D1U3CS-W-1300F-12-Hx4EC Series
81mm Front End AC-DC Power Converter
D1U3CS-W-1300F-12-Hx4EC.A01 Page 3 of 5
www.murata-ps.com/support
STATUS INDICATORS
Conditions LED Status
Standby Rail ON; Main Output OFF; AC Present & correct Blinking Green
Standby Rail ON; Main Output ON Solid Green
Main Output overcurrent; undervoltage, overvoltage warning Blinking Amber
FAN_FAULT; overtemperature; standby rail overcurrent, Main Output overcurrent or overvoltage Red
EMISSIONS AND IMMUNITY
Characteristic Standard Compliance
Input Current Harmonics IEC/EN 61000-3-2 Complies with Class A Limits
Voltage Fluctuation & Flicker IEC/EN 61000-3-3 Complies
Conducted Emissions FCC 47 CFR Part 15
CSIPR 22/EN55022 Class B
ESD Immunity IEC/EN 61000-4-2; Level 3; Criteria A
Radiated Field Immunity IEC/EN 61000-4-3 Level 3; Criteria B
Electrical Fast Transients/Burst Immunity IEC/EN 61000-4-4 Level 3; Criteria B
Surge Immunity IEC/EN 61000-4-5 Level 3; Criteria A
RF Conducted Immunity IEC/EN 61000-4-6 Level 3; Criteria A
Magnetic Field Immunity IEC/EN 61000-4-8 3A/m; Criteria B
Voltage Dips & Interruptions IEC/EN 61000-4-11
230Vin, 100% load, Phase 0°, Dip 100% Duration 10ms (A)
230Vin, 50% load, Phase 0°, Dip 100% Duration 20ms (VSB:A, V1:A)
230Vin, 100% load, Phase 0°, Dip 100% Duration > 12ms (VSB:A, V1:B)
OUTPUT CONNECTOR & SIGNAL INTERFACE
DC Output and Signal Connector: FCI# 51731-057-LF
NB: B4 is the shortest “last make, fi rst break” sequenced signal pin
Blade Assignment Function Description Current (Amps per Pin)
PB1, PB2, PB3 +12V GND Main Output Voltage, Return 30
PB4, PB5, PB6 +12V OUT Main Output Voltage 30
Signal Pin Assignment Signal Name Description
A1 PS_ON_L An input pulled up via an internal 10K ohm to the Standby rail. When pulled low (via an open collector/drain
drive or connection to GND) the Main Output will be turned on/enabled) N/A
A2 +12VRS_RETURN Main Output Remote Sense (-VE/Return) N/A
A3 TEMP_OK TTL compatible Logic HIGH provided when the temperature is within the allowable range of operation.
A4 PS_SEATED Internally connected to GND; when the power module is correctly seated the corresponding mating
connector pin is grounded and therefore allows detection that the power module is in situ. N/A
A5, B5, C5, D5 +VSB Standby Voltage Output 2.0
A6, B6, C6, D6 +VSB GND Standby Voltage Output, Return/GND 2.0
B1 AC_OK Incoming AC Source voltage “OK” (present and within operational limits) N/A
B2 +12VRS Main 12V output remote sense line N/A
B3 +12V_ISHARE Main 12V output current share bus N/A
B4 PS_INHIBIT/PS_KILL
This is the shortest “last make, fi rst break” (last to mate in the sequence).
If left open circuit then the main output will be inhibited (no output).
When inserted in to the system slot this pin must be pulled “low” by the system to enable (turn on) the
Main output and only after all other pins are connected and the power module is correctly seated.
N/A
C1 SDA I2C Serial Data Line N/A
C2 SCL I2C Serial Clock Line N/A
D1 D2 D3 D4 D5 D6
PB1 PB2 PB3 PB4 PB5 PB6
C1 C2 C3 C4 C5 C6
B1 B2 B3 B4 B5 B6
A1 A2 A3 A4 A5 A6