypad. The faceplate is constructed from durable, polyester material which has been
designed specifically for use for HMI faceplates.
Tip
To print your custom-designed image onto the blank faceplate material, you must use a laser
printer that supports the printing of transparencies on both A4 and envelope formats and
also supports color printing.
General TD Installation Information
Tip
To ensure compliance with IP 65 or UL 50 Type 4X:
The minimum panel thickness must be at least 1.5 mm.
For the TD 200, TD 200C, and TD400C, the mounting screws must be tightened to a
torque of 0.7 N-m.
For the TD 100C, the mounting screws must be tightened to a torque of 0.2 Nm (about
0.5 mm the height of the seal).
The gasket must be replaced whenever the TD device is removed and reinstalled.
To procure new gaskets, contact your Siemens distributor or sales representative.
The TD 100C, TD 200, TD 200C, and TD400C devices are suitable for use in Class I,
Division 2, Groups A, B, C, D; Class I, Zone 2, Group IIC; or non-hazardous locations.
WARNING
WARNING - EXPLOSION HAZARD!
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS LOCATION IS KNOWN TO BE
NON-HAZARDOUS
WARNING
WARNING - EXPLOSION HAZARD!
Substitution of components may impair suitability for Class I, Division 2 or Zone 2.
Installing your Text Display (TD) Device
2.3 Mounting the TD 200, TD 200C, and TD400C in a Panel or on a Surface
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 33
2.3 Mounting the TD 200, TD 200C, and TD400C in a Panel or on a
Surface
Mounting the TD 200, TD 200C, and TD400C in a Panel or on a Surface
Tip
If you are using a customized label insert for your TD device, you must first install the new
label insert before you mount the TD device.
Preparing the Mounting Surface for a TD 200, TD 200C, or TD400C
To prepare the surface where the TD device is to be mounted or installed, use the
dimensions for your TD device as shown below:
For a TD 200 and TD 200C, cut a 138 mm x 68 mm hole in the mounting surface (DIN
43700).
For a TD400C, cut a 163.5 mm x 93.5 mm hole in the mounting surface
Refer to Table A-1 for the outside dimensions of your TD device.
163.5mm
93.5 mm
138 mm
68 mm
TD 200, TD 200C TD400C
Figure 2-1 Dimensions for cutting a Hole in the Mounting Surface of the TD 200, TD 200C,and
TD400C
Installing your Text Display (TD) Device
2.3 Mounting the TD 200, TD 200C, and TD400C in a Panel or on a Surface
Text Display (TD) User Manual
34 System Manual, 08/2008, A5E00765548-03
Preparing the TD 200, TD 200C, and TD400C for Mounting
Refer to the figure below and use the following procedure to separate the front cover from
the housing of your TD device:
1. For the TD 200 and TD 200C, use a flat-head screwdriver or a T8 Torx screwdriver to
remove the three screws from the rear of the device. For the TD400C, use a cross
screwdriver for M3 to remove the four screws from the rear of the device.
2. Remove the front cover of the TD device from the housing.
7'7'&
0RXQWLQJ6FUHZV 7'&
0RXQWLQJ6FUHZV
Figure 2-2 Removing the Mounting Screws of the TD device
Positioning the Spacers for the TD 200, TD 200C, and TD400C
The self-adhesive spacers included with the TD 200, TD 200C, and TD400C maintain the
pressure on the TD device circuit board when the TD device is assembled. The number of
spacers required is dependant upon the thickness of the mounting surface.
Refer to Figure 2-3 and use the following procedure to position the spacers:
1. Determine the number of spacers required, based on the thickness of the panel:
For up to 1.5 mm, use one spacer.
For 1.5 mm to 4.0 mm, use two spacers.
2. Place the spacers over the screw holes on the inside of the backplate.
*DVNHW
*DVNHW
)URQW&RYHU
6SDFHUV
%DFNSODWH
0RXQWLQJ6FUHZV
&DELQHW'RRURU&RQWURO3DQHO
Figure 2-3 Positioning Spacers on the TD Device
Installing your Text Display (TD) Device
2.4 Mounting the TD 100C in a Panel or on a Surface
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 35
Mounting the TD 200, TD 200C, and the TD400C
Refer to Figure 2-3 and use the following procedure to complete the mounting of your TD
device:
1. Remove the gasket from the protective cushion.
2. Place the supplied gasket on the frontplate of the TD device.
3. Install the spacers (if required).
4. Fit the frontplate into the cutout you made in the mounting surface.
5. Secure the backplate onto the frontplate of the TD device using the screws you removed
from the backplate. Carefully tighten the screws until snug.
2.4 Mounting the TD 100C in a Panel or on a Surface
Mounting the TD 100C in a Panel or on a Surface
Preparing the Mounting Surface for a TD 100C
To prepare the surface where the TD 100C is to be mounted or installed:
Cut a 69 mm x 82 mm hole in the mounting surface (DIN 43700)
Refer to Table A-1 for the outside dimensions of the TD 100C device.
69 mm
82mm
Figure 2-4 Dimensions for Cutting a Hole in the Mounting Surface of the TD 100C
Installing your Text Display (TD) Device
2.5 Customizing the Labels for the Keys of the TD 200
Text Display (TD) User Manual
36 System Manual, 08/2008, A5E00765548-03
Mounting the TD 100C
Use the following procedure to complete the mounting of your TD 100. See figure below.
1. Remove the gasket from the protective cushion.
2. Place the supplied gasket on the frontplate of the TD device.
3. Fit the TD 100C into the cutout you made in the mounting surface.
4. Attach the special mounting brackets (included) to the TD 100C.
5. Tighten the mounting screws on the mounting brackets to secure the TD 100C to the
panel.
0RXQWLQJEUDFNHW
0RXQWLQJ
6FUHZV
&DELQHW'RRURU&RQWURO3DQHO
0RXQWLQJEUDFNHW
Figure 2-5 Mounting the TD 100C
2.5 Customizing the Labels for the Keys of the TD 200
Customizing the Labels for the Keys of the TD Device
The TD 200 allows you to define the functions for four of the nine keys (or buttons) on the
standard faceplate. You can remove the label insert of the TD 200 and designate the
functions assigned to those user-defined keys. You can also replace the standard TD 200
insert with your own custom insert for the user-defined keys.
You must remove (at least partially) the TD housing in order to access the label insert from
underneath the front cover of the TD device.
Modifying the Label Insert of the TD 200
1. Remove the three screws on the back of the TD device and remove the front cover from
the housing.
2. Remove the label insert by pulling the label insert tab out of the label slot with a pair of
pointed tweezers.
3. Turn the label insert over and create your own label design. (The reverse side of the label
insert is blank.)
4. Insert the label by placing the corner of the label into the label slot.
Installing your Text Display (TD) Device
2.5 Customizing the Labels for the Keys of the TD 200
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 37
5. Reinstall the front cover into the back housing.
6. Replace and tighten the three screws on the back of the TD device to ensure that the
cover and housing are secure.
7DERIODEHOLQVHUW
8VHWZHH]HUVWRJUDVSWKHWDERIWKHODEHOLQVHUW
Figure 2-6 Removing the Label Insert
Creating a Custom Label Insert for the TD 200
The dimensions for creating your own custom label insert are shown in the figure below.
These dimensions are valid for TD 200, hardware revision 3 and later.
PP
PP PP
PP PP
PP PP PP
PPPP
PP PP
PP
PP
PP
PP
PP
PP
PP
PP
PP PP
PP
PP
PP
PP
0DWHULDOWKLFNQHVVPP
:LQGRZRQWKHIDFHSODWHWKDWDOORZV
\RXWRDGGWH[WIRU\RXU7'
Figure 2-7 Dimensions for a Custom Label Insert
Installing your Text Display (TD) Device
2.6 Installing a Faceplate for the TD 100C, TD 200C and TD400C
Text Display (TD) User Manual
38 System Manual, 08/2008, A5E00765548-03
2.6 Installing a Faceplate for the TD 100C, TD 200C and TD400C
Installing a Faceplate for the TD 100C, TD 200C, and TD400C
The TD 100C and TD 200C ship with a blank faceplate (envelope size) for creating a
custom-designed faceplate. The TD400C does not ship with a blank faceplate; you can order
a package with blank faceplates (see appendix A for order information).
The TD devices do not ship with the faceplate attached. The front of the TD is an adhesive
surface (shipped with a protective paper) that allows you to attach your custom faceplate.
Refer to Chapter 3 for information about designing and printing a custom faceplate.
The figure below shows the dimensions for the faceplate of the TD devices. Blank faceplate
material for the TD 100C, TD 200C and TD400C is available in the sizes shown below.
Envelope size for printing a single faceplate (TD 100C, TD 200C only)
A4 size (210 mm x 297 mm) for printing multiple copies of the faceplate (TD 100C, TD
200C, and TD400C)
You must cut the faceplate from the envelope-sized material, but the A4 material is
perforated to allow you to remove the faceplates without cutting.
Use the following procedure to install your custom faceplate on the TD device. The example
shown here is for the TD 200C. Installing a faceplate on a TD 100C and TD400C is similar;
the differences are noted below. To prepare for installation, remove the protective film
covering the display window of the TD device and the back of the preprinted (standard)
faceplate. The protective film is blue for the TD 100C and the TD 200C, and is transparent
for the TD400C.
1. The dimensions for the custom faceplate are shown for the TD device.
2. If your TD device has a strip of protective paper, remove the strip to expose the strip of
the adhesive. For the TD 200C and the TD400C, it is on the left side of the device. For
the TD 100C, it is on the right side of the device.
3. Carefully align your custom faceplate on the entire TD device, and then seal the faceplate
to the exposed adhesive by pressing down on the left (TD 200C and TD400C) or on the
right (TD 100C) side of the faceplate.
Installing your Text Display (TD) Device
2.6 Installing a Faceplate for the TD 100C, TD 200C and TD400C
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 39
4. Carefully lift back the unadhered faceplate and remove the rest of the protective paper
from the TD device.
5. Carefully position the faceplate onto the TD device. Firmly press the faceplate onto the
adhesive, taking care to remove any air bubbles that may have been trapped underneath.
NOTICE
Do not use excessive force when you install the faceplate onto the TD400C device.
If you use excessive force in pressing the faceplate onto the TD400C device, it may
cause damage to the springs under the faceplate.
Ensure that excessive force is not used when you install the faceplate onto the device.
Installing your Text Display (TD) Device
2.6 Installing a Faceplate for the TD 100C, TD 200C and TD400C
Text Display (TD) User Manual
40 System Manual, 08/2008, A5E00765548-03
PP7'&
PP7'&
PP7'&
PP7'&
7'&DQG7'&
PP
7'&
PP 1
&XVWRP)DFHSODWH
2
3
4
5
'LPHQVLRQVIRUWKH7'&XVWRP)DFHSODWH
Figure 2-8 Installing a Custom Faceplate on a TD Device
Installing your Text Display (TD) Device
2.7 Connecting the TD/CPU Cable
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 41
The standard TD faceplates are shown in Figure 1-2. The TD 200C comes configured as a
standard TD 200 (with LEFT and RIGHT arrows). The TD 100C comes configured with six
standard keys (UP, DOWN, LEFT and RIGHT arrows, ESC, and ENTER). The TD400C
comes configured with seven standard keys (UP, DOWN, LEFT, RIGHT, ESCAPE, ENTER,
and SHIFT).
After creating and installing the custom faceplate on your TD device you must also download
the TD configuration that you created with both the Keypad Designer and the Text Display
wizard.
Chapter 3 describes the Keypad Designer
Chapter 4 describes the Text Display wizard
2.7 Connecting the TD/CPU Cable
Connecting the TD/CPU Cable
NOTICE
Operating the TD device with an ungrounded voltage source can damage the TD device.
The TD device may only be connected to grounded voltage sources. Non-grounded
operation can cause the TD device to become damaged.
Always ensure that the voltage source for the TD device is properly grounded.
The TD devices can use the TD/CPU cable for communicating with the S7-200 CPU.
You can connect the TD device directly to the S7-200 CPU, creating a one-to-one
network configuration. In this configuration, one TD device connects to one S7-200 CPU
through the TD/CPU cable.
You can connect multiple TD devices to multiple S7-200 CPUs over a network. The TD
device defaults to address 1 and attempts to communicate to a CPU at address 2.
For more information about connecting to multiple CPUs, see Appendix B. For information
about changing the default addresses in the TD device, see Chapter 5.
If you require a longer cable (>2.5 m) to connect the TD device to the S7-200 CPU, use
PROFIBUS components for the network connection. Refer to the SINEC IK10 Catalog.
Installing your Text Display (TD) Device
2.8 Supplying Power for the TD Device
Text Display (TD) User Manual
42 System Manual, 08/2008, A5E00765548-03
2.8 Supplying Power for the TD Device
Supplying Power for the TD Device
The S7-200 CPU uses the TD/CPU cable to provide power to the TD device. Use this type of
power supply when the distance between the TD device and the S7-200 CPU is less than
2.5 m (the length of the TD/CPU cable). The TD 200, TD 200C and the TD400C have the
option of using an external power supply.
Tip
The TD 100C device must use the TD/CPU cable to provide power from the S7-200 CPU to
the TD device. The TD 100C does not have the option of using an external power supply.
Tip
If the distance between the TD 200, TD 200C or TD400C and the S7-200 CPU is greater
than 2.5 m, use an external 24 VDC power supply.
If you require a longer cable (greater than 2.5 m) to connect the TD device to the S7-200
CPU, use PROFIBUS components for the network connection. Refer to the SINEC IK10
Catalog.
Refer to Appendix B for information about using the TD device on a network.
As shown in the figure below, the TD device provides up to two options for providing power:
The TD/CPU cable allows the S7-200 CPU to provide power to the TD device over the
communications port. This is the only option available for the TD 100C.
For information about the TD/CPU cable and the communications port, refer to
Appendix B.
You can connect the TD 200, TD 200C or the TD400C to an external power supply.
The TD 200, TD 200C or TD400C requires 120 mA at 24 VDC to operate. An optional
power connector is provided with the TD 200, TD 200C and the TD400C.
9'&
9
&RPPXQLFDWLRQVSRUW
&RQQHFWRUIRUDQH[WHUQDOSRZHUVXSSO\
Figure 2-9 Connecting Power to the TD Device (TD 200, TD 200C, and TD400C)
Installing your Text Display (TD) Device
2.9 Establishing a Connection for Your TD Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 43
2.9 Establishing a Connection for Your TD Device
Establishing a Connection for Your TD Device
As described in Chapter 4, you use the Text Display wizard of STEP 7-Micro/WIN to
configure the screens, alarms, languages, and custom keypad layout for the TD 100C,
TD 200C and the TD400C. The S7-200 CPU stores this information in a parameter block (V
memory).
The TD devices ship with a default configuration and are set to communicate at a rate of
9600 baud. The TD devices must communicate with the S7-200 CPU to be able to read the
parameter block.
You must configure your TD device to communicate at the same baud rate as your S7-200
CPU.
TD 100C, TD 200C, and TD400C
Until the TD device successfully connects to the S7-200 CPU and reads the parameter
block, the TD device remains configured for the standard TD keypad shown in the figure
below.
To change the baud rate of your TD device, you use the ESC and ENTER buttons to
navigate to the Diagnostic/TD Setup Menu and change the TD Setup parameters. (See
Chapter 5.) Because the TD devices ship with no faceplate attached, it may be difficult to
consistently press ESC or ENTER.
The TD 100C, TD 200C, and TD400C devices ship with a faceplate for the standard TD
keypad. In addition, the Keypad Designer provides a sample faceplate for the standard TD
keypad in the following directory.
C:/Program Files/Siemens/ TD Keypad Designer/Templates
For temporary use, you can print this faceplate onto paper and lay the paper on top of the
TD device (without removing the covering from the adhesive).
Refer to Chapter 3 for information about opening the Keypad Designer and printing a
faceplate.
Installing your Text Display (TD) Device
2.9 Establishing a Connection for Your TD Device
Text Display (TD) User Manual
44 System Manual, 08/2008, A5E00765548-03
6,(0(16
)
) )
) )
) )
)
6+,)7 (17(5
(6&
6WDQGDUG)DFHSODWH7'&
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
DQG6+,)7
(17(5
DQG(6&
6WDQGDUG)DFHSODWH7'&
6,(0(16
7'&
) ) (17(5
(6&
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV (17(5
DQG(6&
7'&
0
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
6WDQGDUG)DFHSODWH7'&
)
)
)
)
)
)
)
)
)
)
)
)
)
)
6+,)7
(6&
(17(5
6+,)7(17(5DQG(6&
)
)
6,(0(16
Figure 2-10 Standard TD Keypad for the TD 100C, TD 200C and TD400C
Tip
On an initial setup for the TD 100C, TD 200C, or TD400C, use the default keypad template
shipped with the device to configure baud rates and addresses. Once the TD device has
communicated to the CPU, the TD device will use the custom keypad configuration.
Tip
If you are using a custom keypad that does not support the ENTER and ESC buttons, you
must use the standard keypad to set up the TD device.
To restore the standard TD keypad:
1. Power down the TD device
2. Press and hold the lower right corner (where ENTER key is located on the standard
keypad)
3. Power up the TD device
The default keypad is restored until the TD device is power cycled again.
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 45
Using the Keypad Designer to Create a Custom
Faceplate for your Text Display (TD) Device 3
3.1 Overview
Overview of Chapter 3
With the TD 100C, TD 200C, and the TD400C, you can design a custom keypad that
incorporates buttons (keys) of varying size, with varying shapes, colors, or fonts that can be
layered onto any background image. You can configure up to 14 buttons on the TD 100C, up
to 20 buttons on the TD 200C, and up to 15 buttons on the TD400C.
The Keypad Designer application allows you to create a custom-designed layout for the
keypad of the TD 100C, TD 200C, and TD400C, and also includes samples and templates in
the following directories:
Sample bitmaps for buttons and backgrounds:
C:/Program Files/Siemens/TD Keypad Designer/Images
Sample projects:
C:/Program Files/Siemens/TD Keypad Designer/Samples
Templates (for printing multiple copies of the faceplate):
C:/Program Files/Siemens/TD Keypad Designer/Templates
This chapter guides you through the tasks required for creating the layout for the keypad,
creating the configuration file for the keypad, and printing the faceplate for the TD 100C,
TD 200C, and the TD400C.
You use the configuration file when you are configuring the TD 100C, the TD 200C and the
TD400C with the Text Display wizard of STEP 7-Micro/WIN. Refer to Chapter 4 for
information about the Text Display wizard.
TIP
For more information about creating a custom faceplate, refer to FAQ 23707064 on the
Siemens Internet site at www.siemens.com/S7-200.
3.2 Using the Keypad Designer with Other Applications
Using the Keypad Designer with Other Applications
Use the Keypad Designer to create the custom-designed layout for the keypad.
The TD 100C and the TD 200C lets you incorporate buttons (keys) of varying size, with
varying shapes, colors or fonts. The TD400C lets you incorporate buttons (keys) of varying
colors and fonts. The positions and size of the TD400C buttons (keys) are fixed.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.2 Using the Keypad Designer with Other Applications
Text Display (TD) User Manual
46 System Manual, 08/2008, A5E00765548-03
You can configure up to 20 buttons on the TD 200C; up to 14 buttons on the TD 100C; and
up to 15 buttons on the TD400C. As shown in the figure below, you use several applications
to create a custom keypad:
Keypad Designer: Creates the layout and the configuration for the keypad
Third-party graphics application: Designs the graphical appearance of the faceplate
STEP 7-Micro/WIN (Text Display wizard): Configures the parameter block for the TD
device
Word-processing application (optional): Prints multiple copies of the faceplate
Siemens provides document files (in up to 6 languages depending upon your TD device) for
Microsoft Word that helps you to align the panel images for the perforations on the A4 blank
faceplate material. To open these documents, browse to the Templates subdirectory under
the Keypad Designer application (C:/Program Files/Siemens/TD Keypad
Designer/Templates) and select the template for your TD device and language.
.H\SDG'HVLJQHU
Ⴠ &UHDWHWKHOD\RXWRIWKHEXWWRQV
Ⴠ &RQILJXUHWKHIXQFWLRQDOLW\IRU
HDFKEXWWRQ
Ⴠ $GGDQLPDJHIRUWKHNH\SDG
SDQHO
Ⴠ 3ULQWWKHIDFHSODWHIRUWKH7'
GHYLFH
Ⴠ &UHDWHWKHNH\SDGFRQILJXUDWLRQ
ILOHWGWGRUWG
67(30LFUR:,1
7H[W'LVSOD\:L]DUG
&RQILJXUHWKH
SDUDPHWHUEORFNIRU
WKH7'GHYLFH
*UDSKLFV
$SSOLFDWLRQ
7KLUG3DUW\
:RUG3URFHVVLQJ
$SSOLFDWLRQ
2SWLRQDO
3ULQWWKHIDFHSODWHRQWRWKH
EODQNODEHOPDWHULDO
Figure 3-1 Using the Keypad Designer to Create the Custom Faceplate for Your TD Device
As shown in the figure below, you perform the following tasks when designing a custom
keypad:
You use the Keypad Designer to define the layout and the functions for the buttons.
You export the button template to a third-party graphics application. You then create the
panel image by designing the graphical representations for the buttons and the
background for the faceplate.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.2 Using the Keypad Designer with Other Applications
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 47
After you import the panel image into the Keypad Designer, you print the faceplate for the
TD device.
You use the Keypad Designer to create the configuration file (*.td2 for the TD 200C, *.td1
for the TD 100C, or *.td4 for the TD400C).
6DYHWKHNH\SDGFRQILJXUDWLRQ
ILOHWGWGRUWG
67(30LFUR:,1
7H[W'LVSOD\:L]DUG
.H\SDG'HVLJQHU
&UHDWHWKHOD\RXWIRUWKHNH\SDG
Ⴠ$GGWKHEXWWRQVWRWKHNH\SDGJULG
Ⴠ$GMXVWWKHVL]HDQGORFDWLRQRIWKH
EXWWRQV
&RQILJXUHWKHIXQFWLRQDOLW\IRUWKH
EXWWRQV
&UHDWHWKHSDQHOLPDJHIRUWKH
NH\SDG
Ⴠ([SRUWWKHEXWWRQWHPSODWHWRD
WKLUGSDUW\JUDSKLFVDSSOLFDWLRQ
Ⴠ,PSRUWWKHFRPSOHWHGSDQHO
LPDJHWRWKH.H\SDG'HVLJQHU
3ULQWWKHFRPSOHWHGIDFHSODWH
Ⴠ6LQJOHFRSLHVFDQEHSULQWHG
IURPWKH.H\SDG'HVLJQHU
Ⴠ8VHDZRUGSURFHVVLQJ
DSSOLFDWLRQ([SRUWWKHSDQHO
LPDJHWRDILOH
7KLUG3DUW\
*UDSKLFV$SSOLFDWLRQ
'HVLJQWKHJUDSKLFVIRUWKH
IDFHSODWH
Ⴠ'HVLJQWKHEDFNJURXQGIRU
WKHSDQHOLPDJH
Ⴠ'HVLJQWKHEXWWRQLPDJHV
Ⴠ$GGWH[WIRUWKHEXWWRQV
Ⴠ6DYHWKHILOHDVDELWPDS
EPS
:RUG3URFHVVLQJ$SSOLFDWLRQ
2SWLRQDO
3ULQWWKHIDFHSODWHRQWRWKH
EODQNIDFHSODWHPDWHULDO
Ⴠ8VHWKHWHPSODWHIRU
0LFURVRIW:RUGRSWLRQDO
Ⴠ6HWXSWKHSULQWHUIRUWKH
FRUUHFWSDSHUVL]H
Ⴠ3ULQWWKHIDFHSODWH
/DVHU3ULQWHU
6HOHFWNH\SDGFRQILJXUDWLRQILOHWG
WGRUWGZKHQFRQILJXULQJWKH7'
GHYLFHZLWK7H[W'LVSOD\:L]DUG
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
Figure 3-2 Tasks for Creating a Custom Faceplate
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.3 Starting the Keypad Designer
Text Display (TD) User Manual
48 System Manual, 08/2008, A5E00765548-03
3.3 Starting the Keypad Designer
Starting the Keypad Designer
You use the Keypad Designer application to create a custom-designed layout for the keypad
of the TD 100C, the TD 200C, or the TD400C.
When you install STEP 7-Micro/WIN, you also install the Keypad Designer application. The
Keypad Designer does not require STEP 7-Micro/WIN.
You can start the Keypad Designer either from within STEP 7-Micro/WIN or as a stand-alone
application:
To start as a stand-alone application: Select the Start > SIMATIC > TD Keypad Designer
menu command
To start from STEP 7-Micro/WIN: Click the Keypad Designer icon in the Tools window
The Keypad Designer application opens with a blank keypad template. The TD 200C and the
TD400C templates are shown in the figures below.. Select File > New to create a new
keypad layout for either the TD 100C, the TD 200C, or the TD400C. In the Keypad Designer
Type dialog, select the keypad type.
To open an existing project, select the File > Open menu command and browse to the
project.
Figure 3-3 TD 200C Keypad Template
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.3 Starting the Keypad Designer
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 49
Figure 3-4 TD400C Keypad Template
If you open a file with different target (for example, you are working on a TD 200C file, and
you open a TD 100C file), the panel workspace resizes for the new target. Since the
application is sized based on the panel workspace, you may have to resize and re-position
your application framework.
Table 3-1 describes the files that are used by the Keypad Designer.
You can change the language of the Keypad Designer by selecting the Tools > Options
menu command. You select the language from the Options dialog shown below.
Figure 3-5 Options Dialog
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.4 Adding Buttons to the Keypad
Text Display (TD) User Manual
50 System Manual, 08/2008, A5E00765548-03
Table 3- 1 Files Used by the Keypad Designer
File Type Extension Description
TD file
Open, Save,
Save As
*.td2 (TD 200C)
*.td1 (TD 100C)
*.td4 (TD400C)
Create the Keypad project file that stores the
configuration data for the custom-designed keypad
(used by the Text Display wizard)
Button Template
Export
*.bmp Export the layout of the buttons on the keypad to a
graphics application by selecting a file
Panel Image
Import
*.bmp Import the finished bitmap of the faceplate from the
graphics application by selecting a file
Panel Image
Export (Optional)
*.bmp Export the finished faceplate to a word-processing
application for printing multiple copies of the faceplate
3.4 Adding Buttons to the Keypad
Adding Buttons to the Keypad
The TD 100C and the TD 200C allow you relative freedom when designing your keypad.
With the TD400C, the position and size of the buttons are fixed. You cannot add, remove, or
change the TD400C buttons.
On the TD keypad you can configure up to 20 buttons for the TD 200C, up to 14 buttons for
the TD 100C, and up to 15 buttons for the TD400C.
You can vary the size and the location of the buttons (TD 100C and TD 200C only)
You can define the functionality for each button.
The Keypad Designer provides a grid that aligns the location of the buttons with the physical
keypad of the TD device.
ᅛ
.H\SDG'HVLJQHU
&UHDWHWKHOD\RXWIRUWKHNH\SDG
Ⴠ$GGWKHEXWWRQVWRWKHNH\SDGJULG
Ⴠ$GMXVWWKHVL]HDQGORFDWLRQRIWKH
EXWWRQV
Figure 3-6 Adding the Button to the TD 100C and TD 200C Keypad
Tip
Typically, your keypad design should always include buttons with the following functions:
Enter, Escape, Up Arrow, and Down Arrow. These functions allow you to access the pre-
configured menus and functions of the TD device.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.4 Adding Buttons to the Keypad
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 51
Inserting a Button
With the TD 100C and the TD 200C, you can add a button to the keypad grid. The TD400C
does not have this option.
1. Click the Draw Button icon.
2. Move the cursor over the grid.
3. Move the cursor (and button) into position on the keypad grid.
4. Hold down the left mouse button and drag the cursor to adjust the size and shape of the
button.
5. Release the mouse button to insert the button onto the keypad
After you have inserted the button onto the keypad grid, you can relocate the button by
dragging it to a new location on the grid. However, you cannot resize the button.
Figure 3-7 Adding a Button (TD 100C and TD 200C)
Modifying the Shape of a Button
With the TD 100C and the TD 200C you can modify the shape of a button. The Keypad
Designer provides two methods for modifying the shape of a button. The TD400C does not
have this option.
Changing the size or shape of a button by adding a second button on top of the first
button
Erasing a portion of the button
Extending the Shape of a Button
You cannot resize a button that has been inserted onto the keypad grid. However, with the
TD 100C and the TD 200C, you can insert a second button on top of the first button to create
a new size for the button. The TD400C does not have this option.
As shown in the figure below, adding a second button also allows you to create buttons of
non-rectangular shape (combining the shapes of both buttons).
When you insert the second button, ensure that the cursor is within the boundaries of the
first button.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.5 Defining the Properties of the Button
Text Display (TD) User Manual
52 System Manual, 08/2008, A5E00765548-03
Figure 3-8 Extending the Shape of a Button (TD 100C and TD 200C)
Erasing an Area of the Button
With the TD 100C and the TD 200C, you can change the shape of the button by clicking the
Erase Button icon. The TD400C does not have this option.
As shown in the figure below, the Keypad Designer alerts you if the shape of the button is
invalid.
To delete the entire button, select the button and press the Delete key.
Figure 3-9 Erasing an Area of a button (TD 100C and TD 200C)
Tip
A valid button must consist of at least 4 adjacent cells, with each cell having at least 2
neighbor cells. A neighbor cell must be left, right, or up or down from the cell. Diagonal
neighbor cells are not counted.
3.5 Defining the Properties of the Button
Defining the Properties of the Button
After you create the button, you define the function that will be performed when an operator
presses the button.
You use the Properties dialog to configure the functionality for the button:
Select the button to be configured.
Select the Edit > Properties menu command to display the Properties dialog.
You can also right-click the button and select Properties from the context menu. You can
double-click the button to bring up the Set Button Properties.
Select the function for the button and provide a valid function name. Click OK. See
Figure 3-10 for an example of the TD 200C button functions.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.5 Defining the Properties of the Button
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 53
The TD400C has up to 15 buttons that can be defined. You do not have to define (or use) all
the buttons. Some buttons can be blank or unused.
Table 3-2 describes the functions that you can configure for the button. The default function
is to set a bit in the S7-200 CPU (Set PLC Bit).
Some functions can also be used in combination with other buttons, such as SHIFT or the
arrow buttons. The Properties dialog provides suggestions for appropriate buttons for
combining the functions.
After you configure the functions for each button on the keypad, select the File > Save or the
File > Save As menu command to create the configuration file (*.td2 for the TD 200C, *.td1
for the TD 100C, or *.td4 for the TD400C).
Tip
A button that has been configured will display the button name on the button in the panel
layout.
.H\SDG'HVLJQHU
&RQILJXUHWKHIXQFWLRQDOLW\IRUWKH
EXWWRQV
ᅛ
Figure 3-10 Defining the Properties for the Button
Figure 3-11 Button Properties Dialog
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.5 Defining the Properties of the Button
Text Display (TD) User Manual
54 System Manual, 08/2008, A5E00765548-03
Table 3- 2 Button Properties for the TD 100C, TD 200C, and TD400C
Category Function Description
Enter Selects a menu item or confirms a value
Escape Exits from a menu or cancels a selection
Up Arrow Scrolls (upwards) through menu items or increments a value that can be
edited
Down Arrow Scrolls (downwards) through menu items or decrements a value that can
be edited
Left Arrow Moves the cursor to the left
Navigation or Selection
Right Arrow Moves the cursor to the right
Set Bit Sets a memory bit in the S7-200 CPU. You use the Text Display wizard to
assign the specific bit address
For the TD 200C and TD400C, you can use this button to set two different
bits by defining the Shift button
Shift Allows you to use one Set PLC Bit button to control two different bits in
the S7-200 CPU (TD 200C, TD400C)
Clear Value Sets the value being entered to zero (0)
Entering data
Edit V-Memory Edits a V memory location in the S7-200 CPU. You must specify the
address for the V memory at run time (TD 200C, TD400C)
Menu Mode Displays the standard TD menus (See Chapter 5)
Display Alarm Displays the current alarm message(s)
Display User
Menus
Displays the user menu
Menu 1 Screen 0 Displays the first user screen in the first user menu
Menu 2 Screen 0 Displays the first user screen in the second user menu
Menu 3 Screen 0 Displays the first user screen in the third user menu
Menu 4 Screen 0 Displays the first user screen in the fourth user menu
Menu 5 Screen 0 Displays the first user screen in the fifth user menu (TD 200C, TD400C)
Menu 6 Screen 0 Displays the first user screen in the sixth user menu
(TD 200C, TD400C)
Menu 7 Screen 0 Displays the first user screen in the seventh user menu
(TD 200C, TD400C))
User Screens and Alarms
(User menu or Alarms
menu)
See Chapters 4 and 5
Menu 8 Screen 0 Displays the first user screen in the eighth user menu (TD 200C,
TD400C))
CPU Status Displays the View CPU Status screen
Reads and displays the status of the S7-200
Select Language
Set
Displays the Set Language screen, allowing you to switch between the
languages that you configured for the TD 200C, TD400C)
Setting up the TD 200C
(Operator menu)
See Chapter 5
Set PLC Time and
Date
Displays the Set Time and Date screen, allowing you to enter the time
and date
Change PLC
Mode
Displays the Change CPU Mode screen, allowing you to change the
operating mode of the S7-200 (TD 200C, TD400C)
Edit Memory Displays the Edit CPU Memory screen (TD 200C, TD400C)
Force I/O Displays the Force I/O screen (TD 200C, TD400C)
Program Memory
Cartridge
Displays the Make MC screen, allowing you to copy the user program to
the memory cartridge (TD 200C, TD400C)
Diagnostics
(Diagnostic Menu)
See Chapter 5
TD Setup Displays the TD Setup screen
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.6 Exporting the Keypad Layout to a Graphics Application
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 55
Category Function Description
View Messages Displays the View Messages screen (TD 200C, TD400C)
Password
See Chapter 5
Release Password Allows you to immediately restore the password-protection for the TD
device
No Function No Function Allows you to identify a button as "not used"
3.6 Exporting the Keypad Layout to a Graphics Application
Exporting the Keypad Layout to a Graphics Application
After you have configured the buttons on the keypad, you can create the graphical
representation for the faceplate. You can use any third-party graphics application to add
colors, lines and other artwork to the panel design.
The Keypad Designer exports the layout of the buttons as a bitmap file (*.bmp) that you edit
with the graphics application.
As shown in the figure below, the button template provides a bitmap image of the layout of
the keypad that you can use with your graphical application to position, size and align the
graphical elements of your faceplate design. These elements can include logotype, text, or
other images.
The Keypad Designer allows you to export the layout of the buttons into your graphics
application. Use the File > Export >Button Template to File menu command to create a
bitmap file (*.bmp) that you insert into the graphics application.
After you customize the layout (adding background image, colors, buttons or logotype), you
save the file as a bitmap (*.bmp). This bitmap becomes the panel image for the Keypad
Designer.
ᅛ
ᅛ
([SRUWWKHEXWWRQWHPSODWHOD\RXW
IRUWKHNH\SDGWRDWKLUGSDUW\
JUDSKLFVDSSOLFDWLRQ
7KLUG3DUW\
*UDSKLFV$SSOLFDWLRQ
.H\SDG'HVLJQHU
'HVLJQWKHJUDSKLFVIRUWKH
IDFHSODWH
Ⴠ'HVLJQWKHEDFNJURXQGIRUWKH
SDQHOLPDJH
Ⴠ'HVLJQWKHEXWWRQLPDJHV
Ⴠ$GGWH[WIRUWKHEXWWRQV
Figure 3-12 Creating the Panel Image: Export Button Layout
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.7 Adding a Panel Image to the Faceplate
Text Display (TD) User Manual
56 System Manual, 08/2008, A5E00765548-03
Tip
When you design the colors for your panel image, be aware that any white area will be
printed as transparent (clear).
.H\SDG/D\RXW
LQWKH.H\SDG'HVLJQHU
%XWWRQ7HPSODWH
H[SRUWHGWRDJUDSKLFV
DSSOLFDWLRQ
Figure 3-13 Exporting the Button Template to a Graphics Application
3.7 Adding a Panel Image to the Faceplate
Adding a Panel Image to the Faceplate
Using your own graphics application, you create the following graphical elements for the
faceplate of the TD 100C, TD 200C, or the TD400C:
Button images
Background image or color scheme
Text (for the buttons or the background)
Logotypes (and other images or text)
For the TD 100C and the TD 200C, you are not required to use square buttons. However,
you must ensure that your button design covers the area of the button as defined in the
button template.
After you have used your graphics application to modify the panel image for the faceplate,
save the design as a bitmap file (*.bmp).
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.7 Adding a Panel Image to the Faceplate
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 57
ᅛ
ᅛ
,PSRUWWKHFRPSOHWHGSDQHOLPDJH
WRWKH.H\SDG'HVLJQHU
.H\SDG'HVLJQHU
7KLUG3DUW\
*UDSKLFV$SSOLFDWLRQ
6DYHWKHFRPSOHWHGSDQHOLPDJH
DVDELWPDSEPS
Figure 3-14 Creating the Panel Image: Import Panel Image
Importing a Panel Image
When you have completed the graphical design of panel image for the faceplate, you import
the panel image back into the Keypad Designer.
After you open your keypad project (*.td1, *.td2, or *.td4), use the File > Import >Panel Image
from File menu command to select the bitmap file that you created with your graphics
application.
Figure 3-15 Keypad with a Panel Image
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.8 Saving the Keypad to a TD Configuration File
Text Display (TD) User Manual
58 System Manual, 08/2008, A5E00765548-03
Tip
When you design your faceplate, you can create the bitmap with any resolution. However,
the size of the background image for the TD device must exactly match the following
dimensions:
For the TD 200C:
Width: 137 mm (+/- 0.15 mm) (5.42 inches)
Height: 65.7 mm (+/- 0.15 mm) (2.58 inches)
For the TD 100C:
Width: 79 mm ((+/- 0.1 mm) (3.11 inches)
Height: 65.8 mm (+/- 0.1 mm) (2.59 inches)
For the TD400C:
Width: 91.5 (+/- 0.1 mm) (3.6 inches)
Height: 163.5 (+/- 0.1mm) (6.44 inches)
If your faceplate design does not match these dimensions, the Keypad Designer alerts you
before importing the panel image. If you import a panel image with incorrect dimensions, the
Keypad Designer resizes your panel image, which could distort the appearance of your
faceplate design.
3.8 Saving the Keypad to a TD Configuration File
Saving the Keypad to a TD Configuration File
When you save the keypad, you create a TD configuration file (*.td1 for the TD 100C, *.td2
for the TD 200C, and *.td4 for the TD400C). This file contains the following information about
the buttons on the keypad:
Number of buttons
Location and sizes of the buttons
Names of the buttons
Functions assigned to the buttons
Panel image (if one was imported)
Use the File > Save or File > Save As menu command to save the configuration of the
keypad.
The Text Display Wizard uses this information for configuring the TD 100C, TD 200C, or
TD400C. See Chapter 4 for more information.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.9 Reversing the Panel Image
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 59
ᅛ
ᅛ 6DYHWKHNH\SDGFRQILJXUDWLRQ
ILOHWG[
.H\SDG'HVLJQHU
67(30LFR:,1
7H[W'LVSOD\:L]DUG
6HOHFWWKHNH\SDGFRQILJXUDWLRQILOH
WGWGRUWGZKHQFRQILJXULQJ
WKH7'GHYLFHZLWK7H[W'LVSOD\
Figure 3-16 Saving the TD Configuration File
Tip
The Keypad Designer allows you to save invalid or incomplete configurations. This allows
you to save interim versions of your work. However, always ensure that the final
configuration of the keypad is valid and complete before using the configuration file (*.tdx)
with the Text Display wizard.
3.9 Reversing the Panel Image
Reversing the Panel Image
The Reverse Panel Image option only affects the way that the panel image is saved to a file
using the File > Export > Panel Image to File menu command. The exported bitmap file can
then be inserted into the Microsoft Word template. For more information see the next
section, Printing the Panel Image on a Faceplate. The Reverse Panel Image option does not
change the layout of the keypad.
Printing a reversed image allows you to orient the side of the faceplate with the ink from
the printing process towards the TD device. The operator then touches only the plastic
membrane and not the ink when pressing a button. See the figure below..
Printing a non-reversed panel image allows the elements to be read correctly when
printed. Use the non-reversed panel image when you print a paper copy of the faceplate
for review. See figure below.
Use the File > Export > Reverse Panel Image menu command to select this function. A
check mark notifies you that Reverse Panel Image function is selected.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.10 Printing the Panel Image on a Faceplate
Text Display (TD) User Manual
60 System Manual, 08/2008, A5E00765548-03
Figure 3-17 Reversed Panel Image
Figure 3-18 Non-reversed Panel Image
3.10 Printing the Panel Image on a Faceplate
Printing the Panel Image on a Faceplate
To print your custom-designed panel image onto the blank faceplate material, you must use
a laser printer that supports printing transparency material in both the A4 and envelope
formats and also supports color printing.
You can print a single panel image directly from the Keypad Designer on the envelope-
sized blank faceplate (shipped with the TD 100C and TD 200C device). When you print a
single faceplate (File > Print), the panel image is always reversed.
To print multiple panel images, you can use the Microsoft Word template that ensures
your panel image design is properly sized. You can print multiple panel images onto the
perforated A4-size blank faceplate sheets. See Appendix A for order numbers.
Tip
The faceplate material is specially treated on one side to accommodate printing with a laser
printer. The treated surface is up (or toward you) when you are holding the material with the
cut corner in the top right of the sheet.
Ensure that the material is correctly inserted into the laser printer so that the panel image is
printed onto the treated surface of the material. You must print a reversed-panel image
version onto the faceplate material. To reverse the panel image, see the previous section,
Reversing the Panel Image.
Before printing your panel image onto the blank faceplate sheet, first test your design by
printing the panel image onto regular paper. You can then temporarily use the paper
faceplate to test the functionality of the design with your TD device.
Using the blank faceplate sheets also allows you to create large quantities of high-quality
faceplates by utilizing the professional printing services of shops that specialize in laser
printing.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.10 Printing the Panel Image on a Faceplate
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 61
You can order additional blank faceplates in perforated A4-size sheets (10 sheets/package)
for the TD 100C, TD 200C and TD400C. The faceplate material is especially designed for
printing with laser printers.
The blank faceplate material for the TD 100C, TD 200C and TD400C is available in the sizes
below:
Envelope size for printing a single faceplate (TD100C, TD200C): The Keypad Designer
prints registration lines for trimming the faceplate to the correct dimensions. (Use a metal
straight edge and a knife or razor blade to ensure accurate and straight cuts.) The
TD 100C and TD 200C devices ship with a single blank faceplate. The TD400C does not
include a single faceplate.
A4 size (210 mm x 297 mm) for printing multiple copies of the faceplate (TD100C,
TD200C, and TD400C): You can use the Microsoft Word template to print the faceplate
onto perforated areas of the material. You do not have to cut the faceplates from the
material. Order these A4 sheets from your Siemens distributor. See Appendix A for order
numbers.
.H\SDG'HVLJQHU
3ULQWDVLQJOHIDFHSODWHIURPWKH
.H\SDG'HVLJQHU
3ULQWPXOWLSOHIDFHSODWHVIURPD
ZRUGSURFHVVRUDSSOLFDWLRQ
Ⴠ ([SRUWWKHSDQHOLPDJH
Ⴠ 3DVWHRULQVHUWWKHSDQHOLPDJHLQWR
\RXUZRUGSURFHVVLQJDSSOLFDWLRQ
:RUG3URFHVVLQJ$SSOLFDWLRQ
2SWLRQDO
3ULQWWKHIDFHSODWHRQWRWKHEODQN
IDFHSODWHPDWHULDO
Ⴠ 8VHWKHWHPSODWHIRU0LFURVRIW
:RUGRSWLRQDO
Ⴠ 6HWXSWKHSULQWHUIRUWKHFRUUHFW
SDSHUVL]H
Ⴠ 3ULQWWKHIDFHSODWH
Figure 3-19 Printing the Faceplate
Tip
Before attempting to print a custom faceplate, ensure that both the printer and the word-
processing application are set to the correct paper size:
Single-copy sheet: Set both the printer and word-processing application to print on
Envelope.
Multiple-copy A4 sheet: Set both the printer and the word-processing application to print
on A4-size paper.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.10 Printing the Panel Image on a Faceplate
Text Display (TD) User Manual
62 System Manual, 08/2008, A5E00765548-03
Your computer and your laser printer may have other settings that cause the printer to scale
the faceplate to an incorrect size. Always first print a test copy on paper before printing your
faceplate onto the blank material.
Printing a Single Faceplate from the Keypad Designer
You can print individual faceplates directly from the Keypad Designer:
1. Ensure that the laser printer is set to print envelopes.
2. Insert the envelope-size faceplate material into the tray.
3. Select the File > Print menu command.
4. Select the laser printer and click OK.
5. Using the cut lines and a paper cutter, cut the faceplate from the material
Figure 3-20 Printing a Single Faceplate
Tip
For best results use a razor-blade cutting knife with a metal straight edge to cut the faceplate
from the material. You can also use a high-quality paper cutter. Be especially careful when
using scissors or similar tools. Scissors are more likely to stretch or tear the material,
causing irregular edges for the faceplate.
Printing the Faceplate from a Word-Processing Application
You use a word-processing application (such as Microsoft Word) to print multiple copies of
the faceplate onto A4-size blank faceplate material. After you export the panel image of the
faceplate into a document, you adjust the location of the panel images and print the
document.
Tip
Siemens provides document files (in 6 languages) for Microsoft Word that helps you to align
the panel images for the perforations on the A4 blank faceplate material. To open these
documents, browse to the Templates subdirectory under the Keypad Designer application
(C:/Program Files/Siemens/TD Keypad Designer/Templates) and select the template for
your TD device and language.
Before printing the faceplate onto the blank faceplate material, you must ensure that the
document and the printer settings are both set to print on A4 paper. Also, ensure that the
laser printer itself is configured to print A4 paper.
After you print the faceplate document, you use the perforations to remove the faceplates
from the sheet.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.10 Printing the Panel Image on a Faceplate
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 63
Figure 3-21 Printing Multiple Faceplates
To export the panel image to your word-processing application:
1. Open your word-processing application (Microsoft Word) and open the template file.
2. Open the Keypad Designer
3. In the Keypad Designer, select the File > Export > Panel Image to File menu command to
create a bitmap file that you insert into the word-processing application.
4. Insert the panel image into the document by using the word-processing application to
insert the bitmap file (*.bmp) that you created with the Keypad Designer.
5. Follow the instructions in the template file for positioning and sizing the faceplate.
6. After inserting the panel image into the document, save the document using the File >
Save As menu command of the word-processing application.
With the panel images saved in your document, you can print the document to your laser
printer.
Tip
Before printing the panel image onto the blank faceplate material, first test your design by
printing the faceplate onto regular A4 paper.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.11 Installing the Printed Faceplate onto the TD device
Text Display (TD) User Manual
64 System Manual, 08/2008, A5E00765548-03
3.11 Installing the Printed Faceplate onto the TD device
Installing the Printed Faceplate onto the TD 100C, TD 200C, and TD400C
Use the following procedure to install your custom faceplate on the TD device. The example
shown here is for the TD 200C. Installing a faceplate on a TD 100C and TD400C is similar;
the differences are noted below. To prepare for installation, remove the protective film
covering the display window of the TD device and the back of the preprinted (standard)
faceplate. The protective film is blue for the TD 100C and the TD 200C, and transparent for
the TD400C.
1. If your TD device has a strip of protective paper, remove the strip to expose a strip of the
adhesive. For the TD 200C and TD400C, it is on the left side; for the TD 100C, it is on the
right side of the device.
2. Carefully align your custom faceplate on the entire TD device, and then seal the faceplate
to the exposed adhesive by pressing down on the left (TD 200C and TD400C) or on the
right (TD 100C) side of the faceplate.
3. Carefully lift back the unadhered faceplate and remove the rest of the protective paper
from the TD device.
4. Carefully position the faceplate onto the TD device. Firmly press the faceplate onto the
adhesive, taking care to remove any air bubbles that may have been trapped underneath.
NOTICE
Do not use excessive force or a hard (or sharp) tool when you install the faceplate onto
the TD400C device.
If you use excessive force a hard tool when you press the faceplate onto the TD400C
device, it may cause damage to the springs under the faceplate.
Ensure that excessive force or a hard (or sharp) tool is not used when you install the
faceplate onto the device
Refer to Chapter 2 for additional information about installing the TD devices, including the
dimensions for the faceplate.
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.11 Installing the Printed Faceplate onto the TD device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 65
3
1
2
4
&XVWRP)DFHSODWH
7'&DQG7'&
3URWHFWLYHILOP 3URWHFWLYHSDSHU
Figure 3-22 Adhering the Faceplate onto the TD Device
Using the Keypad Designer to Create a Custom Faceplate for your Text Display (TD) Device
3.11 Installing the Printed Faceplate onto the TD device
Text Display (TD) User Manual
66 System Manual, 08/2008, A5E00765548-03
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 67
Using the Text Display Wizard to Configure the S7-
200 CPU for Your Text Display (TD) Device 4
4.1 Overview
Overview of Chapter 4
You do not configure or program the TD device. The Text Display wizard creates a
parameter block that stores the configuration, screens and alarms for the TD device. The S7-
200 CPU stores the parameter block in V memory. At power-up, the TD device reads the
parameter block from the S7-200 CPU.
You use the Text Display wizard of STEP 7-Micro/WIN to perform the following tasks:
Configuring the parameters for the TD device
Creating the screens and alarms to be displayed on the TD device
Creating the language sets for the TD device (TD 200, TD 200C and TD400C only)
Assigning the V memory address for the parameter block
Tip
To connect your TD device to a network, you use the Diagnostic or TD Setup Menu of the
TD device to set up the network addresses, baud rate and other parameters. Refer to
Chapter 5.
4.2 Overview of the Configuration Tasks
Overview of the Configuration Tasks
The S7-200 CPU stores the configuration data for the TD device, including the screens and
alarms, into a parameter block (located in V memory). The Text Display wizard creates the
parameter block. When you download your project (user program and data block) to the S7-
200 CPU, you also download the parameter block as part of the data block.
You do not configure or program the TD device. At power-up, the TD device reads the
parameter block from the S7-200 CPU.
As shown in the figure below, you use the Text Display wizard of STEP 7-Micro/WIN to
create the parameter block for the TD devices. The next figure shows the sequence of the
tasks required for configuring the parameters of the TD device.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.2 Overview of the Configuration Tasks
Text Display (TD) User Manual
68 System Manual, 08/2008, A5E00765548-03
7' 7'& 7'& 7'&
.H\SDG'HVLJQHU
6DYHNH\SDGFRQILJXUDWLRQILOH
WGIRU7'&WGIRU
7'&DQGWGIRU7'&
67(30LFUR:,1
7H[W'LVSOD\:L]DUG
Ⴠ &UHDWHWKHVFUHHQVDQGWKHDODUPVIRU
\RXURSHUDWRULQWHUIDFH
&RQILJXUHWKHSDUDPHWHUEORFNIRUWKH
7'GHYLFH9PHPRU\LQWKH6
&38
3DUDPHWHU%ORFN
:KHQ\RXGRZQORDG\RXUXVHUSURJUDPWKH
6&38VWRUHVWKHSDUDPHWHUEORFNLQ
WKH9PHPRU\DGGUHVV\RXVHOHFWHG
Figure 4-1 Using the Text Display Wizard to Configure the TD Device
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.2 Overview of the Configuration Tasks
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 69
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
7'3DUDPHWHUV
6HOHFWWKHW\SHRI7'GHYLFH
(QDEOHWKH&38IXQFWLRQV
6HOHFWWKHXSGDWHUDWH
6HOHFWWKHODQJXDJHDQGFKDUDFWHUVHW
&RQILJXUHWKHEXWWRQV
6FUHHQV $ODUPV
/DQJXDJH6HWV7'&7'7'&
&UHDWHWKHXVHUPHQX
Ⴠ 'HILQHWKHPHQXLWHPV
Ⴠ $GGWKHVFUHHQV
6HOHFWWKHGLVSOD\RSWLRQV
Ⴠ 'HILQHWKHOHQJWKIRUWKH
PHVVDJH
'HWHUPLQHGHILQHWKH
GHIDXOWGLVSOD\PRGH
'HILQHWKHVFUHHQ
Ⴠ 'HILQHWKHWH[W
$GGDQ\YDULDEOHGDWD
Ⴠ $GGDQ\LFRQV7'&
7'&
'HILQHWKHDODUPPHVVDJH
'HILQHWKHWH[W
$GGDQ\YDULDEOHGDWD
Ⴠ $GGDQ\LFRQV7'&7'&
'HILQHWKHODQJXDJHVVHWV
Ⴠ 6HOHFWWKHODQJXDJHIRUWKH
SURPSWVDQGPHQXV
Ⴠ 6HOHFWWKHFKDUDFWHUVHW
7UDQVODWHWKHDODUPV
DQGWKHVFUHHQV
3DUDPHWHU%ORFN$GGUHVV
'HILQHWKHDGGUHVVRIWKHSDUDPHWHUEORFN
9PHPRU\
Figure 4-2 Configuration Tasks of the Text Display Wizard
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
70 System Manual, 08/2008, A5E00765548-03
4.3 Configuring the Text Display Device
Configuring the Text Display (TD) Device
STEP 7-Micro/WIN provides a wizard that makes it easy to configure the parameter block
and the messages in the data memory area of the S7-200 CPU.
Text Display Wizard Tasks
As shown below, the Text Display wizard performs the same basic tasks for configuring the
TD devices. However, the specific selections reflect the differences between the TD devices.
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
ᅛ
7' 7'&
7'&7'&
6HOHFWWKH7'GHYLFH
6HOHFWIXQFWLRQVWREHHQDEOHG
3DVVZRUGSURWHFWLRQ
6HW7LPHDQGGDWH
)RUFH,2
6HOHFWIXQFWLRQVWREHHQDEOHG
Ⴠ 3DVVZRUGSURWHFWLRQ
Ⴠ 6HW7LPHDQGGDWH
Ⴠ )RUFH,2
Ⴠ &KDQJH&38WR6723RU
581PRGH
Ⴠ &RS\WKHXVHUSURJUDPWRD
PHPRU\FDUWULGJH
Ⴠ (GLWWKH&38PHPRU\
6HOHFWIXQFWLRQVWREH
HQDEOHG
Ⴠ 3DVVZRUGSURWHFWLRQ
Ⴠ 6HW7LPHDQGGDWH
6HOHFWWKHXSGDWHUDWHIRU
WKH7'&
6HOHFWWKHODQJXDJHDQG
FKDUDFWHUVHWIRUWKH
SURPSWVDQGPHQXV
6HOHFWWKHXSGDWHUDWHIRU
WKH7'&RU7'&
6HOHFWWKHXSGDWHUDWH
IRUWKH7'
6HOHFWODQJXDJHDQG
FKDUDFWHUVHWIRUSURPSWV
DQGPHQXVRIWKH7'
&RQILJXUHWKHDFWLRQIRU
WKHEXWWRQVRQWKHNH\SDG 6HOHFWWKHODQJXDJHDQG
FKDUDFWHUVHWIRUWKH
SURPSWVDQGPHQXV
&RQILJXUHWKHEXWWRQVRQWKH
NH\SDG
Ⴠ /RDGFRQILJXUDWLRQILOHWGRU
WGIRUWKHFXVWRPNH\SDG
Ⴠ &RQILJXUHWKHDFWLRQIRUWKH
EXWWRQVRQNH\SDG
&RQILJXUHWKHEXWWRQVRQ
WKHNH\SDG
Ⴠ /RDGWKHFRQILJXUDWLRQ
ILOHWGIRUWKH
FXVWRPNH\SDG
Ⴠ &RQILJXUHWKHDFWLRQ
IRUWKHEXWWRQVRQ
NH\SDG
Figure 4-3 Tasks Required for Configuring the Parameters of the TD Device
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 71
Starting the Text Display Wizard for the TD Device
You use the Text Display wizard to configure the parameters for the TD device. You can also
use the Text Display wizard to modify an existing TD configuration.
To open the Text Display wizard:
1. Start STEP 7-Micro/WIN.
2. Select the Tools > Text Display Wizard menu command.
The Text Display wizard displays the Introduction dialog, as shown in the figure below.
If the Text Display wizard finds an existing TD configuration, the Introduction dialog provides
a list of existing TD configurations and allows you to select a TD configuration to modify.
Use the Next button to proceed through the dialogs of the wizard.
Figure 4-4 Text Display Wizard
Selecting the Type of Device to Configure
As shown below, the Text Display wizard prompts you to select the type of TD device to be
configured.
The Text Display wizard uses this selection to display the dialogs for configuring the
parameters for your specific TD device.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
72 System Manual, 08/2008, A5E00765548-03
Figure 4-5 Selecting the TD Device
Selecting a Password for the TD Device
Selecting a password for the TD device helps you to protect the security of your process or
application. By enabling a four-digit password (from 0000 to 9999), you can control access to
the S7-200 CPU by requiring that an operator enter the password before editing variables
from the TD device.
The TD password also restricts access to the following TD functions:
Set time and date
TD Setup
Forcing I/O
Changing the CPU mode
Creating a memory cartridge
Editing CPU memory
Tip
The TD password affects only the ability of an operator to use the TD device for certain
functions.
If your S7-200 CPU is configured to require a password, the operator must enter the CPU
password to force I/O and create a memory cartridge. The TD password is used in addition
to the CPU password.
Enabling the TD Menu Functions
You can select the TD functions that appear on your TD device menu. The TD devices have
different functions available. Refer to Chapter 5 for information about these CPU functions.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 73
TD 200
Select the functions you want to be available on the TD 200 menus. The TD 200 supports
the following functions:
Setting the Time-of-Day clock: Allows you to set the time and date for the S7-200 CPU
Forcing I/O: Allows you to force I/O points in the S7-200 CPU to be on or off
Figure 4-6 Enabling the CPU Functions for the TD 200
TD 200C and TD400C
Select the functions you want to be available on the TD 200C or TD400C menus. The
TD 200C and TD400C support the following functions:
Setting the Time-of-Day clock: Allows you to set the time and date for the S7-200 CPU
Forcing I/O: Allows you to force I/O points in the S7-200 CPU to be on or off
Creating a memory cartridge: Allows you to create a memory cartridge which is a
complete copy of the CPU
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
74 System Manual, 08/2008, A5E00765548-03
Changing the operating mode: Allows you to set the S7-200 CPU to STOP or RUN
Editing the CPU memory: Allows you to view and change the values of the data stored in
the S7-200 CPU
Figure 4-7 Enabling the CPU Functions for the TD400C and TD 200C
TD 100C
Select the function you want to be available on the TD 100C menus.
The TD 100C supports the Setting the Time-of-Day clock function. This function allows you
to set the time and date for the S7-200 CPU function.
Figure 4-8 Enabling the CPU Functions for the TD 100C
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 75
Selecting the Update Rate for the TD Device
You can select how often the TD device performs a read operation to update the information
from the S7-200 CPU. You can select from "As fast as possible" to "Every 15 seconds" (in
one-second increments).
Selecting the Language and the Character Set
The Text Display wizard allows you to select the language for the system menus and
prompts of the TD device. This selection does not affect the language setting for the screens
or alarms that you enter. You select a character set that supports the language of the text
that you enter for the screens and alarms. (If the character set does not match the Windows
character set, the Text Display wizard may not display the characters correctly. The TD
device displays these characters correctly.)
Select the language for the system menus and prompts displayed by the TD device.
The TD devices support English, French, German, Italian, Simplified Chinese, and
Spanish.
Select the character set for the text in your alarms and screens.
Refer to Appendix A for descriptions of the character sets supported by your TD device.
The Simplified Chinese Character Set is an electronic file that resides on the STEP 7-
Micro/WIN documentation CD
These settings define a language set for the TD device. The Text Display wizard also
provides a series of dialogs for copying the alarms and screens to create additional language
sets (TD 200, TD 200C, and TD400C). For each language set, you select the language and
the character set.
Figure 4-9 Localizing the TD Device
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
76 System Manual, 08/2008, A5E00765548-03
Tip
When you create multiple language sets (TD 200, TD 200C, and TD400C), the Text Display
wizard copies the alarms and screens from the primary language set to the other language
set. You then edit the screens and alarms to translate the text displayed for the new
language set.
If you need to modify the screens or messages (such as to add a new variable or to add a
new alarm), you must edit the primary language. The Text Display wizard copies these
changes to the other language sets.
The Text Display wizard only allows you to change the text in the other language sets.
Selecting the Font Size (TD 100C, TD400C)
The TD 100C and TD400C support two font sizes for displaying user and alarm messages.
Larger fonts are easier to read, but will result in fewer characters per user message. You
select the font size for the TD100C as shown in the figure below. You select the font size for
the TD400C when you configure the alarm or user message (refer to the section on
configuring screens and alarms in this chapter).
The following font sizes are available:
TD 100C:
Small font (16 ASCII or 8 Chinese characters per line)
Large font (12 ASCII characters per line)
Font selection applies to all messages and screens
TD400C:
Small font (24 ASCII or 12 Chinese characters per line)
Large font (16 ASCII or 8 Chinese characters per line)
Each alarm or screen can have a different font
Figure 4-10 Selecting the Font Size (TD 100C)
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 77
Loading a Custom Keypad (TD 100C, TD 200C, and TD400C Only)
The TD 100C, TD 200C, and TD400C allow you to create a custom keypad. As described in
Chapter 3, you can insert buttons onto the keypad. The Keypad Designer saves this
configuration to a file (*.td1 for the TD 100C, *.td2 for the TD 200C, and *.td4 for the
TD400C).
To load the keypad configuration file into the Text Display wizard:
Select the option, Use a custom keypad created with the Keypad Designer. (Find this
check box in the Options area of the Configure Keypad Buttons dialog. See Figure
below.)
Browse to the keypad configuration file (*.tdx) that you created with the Keypad Designer.
The Text Display wizard loads the keypad configuration file and updates the table of buttons
and the button symbols.
The Text Display wizard lists only those buttons that you had defined with the Set Bit
functionality when you created the buttons with the Keypad Designer.
Figure 4-11 Configuring the Functions for the Buttons (TD 200C)
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.3 Configuring the Text Display Device
Text Display (TD) User Manual
78 System Manual, 08/2008, A5E00765548-03
Figure 4-12 Configuring the Functions for the Buttons (TD400C)
Configuring the Buttons on the Keypad
As shown in previous figure, the Configure Keypad Buttons dialog allows you to select a
symbol name and an action for each of the configurable buttons on the TD device.
The TD 200 keypad provides 4 configurable buttons and a SHIFT button that can be
configured for up to 8 bits in the S7-200 CPU
The TD 200C can be configured for up to 20 configurable buttons
The TD 100C can be configured for up to 14 configurable buttons
The TD400C can be configured for up to 15 configurable buttons
Tip
The Configure Keypad Buttons dialog of the Text Display wizard displays only those buttons
that set bits in the S7-200 CPU. The Text Display wizard does not list the buttons with other
functionality, such as ESC or SHIFT.
The symbols that you assign to the buttons on the keypad allow the logic of your user
program in the S7-200 CPU to interact with the TD device. (The Text Display wizard
suggests a symbol for these buttons. You can accept the recommendation or enter a new
symbol for the button.)
For each button, you configure the type of action:
Set bit: When you press the button on the TD device, the TD device sets the bit on in the
S7-200 CPU. The bit stays on until the logic of your user program in the S7-200 CPU
resets the bit.
Momentary contact: When you press the button on the TD device, the TD device sets the
bit on in the S7-200 CPU. When the TD device button is released, the TD device turns
the bit off in the S7-200 CPU.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 79
Tip
The TD device only sets the bit on or off in the S7-200 CPU a single time when the TD
device button is either pressed or released.
Tip
The TD device can display a special icon that provides visual feedback to the operator and
shows that the set bit key was pressed in the CPU. To enable this feature, check the box at
the bottom of the Configure Keypad Buttons wizard screen (see the previous figure).
4.4 Configuring the Screens for the Text Display Device
Configuring the Screens for the TD Device
The TD device supports a set of user-defined screens and a user menu. Screens allow the
operator using the TD device to initiate the interaction with the S7-200 CPU. See the figure
below.
User menu: Provides a hierarchy for switching between groups of screens. For the
TD 200, TD 200C, and the TD400C you configure up to 8 entries in the user menu. For
the TD 100C, you configure up to 4 entries in the user menu.
Screens: You create up to 8 screens for each entry in the user menu.
The TD device displays the screens and the items on the user menu in the order that you
configure them.
If you configure both alarms and screens, you also designate the default display mode for
the TD device.
The operator uses the buttons on the keypad to navigate through the user menu or the
screens that you configured.
ᅛ
ᅛ
6FUHHQV
&UHDWHWKHXVHUPHQX
'HILQHWKHPHQXLWHPV
Ⴠ $GGWKHVFUHHQV
'HILQHWKHVFUHHQ
Ⴠ 'HILQHWKHWH[W
Ⴠ $GGYDULDEOHGDWD
Ⴠ $GGLFRQV
Figure 4-13 Configuring the Screens
The buttons that a TD operator could use to navigate from a user menu to the screens
associated with that item in the menu are shown below.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
80 System Manual, 08/2008, A5E00765548-03
(QWHU
(6&
7KH83$UURZVFUROOVXSWKURXJK
WKHOLVWDQGZUDSVWRWKHODVWLWHP
7KH83$UURZVFUROOVXSWKURXJK
WKHOLVWDQGZUDSVWRWKHODVW
VFUHHQ
(17(5GLVSOD\V
WKHVFUHHQV
(6&UHWXUQVWR
WKHXVHUPHQX
7KH'2:1$UURZVFUROOVGRZQWKURXJK
WKHOLVWDQGZUDSVWRWKHILUVWLWHP
7KH'2:1$UURZVFUROOVGRZQ
WKURXJKWKHOLVWDQGZUDSVWRWKH
ILUVWVFUHHQ
<RXFDQFRQILJXUHXSWRLWHPV
7'7'&7'&RUXS
WRLWHPV7'&IRUWKHXVHU
PHQX
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
<RXFDQFRQILJXUHXSWRVFUHHQV
IRUHDFKXVHUPHQXLWHP
6FUHHQRUOLQHV
&DQEHLQWHUDFWLYH
6FUHHQRUOLQHV
&DQEHLQWHUDFWLYH
6FUHHQRUOLQHV
&DQEHLQWHUDFWLYH
6FUHHQRUOLQHV
&DQEHLQWHUDFWLYH
Figure 4-14 Navigating through a Hierarchy of User-Defined Screens
Tip
The screens in the TD 200 and TD 200C are always two lines. The screens in the TD 100C
are always four lines. The screens in the TD400C can be 4 lines (with the small font), or 2
lines (with the large font).
After you have configured the TD device, you can configure the screens and the user menu.
Click the user menu icon to start creating the user menu for the screens. See the figure
below.
For the user menu, you perform the following tasks:
Create the groups (names) to be displayed on the user menu
Determine the sequence of the groups listed on the user menu
For the screens, you perform the following tasks:
Add the screens to each group (on the user menu)
Create the text message (and add variables) for each screen
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 81
Add icons to the text message (TD 200C and TD400C only)
Determine the sequence of the screens for each group
Figure 4-15 Selecting the Screen Configuration Tasks
Creating the User Menu
The process for creating the screens and user menu is not sequential: You can choose to
enter the screens for each individual group before creating the next group, or you can enter
all of the groups for the user menu before creating any of the screens.
To configure the user menu, you enter the names for each group of screens. See the figure
below for an example of the TD400C. The Text Display wizard displays a green ENTER icon
(and blue arrow) to show which group is selected.
To create the screens associated with a group on the user menu:
1. Move the cursor to the box that designates the group on the user menu.
2. Click the Add Screen button.
3. Create the text for the screen.
4. Click the Add Screen button to create the other screens in this group.
Use the Move Choice Up and Move Choice Down buttons to change the sequence of the
groups listed on the user menu.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
82 System Manual, 08/2008, A5E00765548-03
Figure 4-16 Defining the User Menu
Creating the Text for a Screen
Your screen message can contain the following elements:
Text: Enter your text in the green area that represents the text display area of the TD
device
Icons (optional): Click the icons in the toolbar to insert the icon into the text message
(TD 200C and TD400C only)
Variable data (optional): Click the Insert PLC Data button to embed a variable into the
text message
Font selection (TD400C only): Select the Font button to select a font. You can select a
different font for each row of the user message.
You can designate the screen to be the default screen. The TD will show the default screen
after being powered on.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 83
Figure 4-17 Creating the Message for a TD 200C Screen
Figure 4-18 Creating the Message for a TD400C Screen
Embedding a Variable into the Text of a Screen
You can embed a variable data field into the text of the screen. To open the Insert PLC Data
dialog, move the cursor to the location for the variable in your text and click the Insert PLC
Data button. As shown in the figure below, you enter the following information:
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
84 System Manual, 08/2008, A5E00765548-03
Tip
For the TD 200, TD 200C, and the TD400C, you can embed up to 6 variables per screen.
For the TD 100C, you can embed up to 1 variable per line (4 variables per screen).
Data address:
VB: Numeric String, Text String
VW: Signed, Unsigned
VD: Real, Signed, Unsigned
Data Format: Signed, Unsigned, Real, Numeric String, or Text String
Digits to the right of the decimal: Up to 7
Figure 4-19 Inserting PLC Data
The TD device rounds a real number to the specified decimal place. For example, if the real
number value is 123.456 and you select 2 digits to the right of the decimal, the TD 200
displays this value as: 123.46.
Tip
Refer to the SIMATIC S7-200 Programmable Controller System Manual for information
about the data types or for the memory addresses supported by the S7-200 CPU.
You can also allow the operator to modify the data stored at this memory location in the S7-
200 CPU.
You can require the operator enter the TD password before editing the variable. (You
must have enabled password-protection for the TD device.)
You can configure the cursor to jump to the variable field.
You can define a symbolic name for the variable. You use the symbolic name to access
this data with your user program.
Clicking OK inserts the variable into the text of the screen. The Text Display wizard inserts a
block of 4 characters to show the presence of the variable. The value to be displayed for the
variable is right-justified at that location (anchored to the right-most character).
Data values are always right-justified to the right-most character of an embedded variable.
As a data value grows in magnitude, it utilizes more spaces to the left of the anchor point
and can overwrite the text characters. Always provide sufficient space between the end of
your text and the anchor point to allow for the expected range of the data value.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 85
Tip
The actual number of characters used to display a value varies with the size of the value. To
help calculate the number of characters required for displaying the value of the variable, see
the examples listed in Table 4-1.
The TD device displays all values as decimal numbers. Positive signed values are displayed
without a sign, and negative signed values are displayed with a leading minus sign.
Unsigned values are displayed without a sign. A leading zero is used for all fractional
numbers (for example, 0.5). Real numbers are displayed with the number of decimal places
you specify. The value is rounded to the specified decimal place.
Table 4- 1 Calculating the Number of Characters Required to Display a Value
Size Type Resolution
(Digits to right
of decimal)
Maximum Number
of Characters
Example
String Not applicable Line length 1 Hello, world Byte
(VB) Numeric
String
Not applicable Line length 1 800.333.7421
Unsigned 0
1 to 4
5
6
7
5
6
7
8
9
12345
1234.5, 1.2345
0.12345
0.012345
0.0012345
Word
(VW)
Signed 0
1 to 4
5
6
7
6
7
8
9
10
-12345
-1234.5, -1.2345
-0.12345
-0.012345
-0.0012345
Unsigned 0
1 to 7
10
11
1234567890
123456789.1, 123.4567891
Signed 0
1 to 7
11
12
-1234567890
-123456789.1, -123.4567891
Double-Word
(VD)
Real 0
1 to 7
Line length1
Line length1
-1234567
12345.6, 0.0123456
1 The length of a line (number of characters in a line) varies by TD model and character size. The line
length is always 20 for a TD 200 or TD 200C. The line length is either 12 or 16 characters for a
TD 100C. The line length for the TD400C depends on the font you selected. If you selected a small
font, you have 24 ASCII characters or 12 Chinese characters per line. If you selected a large font,
you have 16 ASCII characters or 8 Chinese characters per line.
Embedded String Variables
There are special considerations when you set up a string variable for the TD devices. String
variables are positioned the same as numeric variables, that is, the right-most character of
the variable is positioned at the right-most position of the embedded variable in the Text
Display wizard. This can cause problems when you want to place a text string adjacent to
other text in the message.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.4 Configuring the Screens for the Text Display Device
Text Display (TD) User Manual
86 System Manual, 08/2008, A5E00765548-03
When you embed a string variable in a TD alarm or screen, the Text Display wizard shows
the embedded variable occupying 4 character spaces (or 2 Chinese characters) for the
variable. These 4 spaces are the right-most 4 characters of the text string. If you want to
have the text adjacent to other text, that is, to the left of the variable, the characters in the
string need to be left-justified and padded with spaces to place the text in the proper position
on the display.
For example: Assume that we want to show the pump status and that status is either "Pump
OK" or "Pump High Temp". The screen display shows the word "Pump" followed by a string
variable which is set to either "OK" or "High Temp". You set up the display in the Text
Display wizard like this:
Pump _ _ _ _ _ _
The underlines are blank spaces, and the squares are the embedded variable (which takes
up 4 character spaces). You can create 2 strings that you copy into the variable based on
the current pump status. These strings are "OK" and "High Temp". These strings are
displayed in the figure below.
3XPS+LJK7HPS RU 3XPS2.
Figure 4-20 Embedded String Variable
The right-most character of the "OK" string is placed in the right-most position of the
embedded variable. Since the string is only 2 characters, it displays on the right side of the
display where the embedded variable is placed.
To make the "OK" string display next to "Pump", simply add blank spaces to the "OK" string
to match the length of the other string. The "OK" string would become "OK ". Now the string
is displayed in the figure below.
3XPS2.
Figure 4-21 Embedded String Variable with Blank Spaces
The figure below shows how to create the two strings using the STR_CPY command. Note
how the "OK" string is padded with blank spaces to left justify the characters on the TD
display.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 87
Figure 4-22 Using STR_CPY to Create Strings
4.5 Configuring the Alarms
Configuring the Alarms
Alarms allow the user program in the S7-200 CPU to initiate interaction with the operator by
displaying an alarm message on the TD device. When your user program sets an alarm bit,
the TD device reads the text of the alarm from the S7-200 CPU.
The figure below lists the key tasks for creating alarms. You configure the following
information for each alarm:
Number of alarms: Up to 80 alarms for the TD 200, TD 200C and TD400C, and up to 40
alarms for the TD 100C to be configured for the TD device
Text message for the individual alarms
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
88 System Manual, 08/2008, A5E00765548-03
Priority for the alarms is determined by the sequence in which you configure the alarms:
The first alarm has the highest priority
The last alarm has the lowest priority
Acknowledgement (if required)
ᅛ
ᅛ
$ODUPV
6HOHFWWKHGLVSOD\RSWLRQV
'HILQHWKHVL]HRIWKHDODUPVHLWKHU
RUOLQHV
Ⴠ 'HILQHKRZWRDQQRXQFHWKHDODUP
'HILQHWKHDODUPPHVVDJH
'HILQHWKHWH[W
Ⴠ ,QVHUWDYDULDEOHRSWLRQDO
Ⴠ ,QVHUWDQLFRQRSWLRQDO
7'&7'&RQO\
Figure 4-23 Configuring the Alarms
The TD 200, TD 200C, and TD400C devices store up to 80 alarms, and the TD 100C device
stores up to 40 alarms. The TD displays the alarm messages according to priority.
The operator uses the buttons on the keypad to scroll through the list of alarms. See the
figure below.
(QWHU
(6&
$FNQRZOHGJHVWKHDODUP
WKDW\RXKDYHVHOHFWHG
6FUROOVXSWKURXJKWKHOLVWRIDODUP
PHVVDJHVDQGZUDSVWRWKHODVWLWHP
6FUROOVGRZQWKURXJKWKHOLVWRIDODUP
PHVVDJHVDQGZUDSVWRWKHILUVWLWHP
5HWXUQVWRWKH
PDLQPHQX <RXFDQFRQILJXUHXSWRDODUPVIRU\RXU7'7'&
DQG7'&DQGXSWRDODUPVIRU\RXU7'&
7KHRUGHURIWKHDODUPVLQ\RXUFRQILJXUDWLRQGHWHUPLQHVWKH
SULRULW\
7KHILUVWDODUPLQ\RXUFRQILJXUDWLRQKDVWKHKLJKHVWSULRULW\
Ⴠ 7KHVHFRQGDODUPLQ\RXUFRQILJXUDWLRQKDVWKHVHFRQG
KLJKHVWSULRULW\
$ODUPKLJKHVWSULRULW\
$ODUP
$ODUPORZHVWSULRULW\
$ODUP
$ODUP
$ODUP
$ODUP
$ODUP
Figure 4-24 Alarm Messages
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 89
Determining the Type of Operator Interaction for an Alarm
The Text Display wizard allows you to determine the type interaction required by the
operator for an alarm. If the user screens are set as the default display mode for the TD
device and an alarm is enabled, an alarm indicator will begin to flash on the TD display. The
indicator is large if there is an alarm enabled that requires acknowledgement. The indicator
will be small if the alarms do not require acknowledgement. The user can switch to the alarm
display to view the alarms.
The alarm display will show one or more alarms in priority order. An UP or DOWN arrow in
the right-most character position indicates more alarms are active, but not visible on the
display. The operator can press either the UP or the DOWN arrow key to scroll through the
other enabled alarms.
The operator can edit or accept variable values by pressing the ENTER key. The TD device
will write the updated variable value to the CPU and set the edit notification bit for that
variable when the operator presses the ENTER key. The TD device then moves the cursor
to the next editable variable. Pressing ENTER for the last editable variable of an alarm writes
this last value to the S7-200 CPU and the TD device then resets the alarm enable bit. For
more information on editing variables, see Editing a Variable that is Embedded in an Alarm
or a Screen in Chapter 5.
Every alarm falls into one of four possible alarm acknowledgement and editing types. This
section explains specifically how each alarm type is handled by the TD device. The four
alarm types follow:
No acknowledgement required, no edits allowed
Acknowledgement required, no edits allowed
No acknowledgement required, edits allowed
Acknowledgement required, edits allowed
No Acknowledgement Required, No Edits Allowed
In this combination of no acknowledgement required and no edits allowed, the TD device
simply displays the alarm. The ENTER key has no function since there are no editable
variables within the alarm. The alarm may contain variables that are updated at the update
rate of the TD device. This type of alarm is replaced on the display if a higher priority alarm is
enabled by the S7-200 CPU. The operator can either press the UP or the DOWN arrow key
to scroll to other alarms or press ESC to return to the menus.
The TD device does not clear the corresponding alarm-enable bit in the S7-200 CPU.
Acknowledgement Required, No Edits Allowed
In this combination of acknowledgement required and no edits allowed, the TD device
displays the alarm and makes the entire alarm flash (blink) until the operator presses ENTER
to acknowledge the alarm. Variable values are updated from the S7-200 CPU at the normal
update rate while the alarm is flashing.
When the operator presses ENTER, the TD device:
Sets the acknowledgement-notification bit for this alarm.
Clears the alarm-enable bit for this alarm. This causes the alarm to be removed from the
display on the next update cycle.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
90 System Manual, 08/2008, A5E00765548-03
Another alarm cannot replace the one flashing until the operator acknowledges the flashing
alarm. This is also true even if a higher priority alarm is enabled in the S7-200 CPU. If the TD
device is configured for single line alarms and the CPU enables a higher priority alarm, the
flashing alarm shifts down to the next line of the display. The operator cannot press the UP
or the DOWN key to scroll through other enabled alarms until the current alarm is
acknowledged.
No Acknowledgement Required, Edits Allowed
In this combination of no acknowledgement required and edits allowed, the TD device
displays a alarm and then waits for the operator to edit a value in the alarm. All of the
variables within the alarm are updated at the update rate. Since the alarm does not require
acknowledgement, this type of alarm is removed from the TD device display if a higher
priority alarm is enabled in the S7-200 CPU.
Acknowledgement Required, Edits Allowed
In this combination of acknowledgement required and edits allowed, the TD device displays
the alarm, causes the entire alarm to flash (blink), and then waits until the operator
acknowledges the alarm and edits or accepts the values in the alarm. This type of alarm
requires that the operator edits or accepts the values displayed in the alarm. If the operator
aborts the edit by pressing the ESC key before editing all the values in the alarm, the alarm
flashes to indicate that edits are still required.
When the alarm is enabled in the S7-200 CPU, the TD device notes this and, if there is
space available on the display, reads the alarm from the CPU. The TD device then displays
the alarm and causes the entire alarm to flash to notify the operator that the alarm is present
and must be acknowledged.
Setting the Default Display Mode and Alarm Parameters
The TD device supports alarms that are displayed under program control. After you have
configured the TD device, you can configure the alarms. When you configure the alarms, you
also select either screens (default) or alarms as the default display mode for the TD device.
Click the Alarms icon to start creating alarms. As shown in the figure below, you select the
following information:
Default display mode: Select either alarms or screens as the default display mode. This
selects which type of messages the TD device displays after powering up or after a
prolonged period of no key presses by the user.
Size of the alarms: Select 1 line or 2 lines (TD 100C, TD200 and TD400C), or 4 lines
(TD400C only).
For Chinese characters, select either one row or two rows of text.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 91
Figure 4-25 Configuring the TD 200C Alarm Options
Figure 4-26 Configuring the TD400C Alarm Options
Tip
The TD 200, TD 200C, and the TD400C support up to 80 alarms, and the TD 100C supports
up to 40 alarms. The priority for the alarms is determined sequentially, from the first alarm
(highest priority) to the last (lowest priority).
Entering the Text for an Alarm
Clicking Next displays the Alarms dialog shown in the figure below. You can select a
symbolic name for the alarm. The user program uses the symbolic name to enable (and
display) the alarm. Click the New Alarm button to create the alarm message. Your alarm
message can contain the following elements:
Text: Enter your text in the green area that represents the text display area of the TD
device
Icons (optional, TD 200C and TD400C): Click the icons in the toolbar to insert the icon
into the text message
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
92 System Manual, 08/2008, A5E00765548-03
Variable data (optional): Click the Insert PLC Data button to embed a variable into the
text message
Fonts: For the TD400C you select the font to use for the alarm message
To ensure that important alarms are acknowledged by an operator, you can configure the
alarm to require acknowledgement.
You select the symbolic name for the acknowledgement bit for the alarm. The user program
uses this symbolic name to report that the alarm has been acknowledged.
To acknowledge an alarm with the TD device, the operator selects the alarm and presses
ENTER.
Figure 4-27 Creating the Text for an Alarm
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 93
Embedding a Variable into the Text of an Alarm
You can embed a variable data field into the text of the alarm. To embed a variable, move
the cursor to the location for the variable in your text and click the Insert PLC Data button. As
shown in the figure below you enter the following information:
Tip
For the TD 200, TD 200C, and the TD400C, you can embed up to 6 variables per alarm. For
the TD 100C, you can embed up to 1 variable per line (1 for one-line alarms, and 2 for two-
line alarms).
Data address:
VB: Numeric String, Text String
VW: Signed, Unsigned
VD: Real, Signed, Unsigned
Data Format: Signed, Unsigned, Real, Numeric String, or Text String
Digits to the right of the decimal: Up to 7
The TD device rounds a real number to the specified decimal place. For example, if
the real number value is 123.456 and you select 2 digits to the right of the decimal, the
TD 200 displays this value as: 123.46.
Figure 4-28 Inserting a Variable into the Text of an Alarm
Tip
Refer to the SIMATIC S7-200 Programmable Controller System Manual for information
about data types or for the memory addresses supported by the S7-200 CPU.
You can also allow the operator to modify the data stored at this memory location in the S7-
200 CPU.
You can require the operator enter the TD password before editing the variable. (You
must have enabled password-protection for the TD device.)
You can configure the cursor to jump to the variable field.
You can define a symbolic name for the variable. You use the symbolic name to access
this data with your user program.
Clicking OK inserts the variable into the text of the alarm. The Text Display wizard inserts a
block of 4 characters to show the presence of the variable. The value to be displayed for the
variable is right-justified at that location (anchored to the right-most character).
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.5 Configuring the Alarms
Text Display (TD) User Manual
94 System Manual, 08/2008, A5E00765548-03
Data values are always right-justified to the right-most character of an embedded variable.
As a data value grows in magnitude, it utilizes more spaces to the left of the anchor point
and can overwrite the text characters. Always provide sufficient space between the end of
your text and the anchor point to allow for the expected range of the data value.
Tip
The actual number of characters used to display a value varies with the size of the value. To
help calculate the number of characters required for displaying the value of the variable, see
the examples listed in Table 4-2.
The TD device displays all values as decimal numbers. Positive signed values are displayed
without a sign, and negative signed values are displayed with a leading minus sign.
Unsigned values are displayed without a sign. A leading zero is used for all fractional
numbers (for example, 0.5). Real numbers are displayed with the number of decimal places
you specify. The value is rounded to the specified decimal place.
For more information about embedding string variables in an alarm, see page 53.
Table 4- 2 Calculating the Number of Characters Required to Display a Value
Size Type Resolution
(Digits to right
of decimal)
Maximum Number
of Characters
Example
String Not applicable Line length 1 Hello, world Byte
(VB) Numeric
String
Not applicable Line length 1 800.333.7421
Unsigned 0
1 to 4
5
6
7
5
6
7
8
9
12345
1234.5, 1.2345
0.12345
0.012345
0.0012345
Word
(VW)
Signed 0
1 to 4
5
6
7
6
7
8
9
10
-12345
-1234.5, -1.2345
-0.12345
-0.012345
-0.0012345
Unsigned 0
1 to 7
10
11
1234567890
123456789.1, 123.4567891
Signed 0
1 to 7
11
12
-1234567890
-123456789.1, -123.4567891
Double-Word
(VD)
Real 0
1 to 7
Line length1
Line length1
-1234567
12345.6, 0.0123456
1 The length of a line (number of characters in a line) varies by TD model and character size. The line
length is always 20 for a TD 200 or TD 200C. The line length is either 12 or 16 characters for a
TD 100C. The line length for the TD400C depends on the font you selected. If you selected a small
font, you have 24 ASCII characters or 12 Chinese characters per line. If you selected a large font,
you have 16 ASCII characters or 8 Chinese characters per line.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.6 Configuring the Language Sets (TD 200, TD 200C, and TD400C)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 95
4.6 Configuring the Language Sets (TD 200, TD 200C, and TD400C)
Configuring the Language Sets for the TD Device (TD 200, TD 200C, TD400C)
The Text Display wizard allows you to configure multiple language sets for your TD device,
including not only the system prompts or messages, but also for the user alarms, user
menus, and screens. The Text Display wizard copies the user alarms and user screens that
you have configured into the language set. You must manually enter the translated text for
each alarm, menu, or screen.
For each language set, you select the following information:
Language for the system prompts
Character set
Identifier
You also select which of the language sets is the primary language for the TD device.
ᅛ
/DQJXDJH6HWV
'HILQHWKHODQJXDJHVVHWV
Ⴠ 6HOHFWWKHODQJXDJHIRUWKHV\VWHPPHQXVDQG
SURPSWV
Ⴠ 6HOHFWWKHFKDUDFWHUVHW
Figure 4-29 Configuring the Languages for the TD Device
Tip
When you create multiple language sets, the Text Display wizard copies the user alarms,
menus, and screens from the primary language set to the other language set. You then edit
the alarms, menus, and screens to translate the text displayed for the new language set.
If you need to modify the screens or messages (such as to add a new variable or to add a
new alarm), you must edit the primary language. The Text Display wizard copies these
changes to the other language sets.
The Text Display wizard only allows you to change the text in the other language sets.
After you have configured the alarms and screens for one language set, you can add a new
language set:
1. Click the icon to start configuring the language sets for the TD device.
2. Add a new language by selecting New Language Set.
3. Select an existing language set to be the source for the new language set.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.6 Configuring the Language Sets (TD 200, TD 200C, and TD400C)
Text Display (TD) User Manual
96 System Manual, 08/2008, A5E00765548-03
4. (Optional) Select the option for primary language to configure the new language as the
default language set for the TD device.
5. Click the Next button to display the Localize Display dialog.
Figure 4-30 Adding a Language
The Localize dialog configures the menus and character set for the TD device
1. Select the language for the system menus and prompts of the TD device.
2. Select the character set for the text.
3. Enter the name to be displayed on the TD device for this language set.
After you click the Next button, the Text Display wizard copies all of the user alarms, menus,
and screens from the selected language set to the new language set.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.6 Configuring the Language Sets (TD 200, TD 200C, and TD400C)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 97
Figure 4-31 Localizing the Display
Notes for Using the Simplified Chinese Character Set
Tip
The Simplified Chinese character set requires a Chinese version of Windows or a Chinese
emulator to properly display Chinese characters in the Text Display wizard. You must start
the Chinese emulator before you start the STEP 7-Micro/WIN software.
On the TD 200C, and the TD 200, you can display up to 20 single-byte characters per line of
your message. Because Simplified Chinese uses double-byte characters, you can display up
to 10 double-byte characters per line for a message in Chinese.
On the TD 100C, you can display up to 16 single-byte characters per line of your message.
Because Simplified Chinese uses double-byte characters, you can display up to 8 double-
byte characters per line for a message in Chinese.
On the TD400C using a small font, you can display up to 24 single-byte characters per line
of your message. Because Simplified Chinese uses double-byte characters, you can display
up to 12 double-byte characters per line for a message in Chinese. If you selected a large
font, you can display up to 16 single-byte characters or 12 Chinese characters per line.
The standard ASCII characters, such as numbers, punctuation, and upper and lowercase
alphabet characters, are available when using the Simplified Chinese character set.
Depending on your keyboard and/ or emulator, some of these standard characters may be
formatted as single-byte characters instead of the double-byte characters like the Simplified
Chinese characters. Standard ASCII characters and Chinese characters can be mixed on
the TD display.
The Text Display wizard displays 8, 10 or 12 double-byte character places for the text of a
screen or alarm. You can fit any of the following combinations into a character position:
1 double-byte character
2 single-byte characters (standard ASCII)
1 single-byte character and 1 single-byte blank
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.7 Assigning the V Memory Address for the Parameter Block
Text Display (TD) User Manual
98 System Manual, 08/2008, A5E00765548-03
You cannot fit one single-byte character plus one double-byte character in a character
position.
The TD 100C does not support the entire Simplified Chinese character set, but does support
the most commonly used characters. Characters that are not supported by the TD 100C are
displayed as a square.
See the Simplified Chinese Characters Set on the STEP 7-Micro/WIN documentation CD for
a list of characters supported by the TD 100C.
4.7 Assigning the V Memory Address for the Parameter Block
Assigning the V Memory Address for the Parameter Block
The Text Display wizard creates the parameter block that you download to the S7-200 CPU
with your user program. The parameter block includes the configuration data for the TD
device and any screens and alarms that you created.
The Text Display wizard calculates the amount of memory required for the parameter block
and suggests a starting address in V memory.
The default location for the parameter block is VB0.
3DUDPHWHU%ORFN$GGUHVV
'HILQHWKHDGGUHVVRIWKHSDUDPHWHUEORFN
9PHPRU\
ᅛ
Figure 4-32 Assigning the Address of the Parameter Block
4.8 Finishing the Configuration for the TD Device
Finishing the Configuration for the TD Device
After you complete the configuration for your TD device, the Text Display wizard displays a
summary dialog. (See the figure below.)
If you enter a name for the TD configuration, STEP 7-Micro/WIN creates an entry in the
project tree for the TD configuration.
STEP 7-Micro/WIN also creates the following subroutines:
TD_CTRL_x (where x is the TD configuration number)
This subroutine ensures that all updates for the TD device (such as alarms or
changing the language setting) occur immediately.
Your user program should use SM0.0 to call this subroutine every scan
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.8 Finishing the Configuration for the TD Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 99
TD_ALM_x (where x is the TD configuration number)
Your user program uses this subroutine to call the alarm by the symbolic name
(configured by the Text Display wizard). This subroutine requires the S7-200 Symbol
Table.
Your user program should call TD_ALM_x on every scan when the alarm is present.
Figure 4-33 Summary Dialog
Note
The TD_CTRL_X subroutine will clear the alarm enable bits each time it is called. This
behavior could be problematic if the TD configuration contains alarms that require
acknowledgement. The TD_CTRL_x subroutine may disable these alarms before they
can be displayed and acknowledged on the TD device. Your program logic must
ensure that any TD_ALM_x alarm subroutine that requires acknowledgement remains
enabled until the TD device writes the alarm acknowledgement bit in the CPU.
Using the Text Display Wizard to Configure the S7-200 CPU for Your Text Display (TD) Device
4.8 Finishing the Configuration for the TD Device
Text Display (TD) User Manual
100 System Manual, 08/2008, A5E00765548-03
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 101
Operating Your Text Display (TD) Device 5
5.1 Overview
Operating Your TD Device
Included in this chapter is information about routine operator tasks, such as entering and
releasing the password, editing variables embedded in a message or screen, and checking
the status information of the S7-200 CPU. This chapter also describes the less-routine
diagnostic functions provided by the TD device for troubleshooting problems in the S7-200
CPU, such as forcing I/O or changing the operating mode
5.2 Using the Text Display Device to Access Screens and Alarms
Using the TD Device to Access Screens and Alarms
The TD devices allow you to structure information as either screens or bit-enabled alarm
messages. You use the buttons of the keypad of the TD device to navigate through the
screens and menus:
TD 200: Uses the standard TD keypad.
TD 100C, TD 200C, and TD400C: Allow you to change the configuration and use your
own custom-designed keypad. (If there is no custom configuration, the TD 100C,TD 200C
and TD400C defaults to the standard TD keypad configuration.)
Tip
For more information about configuring the functionality of the buttons on the keypad:
Chapter 4 provides information about configuring the buttons for the TD devices. The TD
configuration is downloaded to the S7-200 CPU with your user program.
Chapter 3 provides information about creating a custom keypad layout for the TD device,
and assigning specific functionality for each button. (You then integrate the custom
keypad with the screens and alarm messages as described in Chapter 4.)
Operating Your Text Display (TD) Device
5.2 Using the Text Display Device to Access Screens and Alarms
Text Display (TD) User Manual
102 System Manual, 08/2008, A5E00765548-03
As shown in Figure 5-1 and Figure 5-2, the standard TD keypad provides the following
buttons:
ENTER and Escape (ESC) buttons:
ENTER selects a menu item or confirms a value.
ESC exits from a menu or cancels a selection.
Configurable buttons:
Function keys perform the task that you configured with the Text Display wizard. The
TD 200, TD 200C, and TD400C uses F1 to F4, and the TD 100C uses F1 and F2.
SHIFT on the TD 200, TD 200C and TD400C allows the function keys (F5 to F8) to
perform the task that you configured with the Text Display wizard.
7'&
M
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
6WDQGDUG)DFHSODWH7'&
F1
F9
F5
F13
F2
F10
F6
F14
F3
F11
F4
F12
F8
F16
SHIFT
ESC
ENTER
SHIFT, ENTER and ESC
F15
F7
6,(0(16
)
) )
) )
) )
)
6+,)7 (17(5
(6&
6WDQGDUG)DFHSODWH7'&
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
DQG6+,)7
(17(5
DQG(6&
6WDQGDUG)DFHSODWH7'&
6,(0(16
7'&
) )
(17(5
(6&
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV (17(5
DQG(6&
6,(0(16
6,(0(16
)
) )
) )
) )
)
6+,)7 (17(5
(6&
6WDQGDUG)DFHSODWH7'
7H[WGLVSOD\DUHD $UURZEXWWRQV
&RQILJXUDEOHEXWWRQV
DQG6+,)7
(17(5
DQG(6&
Figure 5-1 Standard TD Keyboards
Operating Your Text Display (TD) Device
5.2 Using the Text Display Device to Access Screens and Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 103
Arrow buttons:
UP arrow scrolls (upwards) through menu items or increments a value that can be
edited.
DOWN arrow scrolls (downwards) through menu items or decrements a value that can
be edited.
LEFT and RIGHT arrows move the cursor left or right within the message (TD 100C,
TD 200C, and TD400C only). For a TD 200, use SHIFT+DOWN to move right and
SHIFT+UP to move left. You can also use ENTER to move to the next variable
message.
To select a menu item, use the UP and DOWN arrows to scroll through the list of available
items. The TD device highlights the menu item.
Pressing ENTER selects the highlighted item.
Pressing ESC returns to the previous menu or screen.
Display Backlight on the TD400C
The TD400C allows you to set the amount of time that the display backlight is on. This allows
you to extend the life of theTD400C by turning off the backlight when the display is not
needed.
You can configure the TD400C display backlight on time:
From 1 to 59 minutes in 1 minute increments
Always on
1, 2, 4, or 8 hours
Default on time (10 minutes)
The backlight will turn on when:
The TD400C is powered on
The S7-200 CPU forces a reset of the TD400C with the TD_Reset bit in the TD parameter
block.
You press a key. The time is extended each time a key is pressed.
A new alarm is read from the S7-200 CPU
When the display backlight is turned on, the backlight is on for the time that you configured in
the TD Setup menu.
If the backlight is currently off and you press a key, the first keypress will turn on the
backlight, but will not execute the key function. You must press the key a second time to
execute the key function. There will be no audio or visual feedback for the first keypress that
turns on the backlight. This lets you know that the key did not execute the key function and
you must press the key again.
If your TD400C has an alarm that requires acknowledgement (an alarm that flashes or
blinks), and that alarm is enabled, the display backlight will be on until you acknowledge the
alarm.
Operating Your Text Display (TD) Device
5.2 Using the Text Display Device to Access Screens and Alarms
Text Display (TD) User Manual
104 System Manual, 08/2008, A5E00765548-03
Displaying Information on the TD Device
The TD device provides both screens (user-defined menus with associated screens of
information) and bit-enabled alarm messages:
Menu: A menu is a list of items that select a grouping of related screens. The TD 200,
TD 200C and the TD400C have 8 menus available; the TD 100C has 4 menus available
Screen or alarm:
A screen or alarm for the TD 200 and TD 200C displays up to two lines of text that
provide information for the operator. Each line can be up to 20 characters of text and
data. A screen contains up to 40 characters of text and data. An alarm can be either 1
or 2 lines.
A screen or alarm for the TD400C displays up to four lines of text that provide
information for the operator. Each line can be up to 24 characters of text and data. A
screen contains up to 96 characters of text and data. An alarm can be either 1, 2, or 4
lines.
A screen or alarm for the TD 100C displays up to four lines of text that provide
information for the operator. (Each line can contain either 12 or 16 characters of text
and data. A screen contains 48 or 64 characters of text and data. An alarm can be
either 1 or 2 lines.)
The textual message of the screen or alarm can convey information for the operator
and can also allow the operator to interact with the S7-200 CPU by changing the
embedded value of a variable (such as a set point or limit).
You can configure the TD device to display screens (which are initiated by operator action)
and bit-enabled alarms (which are generated by the S7-200 CPU). You can also configure
the TD 200 and TD 200C, and TD400C device to display an icon to alert the operator of
some event or action required. (Refer to Chapter 4 for information about configuring the TD
device.)
Tip
Pressing ESC returns you to the previous menu. If there is no activity for 20 seconds (no
button pressed), the TD device returns to the default display mode.
The operator uses the buttons on the keypad to navigate through the menu or a list of text.
Figure 5-2 shows the buttons that an operator could use to navigate from a user menu to the
screens associated with that item in the menu. Figure 5-3 shows how to navigate through the
alarms. The TD 200, TD 200C, and the TD400C have eight menus available, and the
TD 100C has four menus available.
Operating Your Text Display (TD) Device
5.2 Using the Text Display Device to Access Screens and Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 105
7KH83$UURZVFUROOVXS
WKURXJKWKHOLVWDQGZUDSV
WRWKHODVWLWHP 7KH83$UURZVFUROOVXS
WKURXJKWKHOLVWDQGZUDSVWR
WKHODVWVFUHHQ
(17(5GLVSOD\V
WKHVFUHHQV
(6&UHWXUQVWR
WKHXVHUPHQX
7KH'2:1$UURZVFUROOV
GRZQWKURXJKWKHOLVWDQG
ZUDSVWRWKHILUVWVFUHHQ
7KH'2:1$UURZVFUROOVGRZQ
WKURXJKWKHOLVWDQGZUDSVWR
WKHILUVWLWHP
6FUHHQ
&DQEHLQWHUDFWLYH
6FUHHQ
&DQEHLQWHUDFWLYH
6FUHHQ
&DQEHLQWHUDFWLYH
6FUHHQ
&DQEHLQWHUDFWLYH
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
8VHUPHQXLWHP
(QWHU
(6&
Figure 5-2 Using the Keypad to Navigate between User Menus and Screens
(QWHU
6&38
:KHQDQDODUPELWWXUQVRQWKH
6&38ZULWHVWKHDVVRFLDWHG
DODUPPHVVDJHWRWKH7'GHYLFH
7KH7'GHYLFHOLVWVWKHDODUPV
DFFRUGLQJWRSULRULW\
(17(5DFNQRZOHGJHVWKHDODUPDQG
UHVHWVWKHDODUPELWLQWKH6&38
7KH83$UURZVFUROOVXSWKURXJK
WKHOLVWRIDODUPVDQGZUDSVWRWKH
ODVWDODUP
7KH'2:1$UURZVFUROOVGRZQWKURXJK
WKHOLVWRIDODUPVDQGZUDSVWRWKHILUVW
DODUP
$ODUPKLJKHVWSULRULW\
$ODUP
$ODUP
$ODUP
$ODUPORZHVWSULRULW\
Figure 5-3 Displaying and Acknowledging Alarms
Operating Your Text Display (TD) Device
5.3 Accessing the Menus and Screens
Text Display (TD) User Manual
106 System Manual, 08/2008, A5E00765548-03
Using the TD Device to Edit Variables in the S7-200 CPU
A screen or alarm message can contain an embedded variable field that allows an operator
to respond by changing the value of the variable. The operator uses the keypad to edit
variables:
Selecting the Screen: The operator uses the UP or DOWN arrows to display the screen
that contains the variable to be edited. (From a menu, the operator presses ENTER to
access the group of screens.)
Navigating to the variable: The operator presses ENTER to navigate to the first editable
variable.
Changing the value of the variable: Pressing the UP arrow increments (increases) the
value, and pressing the DOWN arrow decrements (decreases) the value. (Pressing and
holding the UP or DOWN arrow accelerates the operation.) Pressing both SHIFT+ENTER
resets the variable to 0. Pressing ESC aborts the edit.
Press LEFT or RIGHT to move the cursor position within the variable. The TD 200 uses
SHIFT+UP to move left and SHIFT+DOWN to move right.
Updating the data in the S7-200 CPU: Pressing ENTER writes the updated value for the
variable to the S7-200 CPU and moves the cursor to the next editable variable on the
screen.
For more information about editing variables, see the section Editing a Variable that is
Embedded in an Alarm or a Screen in this chapter.
5.3 Accessing the Menus and Screens
Accessing the Menus and Screens
When you configured the TD device (as described in Chapter 4), you created the screens
and alarms for the TD device. If you configured both alarms and screens, you also
designated which type of message (screens or the alarms) would be the default display
mode for the TD device. After power-up or after a period of inactivity, the TD device returns
to the default display mode.
In addition to the screens and alarms that you configured, the TD device provides standard
functions that the operator can access from system-level and pre-defined menus. From the
default display mode, the operator uses ESC to access the menu hierarchy. The operator
then presses ENTER to select the menu item for accessing the other menus or functions.
Figure 5-5 and Figure 5-6 show the hierarchy of menus for these functions for the TD
devices. (The menus show all of the functions that are available on the TD device. For some
of the functions to be listed on the menu, you must have enabled the function during
configuration. See Chapter 4.)
Operating Your Text Display (TD) Device
5.3 Accessing the Menus and Screens
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 107
(6& (6&
(6&
(6&
(6&
(6&
'HIDXOW'LVSOD\0RGH
6FUHHQV
'HIDXOWVFUHHQ
3UHVV(6&WRGLVSOD\WKH8VHU
0HQXRIWKHVFUHHQV
8VHU0HQXRIWKH6FUHHQV
6FUHHQV
6FUHHQV
8SWRHQWULHV
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
0DLQ0HQX
'LVSOD\$ODUPV
2SHUDWRU0HQX
'LDJQRVWLF0HQX
5HOHDVH3DVVZRUG
3UHVV(6&WRUHWXUQWRWKH
GHIDXOWGLVSOD\PRGH
6HFRQGDU\'LVSOD\
$ODUPV&DQEHFRQILJXUHGDV
GHIDXOWVFUHHQ
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
2SHUDWRU0HQX
&386WDWXV
6HW7LPHDQG'DWH
6HW/DQJXDJH
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
'LDJQRVWLF0HQX
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH&380RGH
0DNH0HPRU\&DUWULGJH
(GLW&380HPRU\
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
Figure 5-4 Menu Hierarchy for the TD 200, TD 200C, and TD400C
Operating Your Text Display (TD) Device
5.3 Accessing the Menus and Screens
Text Display (TD) User Manual
108 System Manual, 08/2008, A5E00765548-03
(6&
(6&
(6&
(6&
'HIDXOW'LVSOD\0RGH
6FUHHQV
'HIDXOWVFUHHQ
3UHVV(6&WRGLVSOD\WKH8VHU
0HQXRIWKHVFUHHQV
8VHU0HQXRIWKH6FUHHQV
6FUHHQV
6FUHHQV
6FUHHQV
6FUHHQV
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
0HQX
6HFRQGDU\'LVSOD\
$ODUPV&DQEHFRQILJXUHGDV
GHIDXOWVFUHHQ
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
'LVSOD\$ODUPV
&386WDWXV
6HW7LPH
5HOHDVH3DVVZRUG
&OHDQ.H\SDG
7'6HWXS
3UHVV(6&WRUHWXUQWRWKH
GHIDXOWGLVSOD\PRGH
Figure 5-5 Menu Hierarchy for the TD 100C
Operating Your Text Display (TD) Device
5.4 Entering and Releasing a Password
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 109
5.4 Entering and Releasing a Password
Entering and Releasing a Password
You use the Text Display wizard of STEP 7-Micro/WIN to configure the password for the TD
device. Refer to Chapter 4 for information about configuring the TD device. To ensure that
an unauthorized user does not have access to the TD device during an interval for the
automatic time-out, you can use the Release Password feature.
Certain operations (such as forcing I/O or making a memory cartridge) may also require that
the operator enter the 8-character CPU password for the S7-200 CPU. (You must have
enabled the S7-200 CPU for password-protection in order for the TD device to prompt the
operator for the CPU password.)
Entering the Password
If configured for a password, the TD device prompts the operator to enter the 4-digit
password before allowing the operator to access screens or menus. If the password uses
fewer than 4 digits, the operator must press ENTER for the unused (remaining) characters.
Use the UP or DOWN arrow to select each digit of the password, pressing ENTER to move
to the next digit. You can also use the RIGHT and LEFT arrows to move within the
password.
The TD device provides a time-out feature which automatically restores password protection
after a period of inactivity. If no buttons have been pressed after 2 minutes, the TD device
then requires a password again before allowing an operator to access menus or to edit
variables.
Releasing the Password
In order to provide additional security for your application, the TD device provides a Release
Password command that immediately restores the password-protection. The TD device then
requires that the operator enter the password before allowing access. The Release
Password command prohibits another person from using the TD device without first entering
a password (for example, before a password entered by an operator times out).
You access the Release Password command from the main menu, as shown in figure below.
The Release Password is not applicable for the CPU password: The TD device releases the
CPU password as soon as the operator exits the function that required the password.
For example: If the operator entered the CPU password in order to force an I/O point in the
S7-200 CPU, the TD device releases the CPU password as soon as the operator exits the
Force menu.
The Release Password command is available only if you defined a 4-digit password when
you configured the TD device.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
110 System Manual, 08/2008, A5E00765548-03
'LVSOD\$ODUPV
2SHUDWRU0HQX
'LDJQRVWLF0HQX
5HOHDVH3DVVZRUG
Figure 5-6 Release Password Command
5.5 Viewing the Screens and the Alarms
Viewing the Screens and the Alarms
As described in Chapter 4, you can configure screens and alarms for the TD device. If you
configure both alarms and screens, you also designate which set of messages (screens or
alarms) are the default display mode for the TD device. The default configuration selects the
screens to be the default display.
After power-up or after a period of inactivity (one minute), the TD device returns to the
default display mode. As shown in the figures below, the operator can switch between the
default display mode and the secondary display mode.
Tip
For the TD 100C, TD 200C, and the TD400C: If you do not configure buttons for ESC or
ENTER, you cannot access the main menu.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 111
(6&
(6&
(6&
(6&
(QWHU
(QWHU
7'7'&DQG7'&6FUHHQV8SWR6FUHHQV(DFKIRU8SWR*URXSV
3UHVV(6&WRGLVSOD\WKH8VHU
0HQXRIWKHVFUHHQV
6FUHHQ
8VHWKH83RU'2:1DUURZ
EXWWRQWRVFUROOWKURXJKWKH
VFUHHQVIRUWKLVJURXS
8VHU0HQX
8VHUPHQXLWHP
8VHUPHQXLWHP
8SWRHQWULHV
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
6FUHHQV
'HIDXOW'LVSOD\0RGH
0DLQ0HQX
3UHVV(6&WRGLVSOD\WKH
GHIDXOWGLVSOD\
'LVSOD\$ODUPV
2SHUDWRU0HQX
'LDJQRVWLF0HQX
5HOHDVH3DVVZRUG
%LW(QDEOHG$ODUPV
6HFRQGDU\'LVSOD\
$ODUPPHVVDJH
8VHWKH83RU'2:1DUURZ
EXWWRQVWRVFUROOWKURXJKWKHOLVW
RIDODUPPHVVDJHV

Figure 5-7 TD 200, TD 200C, and TD400C - Navigating between the Default and Secondary
Displays
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
112 System Manual, 08/2008, A5E00765548-03
(6&
(6&
(6&
(6&
(QWHU
(QWHU
7'&6FUHHQV8SWR6FUHHQV(DFKIRU8SWR*URXSV
3UHVV(6&WRGLVSOD\WKH8VHU
0HQXRIWKHVFUHHQV
8VHU0HQX
6FUHHQ
8VHWKH83RU'2:1DUURZ
EXWWRQWRVFUROOWKURXJKWKH
VFUHHQVIRUWKLVJURXS
6FUHHQV
'HIDXOW'LVSOD\0RGH
3UHVV(6&WRGLVSOD\WKH
0DLQ0HQX
8VHUPHQXLWHP

8SWRHQWULHV
8VHUPHQXLWHP
0DLQ0HQX
3UHVV(6&WRGLVSOD\WKH
GHIDXOWGLVSOD\
'LVSOD\$ODUPV
&386WDWXV
6HW7LPH
5HOHDVH3DVVZRUG
&OHDQ.H\SDG
7'6HWXS
6HFRQGDU\'LVSOD\
%LW(QDEOHG$ODUPV
$ODUPPHVVDJH
8VHWKH83RU'2:1DUURZ
EXWWRQVWRVFUROOWKURXJKWKHOLVW
RIDODUPPHVVDJHV
3UHVV(6&WRGLVSOD\
WKH0DLQ0HQX
Figure 5-8 TD 100C - Navigating between the Default and Secondary Displays
Displaying the Alarms
If you created both screens and alarms when you configured the TD device, the main menu
of the TD device includes a command that allows you to access the secondary (non-default)
display. The TD device always returns to the default display mode after a period of inactivity.
As shown in the TD 200C example in the figure below, the main menu provides a Display
Alarms command for the default TD configuration. If you configured alarms as the default
display, the main menu lists a User Menu entry.
After displaying the alarms, you use the UP and DOWN arrows to scroll through the
sequential list of alarms.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 113
'LVSOD\$ODUPV
2SHUDWRU0HQX
'LDJQRVWLF0HQX
5HOHDVH3DVVZRUG
Figure 5-9 Displaying the Alarms
Tip
The TD 100C, TD 200C, and the TD400C allow you to configure a button specifically for
displaying alarms when you are creating your custom keypad.
The TD device displays the highest priority alarm. The TD device displays an up or down
arrow with the alarm to alert the operator that other alarms have been enabled. (The up
arrow shows that higher-priority alarms have been enabled, and the down arrow shows that
lower-priority alarms have been enabled.)
After reading a new alarm from the S7-200 CPU, the TD device sorts the alarms again to
display the highest priority alarms at the top of the list. The TD device determines the priority
based on the sequence of the alarms in the parameter block:
The first alarm that you created has the highest priority.
The second alarm that you created has the second-highest priority.
The last alarm that you created has the lowest priority.
Tip
You can scroll up and down through the list of enabled alarms. However, the TD device
returns to the highest-priority alarm after a period of inactivity: If you have not pressed a
button for 10 seconds while the TD device has displayed the current alarm, then the TD
device automatically returns to the highest-priority alarm.
Acknowledging an Alarm
If an alarm requires acknowledgement, the TD device does not remove that alarm until you
acknowledge the alarm:
1. Use the UP or DOWN arrow to select the alarm.
2. Press ENTER to acknowledge the alarm.
Types of Alarms
The Text Display wizard allows you to determine the type interaction required by the
operator for an alarm. If the user screens are set as the default display mode for the TD
device and an alarm is enabled, an alarm indicator will begin to flash on the TD display. The
indicator is large if there is an alarm enabled that requires acknowledgement. The indicator
will be small if the alarms do not require acknowledgement. The user can switch to the alarm
display to view the alarms.
The alarm display will show one or more alarms in priority order. An UP or DOWN arrow in
the right-most character position indicates more alarms are active, but not visible on the
display. The operator can press either the UP or the DOWN arrow key to scroll through the
other enabled alarms.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
114 System Manual, 08/2008, A5E00765548-03
The operator can edit or accept variable values by pressing the ENTER key. The TD device
will write the updated variable value to the CPU and set the edit notification bit for that
variable when the operator presses the ENTER key. The TD device then moves the cursor
to the next editable variable. Pressing ENTER for the last editable variable of an alarm writes
this last value to the S7-200 CPU and the TD device then resets the alarm enable bit. For
more information on editing variables, see Editing a Variable that is Embedded in an Alarm
or a Screen in Chapter 5.
Every alarm falls into one of four possible alarm acknowledgement and editing types. This
section explains specifically how each alarm type is handled by the TD device. The four
alarm types follow:
No acknowledgement required. No edits allowed
Acknowledgement required. No edits allowed
No acknowledgement required. Edits allowed
Acknowledgement required. Edits allowed
No Acknowledgement Required, No Edits Allowed
In this combination of no acknowledgement required and no edits allowed, the TD device
simply displays the alarm. The ENTER key has no function since there are no editable
variables within the alarm. The alarm may contain variables that are updated at the update
rate of the TD device. This type of alarm is replaced on the display if a higher priority alarm is
enabled by the S7-200 CPU. The operator can either press the UP or the DOWN arrow key
to scroll to other alarms or press ESC to return to the menus.
The TD device does not clear the corresponding alarm-enable bit in the S7-200 CPU.
Acknowledgement Required, No Edits Allowed
In this combination of acknowledgement required and no edits allowed, the TD device
displays the alarm and makes the entire alarm flash (blink) until the operator presses ENTER
to acknowledge the alarm. Variable values are updated from the S7-200 CPU at the normal
update rate while the alarm is flashing.
When the operator presses ENTER, the TD device:
Sets the acknowledgement-notification bit for this alarm.
Clears the alarm-enable bit for this alarm. This causes the alarm to be removed from the
display on the next update cycle.
Another alarm cannot replace the one flashing until the operator acknowledges the flashing
alarm. This is also true even if a higher priority alarm is enabled in the S7-200 CPU. If the TD
device is configured for single line alarms and the CPU enables a higher priority alarm, the
flashing alarm shifts down to the next line of the display. The operator cannot press the UP
or the DOWN key to scroll through other enabled alarms until the current alarm is
acknowledged.
No Acknowledgement Required, Edits Allowed
In this combination of no acknowledgement required and edits allowed, the TD device
displays a alarm and then waits for the operator to edit a value in the alarm. All of the
variables within the alarm are updated at the update rate. Since the alarm does not require
acknowledgement, this type of alarm is removed from the TD device display if a higher
priority alarm is enabled in the S7-200 CPU.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 115
Acknowledgement Required, Edits Allowed
In this combination of acknowledgement required and edits allowed, the TD device displays
the alarm, causes the entire alarm to flash (blink), and then waits until the operator
acknowledges the alarm and edits or accepts the values in the alarm. This type of alarm
requires that the operator edits or accepts the values displayed in the alarm. If the operator
aborts the edit by pressing the ESC key before editing all the values in the alarm, the alarm
flashes to indicate that edits are still required.
When the alarm is enabled in the S7-200 CPU, the TD device notes this and, if there is
space available on the display, reads the alarm from the CPU. The TD device then displays
the alarm and causes the entire alarm to flash to notify the operator that the alarm is present
and must be acknowledged.
Clearing an Alarm
If an alarm required acknowledgement, the TD device will clear the alarm enable at the
same time that the Alarm Acknowledgement bit is set in the CPU.
If an alarm contains editable variables, the TD device will clear the alarm enable bit when
all of the edits are completed and the last editable variable in the messages is written to
the CPU.
The PLC program logic may clear the alarm enable bit at any time. This will remove the
alarm message from the TD display. An alarm message will not be removed from the
display if the user is editing a variable in the message or if the message has not yet been
acknowledged.
If the message does not require acknowledgement and/or does not contain editable
variables, then the CPU program logic MUST clear the alarm enable bit.
Editing a Variable that is Embedded in an Alarm or a Screen
If you configured a screen or an alarm to include a variable, you can enter a new value for
the variable:
Use ENTER to move the cursor to the variable. The TD device will write the updated
variable value to the CPU and set the edit notification bit for that variable when the
operator presses the ENTER key, completing the edit of the variable.
Use the UP or DOWN arrows to change the value of the variable.
Use the following buttons to move the cursor to different characters within the variable:
TD 100C, TD 200C, and TD400C: LEFT and RIGHT arrows
TD 200: SHIFT+UP arrow and SHIFT+DOWN arrow
ESC rereads the value of the variable from the S7-200 CPU and redisplays the value.
ENTER writes the new value to the S7-200 CPU. (If the alarm contains other variables,
the cursor moves to the next variable.) The TD device will write the updated variable
value to the CPU and set the edit notification bit for that variable when the operator
presses the ENTER key, completing the edit of the variable.
If the variable was configured as a numeric string, the cursor skips over any non-numeric
characters in the message. See Chapter 4. After you have edited all of the variables in an
alarm, the TD device resets the alarm bit in the S7-200 CPU.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
116 System Manual, 08/2008, A5E00765548-03
Notice
Due to restrictions in the format used to store real (floating-point) numbers in both the S7-
200 CPU and the TD device, the accuracy of the number is limited to six significant digits.
Editing a real number with more than six digits may not change the value of the variable, or
may cause other digits within the number to change:
Changing the least significant (right-most) digit of a real-number variable with more than
six digits may have no effect. For example, if you try to change the "9" in "1234.56789",
the value of the variable does not change.
Changing the most significant (left-most) digit of a real-number variable with more than
six digits may cause other (less significant) digits in the variable to change.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 117
TD Bit Usage
A summary of the TD bit usage is shown in Table 5-1.
Table 5- 1 Summary of TD Bit Usage
Bits Associated
with Alarms and
Screens
Enable Condition
for the Bit
Results shown on the TD Display Clear Condition for the Bit
ALARM ENABLE The alarm must be
enabled with the
TD_ALRM
instruction using
the Alarm
Symbolic Name as
the instruction
input.
When an alarm is enabled and the TD default
display mode is set to the alarm mode, the alarm
message is placed on the TD display. If there are
multiple alarms enabled, the highest priority
alarm is displayed.
If an alarm requires user acknowledgment, the
message will flash (blink) until it is acknowledged
by the user. The alarm MUST be acknowledged
before other alarms can be viewed. An alarm that
requires acknowledgement will not be replaced
on the display by higher priority alarms until the
alarm is acknowledged.
If the alarm contains editable variables the user
can edit or accept the values (by pressing the
ENTER key). If the edits are not completed, and
the alarm message required acknowledgement,
the message will again begin to flash.
If the user screens are set as the default display
mode for the TD device and an alarm is enabled,
an alarm indicator will begin to flash on the TD
display. The indicator is large if there is an alarm
enabled that requires acknowledgement. The
indicator will be small if the alarms do not require
acknowledgement. The user can switch to the
alarm display to view the alarms. The alarms will
be presented to the user in priority order.
There are different ways to
clear the alarm enable bit:
If an alarm required
acknowledgement, the TD
device will clear the alarm
enable at the same time that
the 'Alarm
Acknowledgement' bit is set
in the CPU.
If an alarm contains editable
variables, the TD device will
clear the alarm enable bit
when all of the edits are
completed and the last
editable variable in the
messages is written to the
CPU.
The PLC program logic may
clear the alarm enable bit at
any time. This will remove
the alarm message from the
TD display. An alarm
message will not be removed
from the display if the user is
editing a variable in the
message or if the message
has not yet been
acknowledged.
If the message does not
require acknowledgement
and/or does not contain
editable variables, then the
CPU program logic MUST
clear the alarm enable bit.
Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
118 System Manual, 08/2008, A5E00765548-03
Bits Associated
with Alarms and
Screens
Enable Condition
for the Bit
Results shown on the TD Display Clear Condition for the Bit
ALARM
ACKNOW-
LEDGE
Alarm
acknowledgement
is available only if
the wizard
configuration has
the option enabled
for this alarm:
Alarm should
require operator
acknowledgement
The user acknowledges an alarm message by
scrolling to the message and pressing the
ENTER key. The TD device will then set the
acknowledge notification bit in the CPU and the
alarm message will stop flashing (blinking).
If there are no editable variables in the message
the TD device will also clear the alarm enable bit
for this message.
If there are editable variables in the message, the
user must either edit the variables (change them
and press ENTER) or accept the current values
(press ENTER). When the last variable in the
message is edited or accepted, the TD device will
write the variable to the CPU and clear the alarm
enable bit.
If the user does not complete editing the
variables in the message, the TD device will
begin to flash (blink) the message to notify the
user that an action is still pending.
The TD device will set the
alarm acknowledge bit. The
user program logic must
clear the alarm
acknowledgement bit.
Operating Your Text Display (TD) Device
5.6 Performing Typical or Routine Operator Tasks
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 119
Bits Associated
with Alarms and
Screens
Enable Condition
for the Bit
Results shown on the TD Display Clear Condition for the Bit
ALARM
MESSAGE:
EMBEDDED
VARIABLE EDIT
NOTIFICATION
The edit
notification is
available only
when the alarm
contains a variable
and the user has
enabled the
Wizard option to
allow editing of the
variable. "Operator
is allowed to edit
this data". If the
alarm message
contains multiple
editable variables,
each variable has
a unique edit
notification bit.
The TD device will write the updated variable
value to the CPU and set the edit notification bit
for that variable when the operator presses the
ENTER key, completing the edit of the variable.
The user program can
monitor the edit notification
bit to recognize when an
editable value has been
changed by the operator.
The user program can then
take some action based on
the new value for the
variable.
The user program must clear
the edit notification bit so that
subsequent edits can be
recognized.
USER SCREEN:
EMBEDDED
VARIABLE EDIT
NOTIFICATION
The edit
notification is
available only
when the user
screen contains a
variable and the
user has enabled
the Wizard option
to allow editing of
the variable.
"Operator is
allowed to edit this
data".
If the user screen
contains multiple
editable variables,
each variable has
a unique edit
notification bit.
The TD device will write the updated variable
value to the CPU and set the edit notification bit
for that variable when the operator presses the
ENTER key, completing the edit of the variable.
The user program can
monitor the edit notification
bit to recognize when an
editable value has been
changed by the operator.
The user program can then
take some action based on
the new value for the
variable.
The user program must clear
the edit notification bit so that
subsequent edits can be
recognized.
5.6 Performing Typical or Routine Operator Tasks
Performing Typical or Routine Operator Tasks
The Operator Menu allows you to perform the following tasks:
Determining the model and version of the S7-200 CPU (CPU Status)
Viewing the error messages generated by the S7-200 CPU (CPU Status)
Operating Your Text Display (TD) Device
5.6 Performing Typical or Routine Operator Tasks
Text Display (TD) User Manual
120 System Manual, 08/2008, A5E00765548-03
Setting the time in the S7-200 CPU (Set Time and Date)
Selecting a language set for the TD device (Set Language) (TD 200, TD 200C, and
TD400C)
'LVSOD\$ODUPV
2SHUDWRU0HQX
'LDJQRVWLF0HQX
5HOHDVH3DVVZRUG
&386WDWXV
6HW7LPHDQG'DWH
6HW/DQJXDJH
Figure 5-10 Operator Menu for TD 200, TD 200C, and TD400C
Viewing the Status of an S7-200 CPU
The CPU Status command allows you to display the following information:
Model and version of the S7-200 CPU
Error messages generated by the S7-200 CPU
After you select the CPU Status command, the TD device displays the CPU model and
version.
Press the UP or DOWN arrows to display the error messages that were generated by the
S7-200 CPU.
The TD device displays an error message only if an error exists in the S7-200 CPU. The
CPU classifies errors as either fatal errors or non-fatal errors.
'LVSOD\$ODUPV
&386WDWXV
6HW7LPH
5HOHDVH3DVVZRUG
Figure 5-11 CPU Status Menu for TD 100C
Table 5-2 lists the error messages that can be displayed by the TD devices. Refer to the
SIMATIC S7-200 Programmable Controller System Manual for information about specific
errors.
Operating Your Text Display (TD) Device
5.6 Performing Typical or Routine Operator Tasks
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 121
Table 5- 2 Error Messages Relating to the Status of the S7-200 CPU
Type Message Description
Program Checksum Error Hardware failure (S7-200 CPU)
Compare Contact User program error: Illegal Compare contact
EEPROM/Permanent Memory Failure Hardware failure (S7-200 CPU)
Memory Cartridge Failure Memory cartridge failure
Scan Watchdog Timeout Hardware failure (S7-200 CPU)
Fatal
Unknown Error XXXX
(where XXXX = the error number)1
CPU failure (S7-200 CPU)
Non-
Fatal
I/O Error Mod X
(where X = the number of the I/O
module)
An expansion module encountered an I/O error.
If there are multiple failures, the TD device
displays this message multiple times one time for
each failed module.
Runtime Error XXXX
(where XXXX = the error number)1
The S7-200 CPU encountered an error while
executing the user program, such as:
Indirect addressing
HSC setup and execution errors
Attempting to execute an illegal instruction
(ENI, DISI, or HDEF) inside an interrupt routine
Subroutine nesting errors
TODW data errors
Simultaneous Transmit (XMT) and Receive
(RCV) errors
1 Refer to the SIMATIC S7-200 Programmable Logic Controller System Manual for information about
specific errors.
Setting Time and Date in the S7-200 CPU
You can use the TD device to change the time-of-day settings in the S7-200 CPU. This
allows an operator to easily adjust for time changes.
The TD device does not maintain time and date settings. In order to display the time and
date values, the TD device reads the current time and date from the S7-200 CPU and
displays these values. The operator can then use this screen to edit these values and then
write the new time and date settings back to the S7-200 CPU.
Tip
The TD device does not validate the time, date or day of the week values that you enter. You
can inadvertently write an incorrect date or day of the week to the S7-200 CPU.
To allow an operator to change the time and date settings in the S7-200 CPU:
You must have enabled (selected) the time-of-day (TOD) option when you configured the
TD device with the Text Display wizard. Refer to Chapter 4.
The S7-200 CPU must support the TOD clock
Tip
If you configured a password for the TD device, the operator must enter the password before
being allowed to set the time and date.
Operating Your Text Display (TD) Device
5.6 Performing Typical or Routine Operator Tasks
Text Display (TD) User Manual
122 System Manual, 08/2008, A5E00765548-03
If the TD device was not configured to allow changes to the time or if the S7-200 CPU does
not support the TOD clock, the Set Time and Date command does not appear on the
Operator Menu.
After you select the Set Time command, the TD device reads the current date and time from
the S7-200 CPU.
The Time and Date screen displays the following information:
Date: day-month-year (for Chinese, the date is displayed as year-month-day)
Time
Day of the week
'LVSOD\$ODUPV
2SHUDWRU0HQX
'LDJQRVWLF0HQX
5HOHDVH3DVVZRUG
&386WDWXV
6HW7LPHDQG'DWH
6HW/DQJXDJH
Figure 5-12 Setting the Time and Date on the TD 200, TD200C, and TD400C
Use the UP or DOWN arrow buttons to change the values in the fields.
Use the ENTER to move to the next field. (For a TD 100C, TD 200C, and TD400C, you can
also use the RIGHT arrow. For a TD 200, you can use the SHIFT+DOWN arrow.)
Use the ESC to move back to the first field. (For a TD 100C, TD 200C, and TD400C, you
can also use the LEFT arrow. For a TD 200, you can use the SHIFT+UP arrow.)
'LVSOD\$ODUPV
&386WDWXV
6HW7LPH
5HOHDVH3DVVZRUG
Figure 5-13 Setting the Time and Date on the TD 100C
Pressing ENTER when the cursor is located on the last field of the Time and Date screen
writes the new time and date values to the S7-200 CPU and returns to the Operator Menu.
Pressing ESC when the cursor is located on the first field of the Time and Date screen
returns to the Operator Menu.
Operating Your Text Display (TD) Device
5.6 Performing Typical or Routine Operator Tasks
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 123
Changing the Language Set (TD 200C, TD 200, and TD400C only)
You can use the TD device to change the language set in order to localize the TD device for
another country. You must have created different language sets for your alarms and screens
when you configured the TD device with the Text Display wizard. Each language set that you
configure selects the language for the system menus and prompts of the TD device, as well
as the screens and alarms. Refer to Chapter 4 for information about configuring language
sets for the TD device.
Selecting the Set Language command displays a menu of the languages that you configured
with the Text Display wizard as shown in the figure below. Use the UP or DOWN arrows to
select the language to be displayed by the TD device.
'LVSOD\$ODUPV
2SHUDWRU0HQX
'LDJQRVWLF0HQX
5HOHDVH3DVVZRUG
&386WDWXV
6HW7LPHDQG'DWH
6HW/DQJXDJH
/DQJXDJH
/DQJXDJH

FRQILJXUHGODQJXDJHV
Figure 5-14 Selecting One of the Language Sets Configured for the TD Device
Cleaning the Keypad
The Clean Keypad function disables the keypad for 30 seconds to allow you to clean the
keypad without affecting TD operation. The TD device displays a count down timer that
shows the remaining seconds.
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
124 System Manual, 08/2008, A5E00765548-03
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Some of the pre-configured tasks provided by the TD device provide assistance with setting
up the TD device or troubleshooting problems with the S7-200 CPU. These functions are
typically accessed infrequently. See the figures below.
7'$GGUHVV
&38$GGUHVV
3DUDPHWHU%ORFN$GGUHVV
%DXG5DWH
+LJKHVW6WDWLRQ
*DS)DFWRU
&RQWUDVW
)RUFH,QSXW
)RUFH2XWSXW
8QIRUFH$OO,2
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH&380RGH7'&7'&
0DNH0&7'&7'&
(GLW&380HPRU\7'&7'&
'LVSOD\$ODUPV
2SHUDWRU0HQX
5HOHDVH3DVVZRUG
'LDJQRVWLF0HQX
6SDVVZRUGUHTXLUHG
LIFRQILJXUHG
Figure 5-15 TD 200, TD 200C, and TD400C Diagnostic Menu Hierarchy
&386WDWXV
6HW7LPH
5HOHDVH3DVVZRUG
&OHDQ.H\SDG
7'6HWXS
Figure 5-16 TD 100C Diagnostic Menu Hierarchy
Tip
If you are using a custom keypad that does not support the ENTER and ESC buttons, you
must use the standard keypad to set up the TD device.
To restore the standard TD keypad:
1. Power down the TD device
2. Press and hold the lower right corner (where ENTER key is located on the standard
keypad)
3. Power up the TD device
The default keypad is restored until the TD device is power cycled again.
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 125
Setting up the TD Device
As shown in the figure below, you use the TD Setup menu to configure various parameters
for the TD device, such as network addresses, address of the parameter block (stored in V
memory of the S7-200 CPU), baud rate, and other communication parameters.
Setting the network address for the TD device: Use the UP or DOWN arrow to set the
network address (default address = 1).
Setting the CPU address: Use the UP or DOWN arrow to select the network address for
the S7-200 CPU (default = 2).
Setting the address for the parameter block: Designates a V memory location where the
parameter block (or an offset to the location of the parameter block) is stored in the S7-
200 CPU. Setting the address of the parameter block allows you to connect multiple TD
devices to a single S7-200 CPU.
Use the UP or DOWN arrow to select the starting V memory address of the parameter
block that stores the configuration of the TD device.
The address of the parameter block must match the address that you configured in the
S7-200 CPU (address range: VB0 to VB32000, default = VB0).
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH&380RGH
0DNH0&
(GLW&380HPRU\
7'$GGUHVV
&38$GGUHVV
3DUDPHWHU%ORFN$GGUHVV
%DXG5DWH
+LJKHVW6WDWLRQ
*DS)DFWRU
&RQWUDVW
Figure 5-17 TD Setup Menu for the TD 200 and TD 200C
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
126 System Manual, 08/2008, A5E00765548-03
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH&380RGH
0DNH0&
(GLW&380HPRU\
7'$GGUHVV
&38$GGUHVV
3DUDPHWHU%ORFN$GGUHVV
%DXG5DWH
+LJKHVW6WDWLRQ
*DS)DFWRU
.H\SDG%X]]HU
'LVSOD\%DFNOLJKW7LPH
Figure 5-18 TD setup menu for the TD400C
Setting the baud rate for the TD device: choose the baud rate for the TD device. You can
choose either 9.6 kbaud (9600 baud), 19.2 kbaud, or 187.5 kbaud.
Use the UP or DOWN arrow to select the baud rate. The baud rate must match the baud
rate of the S7-200 CPU and any other device on the same network.
Setting the Highest Station: Changes the highest station address for the TD device. This
setting tells the TD device which network addresses to check when looking for other
network master devices. The default highest station address is 31. This means that the
TD device checks addresses 0 through 31 when looking for other network masters. This
setting should only be changed when there are more than 32 master devices on the
network.
Use the UP and DOWN arrows to select the highest address on the network
(default = 31).
Setting the Gap Factor: Changes the Gap Factor for the TD device. This setting tells the
TD device how often to check for other network master devices. The default setting of 10
causes the TD device to check once every 10 messages. A setting of 1 would cause the
TD device to check for other masters after every message.
Use the UP and DOWN arrows to select the gap factor between stations (default = 10).
Setting the contrast:
TD 100C, TD 200, and TD 200C: You can optimize the display for different viewing
angles and lighting conditions by adjusting the contrast of the screen on the TD
device. The default contrast value is 40, with values ranging from 25 (lighter) to 55
(darker).
Use the UP and DOWN arrows to select the contrast setting for the display area of the
TD device (default setting = 40).
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 127
Selecting the keypad buzzer: The TD400C has a keypad buzzer setting (On or Off) to
provide audio feedback when a key is pressed. The default is set to On.
Setting the display backlight time: The TD400C allows you to set the time that the display
backlight is on allowing you to extend the life of the TD400C display.
The backlight on time is configurable from 1 to 60 minutes in one minute increments
You can configure the backlight to be on all the time
The default backlight on time is 10 minutes
Tip
At 9600 baud or 19.2 kbaud, the highest station address may need to be increased, even
though the network does not contain more than 32 masters. Increasing the highest station
address allows more time for the masters to transmit messages.
Viewing the TD Messages Stored in the S7-200 CPU (TD 200, TD 200C, and TD400C only)
You can review all of the TD messages (screens and alarms) that you configured for the TD
device within the language set currently selected for the TD device.
The View Messages command allows you to verify that all of the alarms and screens were
correctly stored in the S7-200 CPU.
The View Messages command does not allow you to edit any values that are displayed in
the messages.
Selecting the View Messages command displays all of the messages and process values
stored in the S7-200 CPU. Use the UP and DOWN arrows to scroll through messages stored
in the S7-200 CPU.
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH67235810RGH
0DNH0&
(GLW&380HPRU\
Figure 5-19 View Messages Command
Forcing the Inputs and Outputs in the S7-200 CPU (TD 200, TD 200C, and TD400C only)
The Force I/O menu allows you to force inputs, force outputs, or unforce all inputs and
outputs. The Force I/O command is available only if you enabled the force-menu when you
configured the TD device with the Text Display wizard.
Caution
Turning off the power to the S7-200 CPU before the force information is written to the
permanent memory in the CPU can cause the S7-200 CPU to experience a failure the next
time you turn the S7-200 CPU on.
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
128 System Manual, 08/2008, A5E00765548-03
To clear the error condition, use the TD device to either unforce all of the I/O points or else
rewrite the force information to the S7-200 CPU. Cycling the power to the S7-200 CPU
should clear the error.
If the S7-200 CPU requires a password before allowing the I/O to be forced, the TD device
prompts the operator to enter the 8-character CPU password.
The Force I/O command provides the following options:
Force Inputs: Allows you to force individual inputs on or off, or to turn off the Force
function
Force Outputs: Allows you to force individual outputs on or off, or to turn off the Force
function
Unforce All I/O: Allows you to turn off the Force function for all of the forced I/O points
Use the UP or DOWN arrow to select the specific I/O point. Pressing ENTER moves the
cursor to the Force options. (For a TD 200C and TD400C, you can also use the RIGHT
arrow. For a TD 200, you can use the SHIFT+DOWN arrow.)
Use the UP or DOWN arrow to select the type of force condition for the selected I/O point.
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH&380RGH
0DNH0&
(GLW&380HPRU\
)RUFH,QSXWV
)RUFH2XWSXWV
8QIRUFH$OO,2
Figure 5-20 Force I/O Command
Tip
Unforcing the I/O points does not place them in the OFF state. Unforcing only removes the
Force option. The points remain in their last state until you manually change them or they are
changed by the user program in the S7-200 CPU.
Changing the Operating Mode of the S7-200 CPU (TD 200C and TD400C)
The Change STOP/RUN Mode command is only available for the TD 200C and TD400C and
is only available if you selected this function when you configured the TD device with the
Text Display wizard. See Chapter 4.
You can use the TD device to change the operating mode of the S7-200 CPU from STOP to
RUN or from RUN to STOP. The operator may need to enter the TD password, if the TD
device is configured for password-protection.
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 129
In order to allow the TD device to change the operating mode, the mode selector switch on
the S7-200 must be set to either RUN or TERM.
The TD device cannot change the operating mode if the mode selector switch is set to
STOP.
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH67235810RGH
0DNH0&
(GLW&380HPRU\
Figure 5-21 Changing the Operator Mode
Copying the User Program to a Memory Cartridge (TD 200C and TD400C)
The Make MC (memory cartridge) command is only available for the TD 200C and TD400C
and only if you selected this function when you configured the TD device with the Text
Display wizard. See Chapter 4.
You can use the TD 200C and TD400C to copy the user program in the S7-200 CPU to a
memory cartridge (MC). The operator may need to enter both the TD password and the CPU
password, if both the TD device and the S7-200 CPU are configured for password-
protection.
Before attempting to write the user program to the memory cartridge, ensure that you have
installed a memory cartridge in the S7-200 CPU.
After you select the Make MC command, the TD device alerts you that this operation will
erase any existing data on the memory cartridge. Press the DOWN arrow to continue.
After reading the message, press ENTER to continue or press ESC to abort the operation
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH67235810RGH
0DNH0&
(GLW&380HPRU\
Figure 5-22 Making a Memory Cartridge
Editing the CPU Memory (TD 200C and TD400C)
The Edit CPU Memory command is only available for the TD 200C and TD400C and only if
you selected this function when you configured the TD device with the Text Display wizard.
See Chapter 4
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
130 System Manual, 08/2008, A5E00765548-03
You can use the TD 200C and TD400C to edit the values stored in the memory of the S7-
200 CPU. The operator may need to enter the TD password, if the TD device is configured
for password-protection.
After you select the Edit CPU Memory command (see the figure below), the TD device
displays the Edit CPU Memory screen.
7'6HWXS
9LHZ0HVVDJHV
)RUFH,2
&KDQJH67235810RGH
0DNH0&
(GLW&380HPRU\
Figure 5-23 Edit CPU Memory Command
As shown in the figure below, you press ESC to edit the data in the memory address. The
TD device places a cursor on the memory area.
To edit the memory address: Use the UP or DOWN arrows to change the memory
address. (Use the RIGHT or LEFT arrow keys to move between the fields of the memory
address.) Press ENTER to display the value of that memory address and to move the
cursor to the data type field.
To edit the data type: Use the UP or DOWN arrows to change the data type. Press
ENTER to display the value and to move the cursor to the value field.
To edit the value stored in the memory address: Use the UP or DOWN arrows to change
the value.
Press ENTER to write the new values to the memory address in the S7-200 CPU. Pressing
ESC aborts the function.
(6&
9 :  ,17 
9:,17

(QWHU (QWHU
(QWHU
3UHVV(6&WRHGLWWKH
&38PHPRU\
3UHVV(17(5WRZULWHWKHQHZ
YDOXHWRWKH&38PHPRU\
7KH83DQG'2:1DUURZV
FKDQJHWKHGDWDLQWKH
VHOHFWHGILHOG
(GLWWKHPHPRU\DGGUHVV (GLWWKHGDWDW\SH (GLWWKHYDOXH
9DOXH
'DWDW\SH
$GGUHVV6L]H
$UHD
Figure 5-24 Editing the Memory in the S7-200 CPU
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 131
Table 5-3 lists the memory address and data types possible. For information about the
memory areas, sizes of the data, and data types supported by your S7-200 CPU, refer to the
S7-200 Programmable Controller System Manual.
Use the UP and DOWN arrows to scroll through the list of valid entries for each field.
To change the numeric value displayed in the address and value fields:
Use the UP and DOWN arrows to adjust each digit in the value or address.
Use the LEFT and RIGHT arrows to move between the digits of the value or address.
Press ENTER to write the new value to the S7-200 CPU.
Tip
Binary values cannot be edited.
Table 5- 3 Possible Values for the CPU Memory Address and Data Type
Field Description
Memory area V Variable memory area
M Bit Memory area
SM Special Memory area
T Timers Current value only1, INT only
C Counters Current value only1, INT only
I Inputs
Q Outputs
Memory size B (byte)
W (word)
D (double-word)
Address 0 to 32000 (limited by the memory for your S7-200 CPU)
Refer to the S7-200 Programmable Controller System Manual for the range of
memory supported by the different S7-200 CPU models)
Operating Your Text Display (TD) Device
5.7 Performing Specialized Operator Tasks (Diagnostic/Setup Menu)
Text Display (TD) User Manual
132 System Manual, 08/2008, A5E00765548-03
Field Description
Data type INT Integer (valid for Byte, Word or Double-word)
Byte values are displayed as unsigned integers
Word and Double-word values are displayed as signed integers
REAL Real or floating-point (valid for Double-word only)
The value displayed for a Real number is rounded to 6 or 7 significant digits. The TD
device displays the Real number in fixed-point format only (no scientific notation)
The TD device cannot display Real numbers larger than 18 digits and allows up to 7
decimal places. (For example: The TD device displays
0.00000005 as 0.0000001, and displays real numbers less than
0.00000005 as "0.0".)
The TD device writes the number displayed to the S7-200 CPU without
rounding.
HEX Hexadecimal (valid for Byte, Word, and Double-word)
BIN Binary (valid for Byte and Word only)
Binary values are displayed in the same pattern (7..0) as discussed in the
S7-200 Programmable Controller System Manual and displayed by the
Status Chart of STEP 7-Micro/WIN
Binary values cannot be edited
1 The TD device displays only the current value for timers and counters. To display preset values for
timers or counters, you must store these values in V memory. The TD device does not display the
value of the timer or counter bit.
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 133
Technical Specifications and Reference Information A
A.1 General Specifications for the Text Display Devices
General Technical Specifications for the Text Display Devices
Order Number Description Dimensions (mm) (H x H x D) Weight
6ES7 272- 1BA10-0YA1 TD 100C Operator Interface 89.6 x 76 x 35.7 0.11 kg
6ES7 272-0AA30-0YA1 TD 200 Operator Interface 148 x 76 x 28 0.19 kg
6ES7 272-1AA10-0YA1 TD 200C Operator Interface 148 x 76 x 28 0.20 kg
6AV6640-0AA00-0AX1 TD400C Operator Interface 174 x 102 x 31 0.31 kg
6ES7 272-1AF00-7AA0 TD 200C Blank faceplate material, A4 size (10 sheets/package)
6ES7 272-1BF00-7AA0 TD 100C Blank faceplate material, A4 size (10 sheets/package)
6AV6671-0AP00-0AX0 TD400C Blank faceplate material, A4 size (10 sheets/package)
6ES7 901-3EB10-0XA0 TD/CPU cable 2.5 meters 0.15 kg
A.2 Technical Specifications for the TD 100C, TD 200 and TD 200C
Technical Specifications for the TD 100C, TD 200 and TD 200C
Table A- 1 Technical Specifications for the TD 100C, TD 200 and TD 200C
General TD 100C
6ES7 272-1BA10-0YA1
TD 200
6ES7 272-0AA30-0YA1
TD 200C
6ES7 272-1AA10-0YA1
Keyboard Customizable faceplate
Supports up to 14 keys
Membrane keypad with 9
keys; Tab inserts for
customer-specific labeling
Customizable faceplate
Supports up to 20 keys
Display FSTN-Graphic Display with 132
x 65 (columns x rows), no
backlight
STN-Graphic Display with 181 x 33 (Columns x Rows), LED
backlight
PLC interface RS 485 (PPI); 9.6 / 19.2 / 187.5 Kbits/s
Technical Specifications and Reference Information
A.2 Technical Specifications for the TD 100C, TD 200 and TD 200C
Text Display (TD) User Manual
134 System Manual, 08/2008, A5E00765548-03
General TD 100C
6ES7 272-1BA10-0YA1
TD 200
6ES7 272-0AA30-0YA1
TD 200C
6ES7 272-1AA10-0YA1
Supply voltage (UN) Supplied by the S7-200 CPU,
no external supply,
(24 VDC (8 VDC ... 30 VDC)
safety extra low voltage, NEC
Class 2 or limited power source)
24 VDC, 15 VDC ... 30 VDC, safety extra low voltage, NEC
Class 2 or limited power source (supplied by the S7-200
CPU, mains adapter or a 24 VDC external supply). The TD
device has no integrated means of protection against strong
interference pulses in the microsecond range (surge
impulse). If the power being supplied has no appropriate
means of protection, then a surge voltage protector should
be pre-connected.
Current consumption (IN) Typical 20 mA, maximum 50
mA, at UN 24V (no fuse in TD
100C)
Typical 70 mA, (terminating resistors switched off)
Maximum 120 mA at UN 24V (3.15A fuse in TD 200).
Inrush current Not applicable Maximum 0.6 A / 15 ms
Degree of protection IP 651 (mounted on front of the
panel)
IP 20 (mounted on casing)
UL 50 Type 4X1
IP 652 (mounted on front of the panel)
IP 20 (mounted on casing)
UL 50 Type 4X2
Safety
Safety standard IEC61131-2, UL508,
CSA C22.2 No. 142
EN 60950, IEC 60950, UL 60950, CSA C22.2 No. 60950
Noise emission <45dB(A) to DIN 45635 (no fan)
1 To ensure compliance of the TD 100C with IP 65 and UL 50 Type 4X, you must follow these guidelines. The minimum
panel thickness must be at least 1.5 mm. The mounting screws on the TD 100C device must be tightened to a torque of
0.2 Nm (about 0.5 mm the height of the seal). The gasket must be replaced whenever the TD device is removed and
reinstalled. To procure new gaskets, contact your Siemens distributor or sales representative.
2 To ensure compliance of the TD 200C and TD 200 with IP 65 and UL 50 Type 4X, you must follow these guidelines. The
minimum panel thickness must be at least 1.5 mm. The mounting screws on the TD 200C or TD 200 device must be
tightened to a torque of 0.7 N-m. The gasket must be replaced whenever the TD device is removed and reinstalled. To
procure new gaskets, contact your Siemens distributor or sales representative.
Technical Specifications for the TD 100C, TD 200 and TD 200C (continued)
General TD 100C
6ES7 272-1BA10-0YA1
TD 200
6ES7 272-0AA30-0YA1
TD 200C
6ES7 272-1AA10-0YA1
Electromagnetic Compatibility (EMC) (tested with TD/CPU cable 6ES7 901-3EB10-0XA0)
Emitted interference
Limit class
Class B to EN 55022 = CISPR 22
Noise immunity on signal
lines
±2kV according to IEC 61000-4-4; Burst
Noise immunity to discharge
of static electricity
±4kV Contact discharge (according to IEC 61000-4-2; ESD)
±8kV Air discharge (according to IEC 61000-4-2; ESD)
Technical Specifications and Reference Information
A.2 Technical Specifications for the TD 100C, TD 200 and TD 200C
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 135
General TD 100C
6ES7 272-1BA10-0YA1
TD 200
6ES7 272-0AA30-0YA1
TD 200C
6ES7 272-1AA10-0YA1
Conducted interference on
DC power supply line
Not applicable ±2kV according to IEC 61000-4-4; Burst
±1kV according to IEC 61000-4-5; ms-impulse (Surge); (line
against line)
±2kV according to IEC 61000-4-5; ms-impulse (Surge); (line
against earth)
Power supplies with the same voltage can only be
used with additional means of protection, for example,
a surge voltage protector available from the Dehn company,
type BVT AD 24, order No. 918 402.
Noise immunity to high
frequency emission
10 V with 80% amplitude modulation at 1 kHz, 10 kHz to 80 MHz
(according to IEC 61000-4-6)
10 V/m with 80% amplitude modulation at 1 kHz, 80 MHz to 1 GHz ,
and 1.4 GHz to 2 GHz (according to IEC 61000-4-3)
Power supplies with the same voltage can only be used with additional means of protection,
for example, a surge voltage protector available from the Dehn company, type BVT AD 24,
order No. 918 402.
Climatic Conditions
Temperature
Operation
Storage/Transport
Tested according to IEC 60068-2-1, IEC 60068-2-2
±0° C to +60° C (+32° F to +140° F) (rate of temperature change max. 10° C/h)
-20° C to +60°C (-4° F to +140° F) (rate of temperature change max. 20° C/h
Relative humidity
Operation
Storage/Transport
Tested according to IEC 60068-2-78, IEC 600068-2-30
95% at 30°C (no condensation)
95% at 55°C (no condensation)
Mechanical Environmental Conditions
Vibration
Operation
Transport (packaged)
Tested according to
IEC 60068-2-6
5 Hz to 9 Hz,
amplitude, 3,5 mm
9 Hz to 150 Hz,
acceleration 9.8 m/s2
5 Hz to 9 Hz,
amplitude 3.5 mm
9 Hz to 500Hz,
acceleration 9.8 m/s2
Tested according to
IEC 60068-2-6
10 Hz to 58 Hz,
amplitude 0.075 mm
58 Hz to 150 Hz,
acceleration 9.8 m/s2
5 Hz to 9 Hz,
amplitude 3.5 mm
9 Hz to 500 Hz,
acceleration 9.8 m/s2
Shock
Operation
Transport (packaged)
Tested according to IEC 60068-2-27/29
Semisinusoidal: 150 m/s2 (15g), 11 ms
Semisinusoidal: 250 m/s2 (25g), 6 ms
Special Features
Quality assurance In accordance with ISO 9001
Servicing Maintenance-free (no battery)
Panel mounting Accessories for panel mounting are enclosed
Technical Specifications and Reference Information
A.3 Technical Specifications for the TD400C
Text Display (TD) User Manual
136 System Manual, 08/2008, A5E00765548-03
A.3 Technical Specifications for the TD400C
Technical Specifications for the TD400C
Table A- 2 Technical Specifications for the TD400C
General TD400C
6AV6640--0AA00-0AX1
Keyboard Customizable faceplate
Supports up to 15 keys
Display STN-Graphic Display with 192 x 64 (Columns x Rows), backlight
PLC interface RS 485 (PPI); 9.6 / 19.2 / 187.5 Kbits/s
Supply voltage (UN) 24 VDC, 15 VDC ... 30 VDC, safety extra low voltage, NEC Class 2 or limited power source
(supplied by the S7-200 CPU, mains adapter or a 24 VDC external supply). The TD device
has no integrated means of protection against strong interference pulses in the microsecond
range (surge impulse). If the power being supplied has no appropriate means of protection,
then a surge voltage protector should be pre-connected.
Current consumption (IN) Typical 41 mA
Inrush current Maximum 570 mA
Degree of protection IP 651 (mounted on front of the panel)
IP 20 (mounted on casing)
Noise emission <45dB(A) to DIN 45635 (no fan)
1 To ensure compliance of the TD400C with IP 65 and UL 50 Type 4X, you must follow these guidelines. The minimum
panel thickness must be at least 1.5 mm. The mounting screws on the TD device must be tightened to a torque of 0.7 N-m.
The gasket must be replaced whenever the TD device is removed and reinstalled. To procure new gaskets, contact your
Siemens distributor or sales representative.
Table A- 3 Technical Specifications for the TD400C (continued)
General TD400C
6AV6640-0AA00-0AX1
Electromagnetic Compatibility (EMC) (tested with TD/CPU cable)
Emitted interference
Limit class
A to EN 55011 = CISPR 11
Noise immunity on signal
lines
±2kV, Testing according to IEC 61000-4-4; Burst
Noise immunity to discharge
of static electricity
±8kV Air discharge (according to IEC 61000-4-2; ESD)
±6kV Contact discharge (according to IEC 61000-4-2; ESD)
Conducted interference on
DC power supply line
±2kV, Testing according to IEC 61000-4-4; Burst
±1kV according to IEC 61000-4-5; ms-impulse (Surge); (line against line)
±2kV according to IEC 61000-4-5; ms-impulse (Surge); (line against earth)
Power supplies with the same voltage can only be used with additional means of
protection, for example, a surge voltage protector available from the Dehn company, type
BVT AD 24, order No. 918 402.
Technical Specifications and Reference Information
A.4 Certificates, Directives and Declarations for the TD Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 137
General TD400C
6AV6640-0AA00-0AX1
Noise immunity to high
frequency emission
10 V with 80% amplitude modulation at 1 kHz, 10 kHz to 80 MHz
10 V/m with 80% amplitude modulation at 1 kHz, 80 MHz to 1 GHz
3 V/m with 80% amplitude modulation at 1.4 GHz to 2 GHz
1 V/m with 80% amplitude modulation at 2.0 GHz to 2.7 GHz
Climatic Conditions
Temperature
Operation
Storage/Transport
0 to +50 °C
-20 to +60°C
Relative humidity
Operation
Storage/Transport
85% (30℃), no condensation
95% (25℃ to 55℃), no condensation
Mechanical Environmental Conditions
Vibration
Operation
Transport (packaged)
Tested according to IEC 60068-2-6
5 Hz to 9 Hz, amplitude, 3,5 mm
9 Hz to 150 Hz, acceleration 9.8 m/s2
5 Hz to 9 Hz, amplitude 3.5 mm,
9 Hz to 500 Hz, acceleration 9.8 m/s2
Shock
Operation
Transport (packaged)
Tested according to IEC 60068-2-27/29
Semisinusoidal: 150 m/s2 (15g), 11 ms
Semisinusoidal: 250 m/s2 (25g), 6 ms
Special Features
Quality assurance In accordance with ISO 9001
Servicing Maintenance-free (no battery)
Panel mounting Accessories for panel mounting are enclosed
A.4 Certificates, Directives and Declarations for the TD Device
Certificates, Directives and Declarations for the TD Device
IEC 61131-2
The TD 100C and TD400C devices satisfy the requirements and criteria of the IEC directive
2004/108/EC standard (programmable controllers, part 2 on equipment requirements and
tests).
Notes on the CE Symbol
The following applies to the SIMATIC product described in this operating
instruction
Technical Specifications and Reference Information
A.4 Certificates, Directives and Declarations for the TD Device
Text Display (TD) User Manual
138 System Manual, 08/2008, A5E00765548-03
EMC Directive
This product fulfils the requirements for the EC directive 2004/108/EC on "electromagnetic
compatibility" and the following fields of application apply according to this CE symbol. See
Table A-4.
Table A- 4 EMC Directive
Field of Application Requirement for Emitted
Interference
Requirement for Noise Immunity
Residential, commercial areas
and light industrial environments
EN 6100-6-3 EN 61000-6-1
Industry EN 61000-6-4 EN 61000-6-2
Declaration of Conformity (TD 200C, TD 200, and TD400C)
The EC declarations of conformity and the documentation relating to this are available to the
authorities concerned, according to the above EC directive, from:
Siemens AG
Bereich Automatisierungs- und Antriebstechnik
I IA AS RD ST
Postfach 1963
D-92209 Amberg
Tel.: 09621 80 3283
Fax: 09621 80 3278
Observing the Setup Guidelines
The setup guidelines and notes on safety given in the manual must be observed on startup
and during operation.
Technical Specifications and Reference Information
A.5 Approvals for USA, Canada and Australia
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 139
A.5 Approvals for USA, Canada and Australia
Approvals for USA, Canada and Australia
The characters stamped on a device are indicative of the requirements which that device
meets:
Underwriters Laboratories: cULus Approval, Hazardous Location
cULus Listed 21BP I.T.E. for Hazardous Location
Underwriters Laboratories Inc., according to:
TD 200 and TD 200C:
UL 60950 (Information Technology)
CSA C22.2 No. 60950 (Information Technology)
cULus Listed 7RA9 IND. Cont. EQ. for Hazardous Location
Underwriters Laboratories Inc., according to:
TD 100C and TD400C
UL 508 (Industrial Control Equipment)
CSA C22.2 No. 142 (Industrial Control Equipment)
UL 1604 (Hazardous Location)
CSA-213 (Hazardous Location)
APPROVED for use in:
CI. I, Div.2, GP. A, B, C, D, T5
CI. I, Zone 2, GP.IIC, T5
Please see the note below:
Note
This plant has to be mounted according to the NEC (National Electric Code) stipulations.
When used in environments according to class I, division 2 (see above), the SIMATIC TD
device must be mounted in a housing that corresponds to at least IP54 according to EN
60529.
FM approval to Factory Mutual Approval Standard Class Number 3611, Class I,
Division 2, Group A, B, C, D, and Class I, Zone 2, Group IIC.
Temperature Class T5 is adhered to when the ambient temperature during
operation does not exceed 50 degrees C
Note for Australia: The TD 100C, TD 200, and TD 200C devices fulfil the
requirements for Norm AS/NZS CISPR 22. The TD400C device fulfils the
requirements for Norm AS/NZS CISPR 11.
Technical Specifications and Reference Information
A.5 Approvals for USA, Canada and Australia
Text Display (TD) User Manual
140 System Manual, 08/2008, A5E00765548-03
FM Approval Notes
FM approval, if present, is to Factory Mutual Approval Standard Class Number 3611, Class I,
Division 2, Group A, B, C, D, and Class I, Zone 2, Group IIC.
Temperature class T5 is adhered to when the ambient temperature during operation does
not exceed 50 degrees C.
WARNING
Personal injury or property damage can result if you do not follow FM hazardous location
guidelines.
In hazardous areas, personal injury or property damage can result if you close or
disconnect an electrical circuit during operation (for example, plug-in connections, fuses,
switches).
Do not close or disconnect any live circuits unless explosion hazards can be definitely
excluded. Do not disconnect while the circuit is live unless the location is known to be non-
hazardous.
Technical Specifications and Reference Information
A.6 Standard TD Character Set (TD 200, TD 200C)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 141
A.6 Standard TD Character Set (TD 200, TD 200C)
Standard TD Character Set (TD 200, TD 200C)
Figure A-1 Standard TD Character Set for the TD 200 and TD 200C
Technical Specifications and Reference Information
A.6 Standard TD Character Set (TD 200, TD 200C)
Text Display (TD) User Manual
142 System Manual, 08/2008, A5E00765548-03
Figure A-2 Standard TD Character Set for the TD 200 and TD 200C (continued)
Alt Key Combinations for International and Special Characters
Certain international and special characters may not display correctly on the TD display if
entered with the Text Display wizard with the standard TD character set. For international
and special characters, use the ALT key and number combinations shown in Table A-5 to
enter the characters in the Text Display wizard.
Table A- 5 ALT Key Combinations for International Special Characters
Character ALT + Key Combination
ü Alt + 0129
ä Alt + 0132
æ Alt + 0144
Æ Alt + 0145
å Alt + 0147
ö Alt + 0148
Å Alt + 0149
° Alt + 0223
α Alt + 0224
ß Alt + 0225
є Alt + 0227
ų Alt + 0228
σ Alt + 0229
¢ Alt + 0236
ñ Alt + 0238
Alt + 0244
Σ Alt + 0246
Alt + 0247
Alt + 0126 (left arrow ← )
Alt + 0127 (right arrow →)
[ Alt + 0251 (single bar)
Technical Specifications and Reference Information
A.6 Standard TD Character Set (TD 200, TD 200C)
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 143
Character ALT + Key Combination
[[ Alt + 0252 (double bar)
[[[ Alt + 0253 ( triple bars)
[[[[ Alt + 0254 (four bars)
[[[[[ Alt + 0255 (five bars)
Alt + 0249 (up arrow)
Bar Graph Character Set (TD 200, TD 200C)
The bar graph characters that are supported by the standard TD character set are shown
below.
Figure A-3 Bar Graph Character Set for the TD 200 and TD 200C
Technical Specifications and Reference Information
A.7 Arabic Character Set (TD 200, TD 200C, and TD400C)
Text Display (TD) User Manual
144 System Manual, 08/2008, A5E00765548-03
A.7 Arabic Character Set (TD 200, TD 200C, and TD400C)
Arabic Character Set (TD 200, TD 200C, and TD400C)
Figure A-4 Arabic Character Set
Technical Specifications and Reference Information
A.8 Baltic Character Set
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 145
A.8 Baltic Character Set
Baltic Character Set
Figure A-5 Baltic Character Set
Technical Specifications and Reference Information
A.9 Simplified Chinese Character Set
Text Display (TD) User Manual
146 System Manual, 08/2008, A5E00765548-03
A.9 Simplified Chinese Character Set
Simplified Chinese Character Set
The TD devices support the Simplified Chinese character set (GB2312-80) for the People's
Republic of China. The TD devices use Microsoft Windows encoding for this character set.
The Windows encoding allows the TD devices to display the same characters as shown in
the STEP 7-Micro/WIN Text Display wizard when you are using a Chinese emulator or a
Chinese version of Microsoft Windows.
Chinese characters are represented in STEP 7-Micro/WIN by a pair of numbers which
represent the encoding of the character in the GB2312-80 specification. The TD devices also
use a pair of numbers to represent the Chinese character.
Notes for Using the Simplified Chinese Character Set
Tip
The Simplified Chinese character set requires a Chinese version of Windows or a Chinese
emulator to properly display Chinese characters in the Text Display wizard. You must start
the Chinese emulator before you start the STEP 7-Micro/WIN software.
On the TD 200C and the TD 200, you can display up to 20 single-byte characters per line of
your message. Because Simplified Chinese uses double-byte characters, you can display up
to 10 double-byte characters per line for a message in Chinese.
On the TD 100C, you can display up to 16 single-byte characters per line of your message.
Because Simplified Chinese uses double-byte characters, you can display up to 8 double-
byte characters per line for a message in Chinese.
On the TD400C using a small font, you can display up to 24 single-byte characters per line
of your message. Because Simplified Chinese uses double-byte characters, you can display
up to 12 double-byte characters per line for a message in Chinese. If you selected a large
font, you can display up to 16 single-byte characters or 8 Chinese characters.
The standard ASCII characters, such as numbers, punctuation, and upper and lowercase
alphabet characters, are available when using the Simplified Chinese character set (shown
below). Depending on your keyboard and/ or emulator, some of these standard characters
may be formatted as single-byte characters instead of the double-byte characters like the
Simplified Chinese characters. Standard ASCII characters and Chinese characters can be
mixed on the TD display.
The Text Display wizard displays 8 , 10, or 12 double-byte character places for the text of a
screen or alarm. You can fit any of the following combinations into a character position:
1 double-byte character
2 single-byte characters (standard ASCII)
1 single-byte character and 1 single-byte blank
You cannot fit one single-byte character plus one double-byte character in a character
position.
Technical Specifications and Reference Information
A.9 Simplified Chinese Character Set
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 147
TD 100C does not support the entire Simplified Chinese character set, however, the most-
used characters have been included in the TD 100C. See the Simplified Chinese Characters
Set for a list of supported characters. Characters that are not supported by the TD 100C are
displayed as a square.
Tip
The Simplified Chinese Character Set electronic file resides on the STEP 7-Micro/WIN
documentation CD. This file shows the characters supported by the different TD devices.
The Standard Character Set (ASCII) for the TD400C is shown below.
Figure A-6 Standard Character Set (ASCII Code) for TD400C
Technical Specifications and Reference Information
A.10 Cyrillic Character Set
Text Display (TD) User Manual
148 System Manual, 08/2008, A5E00765548-03
A.10 Cyrillic Character Set
Cyrillic Character Set
Figure A-7 Cyrillic Character Set
Technical Specifications and Reference Information
A.11 Greek Character Set
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 149
A.11 Greek Character Set
Greek Character Set
Figure A-8 Greek Character Set
Technical Specifications and Reference Information
A.12 Hebrew Character Set (TD 200, TD 200C, and TD400C)
Text Display (TD) User Manual
150 System Manual, 08/2008, A5E00765548-03
A.12 Hebrew Character Set (TD 200, TD 200C, and TD400C)
Hebrew Character Set (TD 200, TD 200C, and TD400C)
Figure A-9 Hebrew Character Set
Technical Specifications and Reference Information
A.13 Latin 1 Character Set
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 151
A.13 Latin 1 Character Set
Latin 1 Character Set
Figure A-10 Latin 1 Character Set
Technical Specifications and Reference Information
A.14 Latin 2 Character Set
Text Display (TD) User Manual
152 System Manual, 08/2008, A5E00765548-03
A.14 Latin 2 Character Set
Latin 2 Character Set
Figure A-11 Latin 2 Character Set
Technical Specifications and Reference Information
A.15 Turkish (Latin 5) Character Set
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 153
A.15 Turkish (Latin 5) Character Set
Turkish (Latin 5) Character Set
Figure A-12 Turkish (Latin 5) Character Set
Technical Specifications and Reference Information
A.15 Turkish (Latin 5) Character Set
Text Display (TD) User Manual
154 System Manual, 08/2008, A5E00765548-03
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 155
Connecting Multiple Devices on a Network B
B.1 Overview
Overview of Appendix B
You can connect multiple TD devices and S7-200 CPUs together on one communication
network. The TD devices act as network masters and do not interfere with each other. You
can designate the S7-200 CPUs to be either masters or slaves on the network.
B.2 Communicating with Multiple CPUs
Communicating with Multiple CPUs
Figure B-1 shows a typical network with two TD 200s and two S7-200 CPUs. Each TD 200
communicates to one of the CPUs. The addresses of each device are noted below the
device in the figure. In this example:
TD 200 Number 1 is configured to communicate to the S7-200 CPU at address 2 (CPU 1)
TD 200 Number 2 is configured to communicate to the S7-200 CPU at address 3 (CPU 2)
Tip
You can connect multiple TD devices to a single S7-200 CPU. You can store separate
parameter blocks for each TD device in different V memory locations in the CPU.
If you do not store separate parameter blocks for each TD device that is connected to the
CPU, any of these TD devices can acknowledge the same messages and use function keys
to initiate operations in the CPU.
7'7'B
7'7'B
&38&38B
&38&38B
$GGUHVV
$GGUHVV
$GGUHVV
$GGUHVV
7RDGGLWLRQDO&38V
Figure B-1 Typical Multiple CPU Network
Connecting Multiple Devices on a Network
B.3 Determining the Distances, Transmission Rate, and Cable
Text Display (TD) User Manual
156 System Manual, 08/2008, A5E00765548-03
Tip
The display time slows as more TD devices are added to the network.
Network connectors are available from Siemens. Using these connectors allows you to
isolate the CPUs from one another (the 24 VDC), but still allows you to power the TD device
from the CPU. See the SIMATIC S7-200 Programmable Controller System Manual for more
information about using network connectors.
B.3 Determining the Distances, Transmission Rate, and Cable
Determining the Distances, Transmission Rate, and Cable
As shown in Table B-1, the maximum length of a network segment is determined by two
factors: isolation (using an RS-485 repeater) and baud rate.
Isolation is required when you connect devices at different ground potentials. Different
ground potentials can exist when grounds are physically separated by a long distance. Even
over short distances, load currents of heavy machinery can cause a difference in ground
potential.
Table B- 1 Maximum Length for a Network Cable
Baud Rate Non-Isolated CPU Port1 CPU Port with Repeater or EM 277
9.6 kbaud to 187.5 kbaud 50 m 1,000 m
1 The maximum distance allowed without using an isolator or repeater is 50 m. You
measure this distance from the first node to the last node in the segment,
Using Repeaters on the Network
An RS-485 repeater provides bias and termination for the network segment. You can use a
repeater for the following purposes:
To increase the length of a network: Adding a repeater to your network allows you to
extend the network another 50 m. If you connect two repeaters with no other nodes in
between (as shown in Figure B-2), you can extend the network to the maximum cable
length for the baud rate. You can use up to 9 repeaters in series on a network, but the
total length of the network must not exceed 9600 m.
To add devices to a network: Each segment can have a maximum of 32 devices
connected up to 50 m at 9600 baud. Using a repeater allows you to add another segment
(32 devices) to the network.
To electrically isolate different network segments: Isolating the network improves the
quality of the transmission by separating the network segments which might be at
different ground potentials.
A repeater on your network counts as one of the nodes on a segment, even though it is not
assigned a network address.
Connecting Multiple Devices on a Network
B.4 Selecting the Network Cable
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 157
P P
6HJPHQW 6HJPHQW 6HJPHQW
8SWRP
56
5HSHDWHU
56
5HSHDWHU
Figure B-2 Sample Network with Repeaters
B.4 Selecting the Network Cable
Selecting the Network Cable
S7-200 networks use the RS-485 standard on twisted pair cables. Table B-2 lists the
specifications for the network cable. You can connect up to 32 devices on a network
segment.
Table B- 2 General Specifications for Network Cable
Specifications Description
Cable type Shielded, twisted pair
Loop resistance ≤115 Ω /km
Effective capacitance 30 pF/m
Nominal impedance Approximately 135 Ω to 160 Ω (frequency =3 MHz to 20 MHz)
Attenuation 0.9 dB/100 m (frequency=200 kHz)
Cross-sectional core area 0.3 mm2 to 0.5 mm2
Cable diameter 8 mm ±0.5 mm
B.5 Biasing and Terminating the Network Cable
Biasing and Terminating the Network Cable
Siemens provides two types of network connectors that you can use to easily connect
multiple devices to a network: a standard network connector and a connector that includes a
programming port (which allows you to connect a programming station or an HMI device to
the network without disturbing any existing network connections). The programming port
connector passes all signals (including the power pins) from the S7-200 through to the
programming port, which is especially useful for connecting devices that draw power from
the S7-200 (such as a TD 200).
Both connectors have two sets of terminal screws to allow you to attach the incoming and
outgoing network cables. Both connectors also have switches to bias and terminate the
network selectively. Figure B-3 shows typical biasing and termination for the cable
connectors.
Connecting Multiple Devices on a Network
B.6 Building a TD/CPU Cable
Text Display (TD) User Manual
158 System Manual, 08/2008, A5E00765548-03
$%$% $%$% $%$%









 &DEOHVKLHOG
&DEOHVKLHOG
3LQ 3LQ
&DEOHVKLHOG
1HWZRUN
FRQQHFWRU
6ZLWFKSRVLWLRQ 2II
1RWHUPLQDWLRQRUELDV
6ZLWFKSRVLWLRQ 2Q
7HUPLQDWHGDQGELDVHG
%DUHVKLHOGLQJDSSUR[LPDWHO\PPLQPXVWFRQWDFWWKHPHWDOJXLGHVRIDOOORFDWLRQV
&DEOHPXVWEHWHUPLQDWHG
DQGELDVHGDWERWKHQGV 6ZLWFKSRVLWLRQ 2Q
7HUPLQDWHGDQGELDVHG
6ZLWFKSRVLWLRQ 2Q
7HUPLQDWHGDQGELDVHG
6ZLWFKSRVLWLRQ 2II
1RWHUPLQDWLRQRUELDV
2Q 2Q
2II
Figure B-3 Bias and Termination of the Network Cable
B.6 Building a TD/CPU Cable
Building a TD/CPU Cable
The TD/CPU cable is used for connecting a display device to an S7-200 CPU. If you do not
have a TD/CPU cable, refer to Figures B-4 and B-5 to create your own cable.
Making a Cable That Supplies Power to the TD Device
CAUTION
Connecting the 24 VDC power output (pin 7 of communication port) of multiple S7-200
CPUs may cause erratic operation of the I/O, which could potentially cause personal injury
and/or property damage.
The 24 VDC power supply is also the sensor supply for the I/O. Interconnecting the output
power supplies of multiple CPUs could possibly overload the sensor supply, which could
cause the I/O to operate incorrectly.
When networking S7-200 CPUs, connect only the communication lines (pins 3, 5, and 8).
You must not connect the power output (pin 7).
Tip
The TD 100C must use the TD/CPU cable shown in Figure B-4.
Connecting Multiple Devices on a Network
B.6 Building a TD/CPU Cable
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 159
Figure B-4 shows you the pin-out of TD/CPU cable with power supplied to the TD device.
Use this option when you want the TD device to receive power from an S7-200 CPU.
9'& 9'&
66LGH
7'6LGH
9'&5HWXUQ
7UDQVPLW5HFHLYH'DWD
7UDQVPLW5HFHLYH'DWD
9'&5HWXUQ
7UDQVPLW5HFHLYH'DWD
7UDQVPLW5HFHLYH'DWD
6KLHOG
Figure B-4 TD/CPU Cable with Power Connections
Making a Cable That Does Not Supply Power to the TD Device (TD 200, TD 200C, and TD400C only)
Figure B-5 shows you the pin-out of a TD/CPU cable without power supplied to the TD
device. Use this option when you want the TD device to receive power from an external
power supply. The maximum length for the cable is 1200 meters.


















7'6LGH 66LGH
7UDQVPLW5HFHLYH'DWD
7UDQVPLW5HFHLYH'DWD
7UDQVPLW5HFHLYH'DWD
7UDQVPLW5HFHLYH'DWD
6KLHOG
Figure B-5 TD/CPU Cable without Power Connections
Connecting Multiple Devices on a Network
B.7 CPU Grounding and Circuit Reference Point Guidelines for Using Isolated Circuits
Text Display (TD) User Manual
160 System Manual, 08/2008, A5E00765548-03
B.7 CPU Grounding and Circuit Reference Point Guidelines for Using
Isolated Circuits
CPU Grounding and Circuit reference Point Guidelines for Using Isolated Circuits
The following items are CPU grounding and circuit guidelines for using isolated circuits:
You should identify the reference point (0 voltage reference) for each circuit in the
installation, and the points at which circuits with possibly different references can connect
together. Such connections can result in unwanted current flows that can cause logic
errors or can damage circuits. A common cause of different reference potentials is
grounds that are physically separated by long distances. When devices with widely
separated grounds are connected with a communication or sensor cable, unexpected
currents can flow through the circuit created by the cable and the ground. Even over short
distances, load currents of heavy machinery can cause differences in ground potential or
can directly induce unwanted currents by electromagnetic induction. Power supplies that
are improperly referenced with respect to each other can cause damaging currents to
flow between their associated circuits.
When you connect CPUs with different ground potentials to the same PPI network, you
should use an isolated RS-485 repeater.
S7-200 products include isolation boundaries at certain points to help prevent unwanted
current flows in your installation. When you plan your installation, you should consider
where these isolation boundaries are provided, and where they are not provided. You
should also consider the isolation boundaries in associated power supplies and other
equipment, and where all associated power supplies have their reference points.
You should choose your ground reference points and use the isolation boundaries
provided to interrupt unneeded circuit loops that could allow unwanted currents to flow.
Remember to consider temporary connections which may introduce a new circuit
reference, such as the connection of a programming device to the CPU.
When locating grounds, you must also consider safety grounding requirements and the
proper operation of protective interrupting devices.
In most installations, you will have the best noise immunity if you connect the CPU sensor
supply M terminal to ground.
The following descriptions are an introduction to general isolation characteristics of the S7-
200 family, but some features may be different on specific products. Consult your product
specifications in the appropriate manual for information about which circuits include isolation
boundaries and the ratings of the boundaries. Isolation boundaries rated less than 1,500
VAC are designed as functional isolation only, and should not be depended on as safety
boundaries.
Logic circuit reference is the same as DC sensor supply M.
Logic circuit reference is the same as the input power supply M on a CPU with DC power
supply.
CPU communication ports have the same reference as logic circuit.
Analog inputs and outputs are not isolated from logic circuit. Analog inputs are full
differential to provide low voltage common mode rejection.
Logic circuit is isolated from ground to 500 VAC.
Connecting Multiple Devices on a Network
B.7 CPU Grounding and Circuit Reference Point Guidelines for Using Isolated Circuits
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 161
DC digital inputs and outputs are isolated from logic circuit to 500 VAC.
DC digital I/O groups are isolated from each other by 500 VAC.
Relay outputs are isolated from logic circuit to 1,500 VAC.
Relay output groups are isolated from each other by 1,500 VAC.
AC power supply line and neutral are isolated from ground, the logic circuit, and all I/O to
1,500 VAC.
Connecting Multiple Devices on a Network
B.7 CPU Grounding and Circuit Reference Point Guidelines for Using Isolated Circuits
Text Display (TD) User Manual
162 System Manual, 08/2008, A5E00765548-03
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 163
Troubleshooting C
C.1 Troubleshooting Guide
Troubleshooting
Refer to Table C-1 for a list of the problems that could occur with the TD device and possible
causes and solutions.
Table C- 1 Error Messages
Problem Possible Cause Possible Solution
The TD device could not find a
parameter block in the programmable
logic controller.
Configure a parameter block for the TD
device using the Text Display wizard,
and download it to the S7-200.
Be sure the parameter block address in
the TD device matches the actual
address of the parameter block.
NO PARAMETER BLOCK
The TD device found a parameter block
in the programmable logic controller,
but it contains errors.
Be sure all fields are within range.
Be sure all addresses are valid for the
S7-200 CPU.
Address of the S7-200 CPU is incorrect Correct the address error
S7-200 CPU does not have power Power up the CPU
Cable problems Check the cable connections
Wrong baud rate configured Correct the baud rate
Multiple CPUs at the same address Remove other CPUs and retry
May need network terminations Refer to Appendix B
No CPU COMM
Network too long or too many devices
on network
Refer to Appendix B
HARDWARE ERROR TD device is inoperable The TD device could be defective
Replace with a new TD device.
Multiple masters with the same
address.
Remove other masters and retry
Cable problems Check the cable connections
NETWORK ERROR
TD device cannot establish a network
connection or enter an existing network
Multiple CPUs at the same address Remove the other CPUs and retry
CPU BUSY Some other master has locked the S7-
200 CPU by uploading or downloading
a program to that CPU
Wait - The message disappears in a
few seconds
CPU IN STOP MODE RUN/STOP switch is in STOP Put CPU in RUN mode
Troubleshooting
C.1 Troubleshooting Guide
Text Display (TD) User Manual
164 System Manual, 08/2008, A5E00765548-03
Problem Possible Cause Possible Solution
Display backlight is on, but no message
is displayed
Program checksum failure Defective hardware: Replace with a
new TD device
User cannot access the TD system
menus
The custom keypad does not contain
the ESC and ENTER buttons
To restore the standard TD keypad:
1. Power down the TD device
2. Press and hold the lower right
corner (where ENTER key is
located on the standard keypad)
3. Power up the TD device
The default keypad is restored until the
TD device is power cycled again.
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 165
Index
A
agency approvals
Canadian Standards Association (CSA), 4
Underwriters Laboratories (UL), 4
alarms, 110
accessing, 19
alarm parameters, 90
configuring, 87
default display, 90
determining type of operator interaction, 89
displaying, 21
embedding variable, 93
storing in parameter block, 21
text for, 91
Approvals for TD devices, 139
Arabic Character Set, 144
arrow buttons, 103
ATEX, 138
B
Baltic Character Set, 145
Bar Graph character set, 143
baud rate, 126
bitmaps, sample, 15
button properties by TD device, 53
buttons
adding to keypad, 50
arrow, 103
configurable, 102
configuring on keypad, 78
defining properties, 52
Enter and Escape, 102
Buttons
Inserting, 51
C
cable
connecting the TD/CPU cable, 41
Cable
building a network, 158
Cable for network, 157
cable, TD/CPU, 31
CE Labeling, 5
CE Symbol, 138
certification, 5
character set
selecting, 75
Character sets
Standard Character Set, 147
Character Sets
Arabic, 144
Cyrillic, 148
Greek, 149
Hebrew, 150
Latin 1, 151
Latin 2, 152
Simplified Chinese, 146
Standard TD, 141
Turkish (Latin 5), 153
Characters Sets
Baltic, 145
characters supported, 16
Characters, International and Special, 142
clearing keypad, 123
cnfiguration
saving keypad to, 58
Communicating on a network, 155
communication port, 15
comparing TD features, 18
compatibility with other TD devices, 13
configurable buttons, 102
configuration overview, 24
Configure
Text Display device, 71
configuring
alarms, 87
language sets, 95
screens, 79
configuring buttons
TD 100C, TD 200C, and TD400C, 46
configuring the TD
completing, 98
with Text Display wizard, 70
connecting
TD/CPU cable, 41
connection to CPU, establishing, 43
contact information, 7
technical support, 7
contrast, 126
copy user program to memory cartridge, 129
Index
Text Display (TD) User Manual
166 System Manual, 08/2008, A5E00765548-03
CPU address, 125
CPU Grounding, 160
CPU memory
editing, 129
CPU memory address and data type, 131
CPU operating mode, 128
CPU Status, 120
creating a custom faceplate, 27
Creating text for screen, 82
C-Tick Standards, 5
cULs, 139
custom faceplate, 46
creating, 27
printing, 28
custom keypad
loading to the TD device, 77
custom label for TD 200
dimensions, 37
customizing label
keys of TD 200, 36
Cyrillic Character Set, 148
D
data type, 131
default display mode, 110
defining properties of buttons, 52
Diagnostic/Setup Menu, 124
Dimensions, 133
dimensions for mounting hole, 33
dimensions for TD 200 label, 37
display backlight, 127
display backlight TD400C, 103
displaying screens and alarms, 21
E
EC declarations, 138
edit variables, 106
editing CPU memory, 129
embedded string variables, 85
embedding a variable, 83
EMC directive, 138
error messages, 120
F
faceplate
creating a custom, 27
installing, 38
printing, 28
printing panel image to, 60
procedure to install, 38
faceplate for TD 100C and TD 200C, 32
faceplate, blank
ordering information, 28
Factory Mutual (FM) approvals, 140
Factory Mutual Research Standards, 5
features of TD device, 16
font size
selecting, 76
fonts supported, 17
Force I/O, 127
G
gap factor, 126
gaphics application
export layout, 55
gasket, 32
Greek Character Set, 149
H
Hebrew Character Set, 150
highest station, 126
I
installation of TD device
general, 32
installation overview, 22
installing
printed faceplate to TD device, 64
installing faceplate, 38
installing TD device, 26
Internet site for Text Display, 5
K
kepad
save to TD configuration file, 58
keypad
adding buttons, 50
keypad buzzer, 127
Keypad Designer, 46
adding buttons, 50
starting the, 48
templates, 46
keypad Llyout
export to graphics application, 55
Index
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03 167
keypad, clearing, 123
L
language set
selecting, 75
language sets, 123
configuring, 95
languages supported, 16
Latin 1 Character Set, 151
Latin 2 Character Set, 152
M
manuals
S7-200 Programmable Controller System Manual, 3
memory cartridge
copying to, 129
menu hierarchy, 106
message
creating for screen, 82
messages
viewing, 127
mounting
preparing the TD device, 34
spacers, 34
TD device, 33
mounting brackets, 31
mounting dimensions, 33
mounting procedure
TD 100C, 35
mounting the TD 100C, 35
mounting the TD device
steps required, 35
N
network
TD as master, 15
Network
communicating with multiple CPUS, 155
isolation and baud rate, 156
network address, 125
Network cable, 157
biasing and terminating, 157
O
operator interaction for alarms, 89
Operator Menu, 119
Order numbers, 133
P
panel image
printing, 60
reversing, 59
panel thickness, 32
parameter block
assigning V memory address, 98
screens and alarms, 21
parameter block address, 125
password, 109
Password, selecting, 72
pnel image
adding to faceplate, 56
importing, 56
power connector, 15
power, supplying, 42
printing
custom faceplate, 28
printing panel image, 60
program files, 15
projects, sample, 15
R
Repeaters on Network, 156
reversing panel image, 59
S
S7-200 Programmable Controller System Manual, 3
sample bitmaps, 15
sample projects, 15
sample templates, 15
screen
creating text, 82
message, 82
screens, 110
accessing, 19
configuring, 79
displaying, 21
storing in parameter block, 21
screws, mounting, 32
service and support, 5
Setting up TD device, 125
Simplified Chinese Character Set, 146
spacers, 34
Specifications, 133
TD400C, 136
Index
Text Display (TD) User Manual
168 System Manual, 08/2008, A5E00765548-03
Standard Character Set (ASCII), 147
standard faceplate, 43
standard functions, 106
Standard TD Character Set, 141
STEP 7-Micro/WIN, 15
versions, 3
STOP/RUN mode, 128
summary of configuration, 98
T
TD 100C, 13
components shipped with, 31
features, 18
TD 200, 14
components shipped with, 31
customizing label for keys, 36
features, 18
TD 200C, 13
components shipped with, 31
features, 18
TD device
commmunication baud rate, 43
configuring the buttons on keypad, 78
displaying information, 104
installing printed faceplate, 64
loading a custom keypad, 77
select language and character set, 75
selecting font size, 76
selecting update rate, 75
standard faceplate, 19
supplying power, 42
TD devices, 13
comparing features, 18
compatibility, 13
fonts supported, 17
TD features, 16
TD Menu functions
enabling CPU, 72
TD Setup Menu, 126
TD400C, 14
components shipped with, 31
display backlight, 103
features, 18
specifications, 136
technical support, 7
templates, 46
templates, sample, 15
Text Display
configure, 71
text display area, 15
Text Display device versions, 3
Text Display wizard, 15
starting, 71
tasks for configuring, 70
Time and Date, 121
Troubleshooting the TD device, 163
Turkish (Latin 5) Character Set, 153
U
UL Standards, 5
Update rate
selecting for TD device, 75
user menu, 81
V
values
calculating, 85
variable
embedding into text of screen, 83
variables
editing, 106
view TD messages, 127
V-memory address
assigning for parameter block, 98
W
Weight, 133