Timer modules for use in conjunction with
relay & socket.
86.00 - Multi-function & multi-voltage timer
module
86.30 - Bi-function & multi-voltage timer module
• Timer module type 86.00 for 90, 92, 96
series sockets and type 86.30 for 90, 92, 94, 95,
96, 97 series sockets
• Wide supply voltage range:
12…240VAC/DC (86.00)
12…24VAC/DC or 230…240VAC (86.30)
• LED indicator
86.00
86.30
86.00 86.30
• Time scale: from 0.05s to 100h
• Multi-function
• Plug-in for use with 90.02, 90.03, 92.03 and
96.04 sockets
• Time scale: from 0.05s to 100h
• Bi-function
• Plug-in for use with 90.02, 90.03, 92.03, 94.P3,
94.P4, 94.02, 94.03, 94.04, 95.P3, 95.P5, 95.03,
95.05, 96.02, 96.04, 97.P1, 97.P2, 97.01 and
97.02 sockets
AI: On-delay
DI: Interval
SW: Symmetrical flasher (starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
EE: Interval with control signal off
FE: Interval with control signal on and off
AI: On-delay
DI: Interval
Relay + socket
Wiring diagram
(without control signal)
Relay + socket
Wiring diagram
(with control signal)
Relay + socket
Wiring diagram
Contact specification
Contact configuration
See 56, 60 and 62 series relays
Note: Do not use with relays
62.3x.x012.x300 and 62.3x.x012.x600
See 40, 44, 46, 55, 56, 60 and
62 series relays
Rated current/Maximum peak current A
Rated voltage/
Maximum switching voltage VAC
Rated load AC1 VA
Rated load AC15 (230VAC) VA
Single phase motor rating (230VAC) kW
Breaking capacity DC1: 30/110/220V A
Minimum switching load mW (V/mA)
Standard contact material
Supply specification
Nominal voltage (UN) VAC (50/60Hz) 12…240 12…24 110…125 230…240
VDC 12…240 12…24 — —
Rated power AC/DC W 1.2 0.15
Operating range VAC (50/60Hz) 10.2…265 9.6…33.6 88…137 184…265
DC 10.2…265 9.6…33.6 — —
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (5…100)s, (0.5…10)min, (5…100)min, (0.5…10)h, (5…100)h
Repeatability % ±1 ±1
Recovery time ms ≤50 ≤50
Minimun control impulse ms 50 —
Setting accuracy full range % ±5 ±5
Electrical life at rated load in AC1 cycles See 56, 60 and 62 series relays See 40, 44, 46, 55, 56, 60 and 62 series relays
Ambient temperature range °C –20…+50 –20…+50
Protection category IP 20 IP 20
Approvals (according to type)
1
X-2016, www.findernet.com
H
86
SERIES
86 SERIES
Timer modules