Type: 22DILEM
Article No.: 010112
Ordering information
Connection technique Screw terminals
Description 4−pole
Conventional thermal current I th = I e
AC−1 Open Ith = IeA 10
Contacts N/O = Normally open 2 N/O
Contacts N/C = Normally closed 2 N/C
Can be combined with contactor DILE(E)M−10(−G)(...)
DILEM−4(−G)(...)
Contact sequence
Notes concerning the product group
Auxiliary contact module contacts:
...DILEM to EN 50 012
...DILE to EN 50 005
Contacts to EN 50012 should be given preference.
Auxiliary contact modules with interlocked opposing contacts.
Not in the case of early−make or late−break contacts
General
1
Standards IEC/EN 60947, VDE 0660,
CSA, UL
Maximum operating frequency
Mechanical Ops./h 9000
Climatic proofing
Damp heat, constant, to IEC
60068−2−78
Damp heat cyclic to IEC
60068−2−30
Ambient temperature
Open °C −25/50
Enclosed °C −25/40
Mechanical shock resistance (IEC/EN
60068−2−27)
Half−sinusoidal shock, 10 ms
Basic unit without auxiliary contact
module
Main contacts, make contacts g 10
Main contacts Make/break contacts g 10/8
Basic unit with auxiliary contact
module
Main contacts make contact g 10
Auxiliary contacts Make/break
contacts g 20/20
Protection type IP 20
Protection against direct contact
when actuated from front (IEC 536) Finger and back−of-hand
proof
Terminal capacity of auxiliary and
main contacts
Solid mm21 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Flexible with ferrule mm21 × (0.75 – 1.5)
2 × (0.75 – 1.5)
Solid or stranded AWG 18 – 14
Terminal screw M3.5
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 × 5.5
1 × 6
Max. tightening torque Nm 1,2
Terminal capacity springloaded
terminals main and control circuits
Solid mm21 × (1 – 2.5)
2 × (1 – 2.5)
2
Flexible with ferrule mm21 × (1 – 2.5)
2 × (1 – 2.5)
Standard screwdriver mm 0.6 × 3.5
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution
degree III/3
Rated insulation voltage
AC UiV AC 690
Rated operational voltage
Rated operational voltage UeV AC 690
Safe isolation to VDE 0106 Part 101
and Part 101/A1
between coil and contacts V AC 300
between the contacts V AC 300
Making capacity (cos to IEC/EN
60947) A 110
Breaking capacity
220/230 V A 90
380/400 V A 90
500 V A 64
660/690 V A 54
Short−circuit protection maximum
fuse
Type “2” coordination gL/gG A 10
Type “1” coordination gL/gG A 20
AC
AC−1 duty
conv. therm. current 3 pole 50 – 60
Hz
open
at 40 °C Ith A 22
at 50 °C Ith A 20
at 55 °C Ith A 19
enclosed Ith A 16
AC−3 duty
Rating, AC−3 motor load switch
380/400 V PkW 4
AC−4 duty
3
AC−4
380/400 V PkW 3
DC
Operations
Magnet systems
Duty factor % DF 100
Switching times at 100 % Uc
Reversing contactors
Arcing time at 690 V AC ms max. 12
Auxiliary contacts
Interlocked opposing contacts to ZH
1/457, including auxiliary contact
module Yes
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution
degree III/3
Rated insulation voltage UiV AC 690
Rated operational voltage
Rated operational voltage UeV AC 600
Safe isolation to VDE 0106 Part 101
and Part 101/A1
between coil and auxiliary contacts V AC 300
between the auxiliary contacts V AC 300
Rated operational current
AC–15
220/240 V IeA 4
380/415 V IeA 2
500 V IeA 1,5
DV−13
Contacts in series:
1 24 V A 2,5
2 60 V A 2,5
3 100 V A 1,5
3 220 V A 0,5
Conventional thermal current Ith A 10
Control circuit reliability (at Ue = 24 V
DC, Umin = 17 V, I min= 5.4 mA) Failure rate −8, < one failure at 100
million operations
Component lifespan at Ue = 240 V
AC–15 Operations × 1060,2
DC−13
4
L/R = 50 ms: 2 contacts in series at Ie
= 0.5 A Operations × 1060,15
Short−circuit rating without welding
Maximum overcurrent protective
device PKZM0−4
Short−circuit protection maximum
fuse
500 V A
gG/gL 6
500 V A fast 10
Current heat loss at Ith
Per contact W 0,2
Notes
At maximum permissible
ambient temperature.
Smoothed DC or
three−phase bridge rectifier
Making and breaking
conditions to DC−13, time
L/R constant as stated
Mounting position
As required except vertical with terminals A1/A2 at the bottom
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net
Copyright 2006 by Moeller GmbH. Subject to modifications. HPL−C2006GB−INT V2.3