PGFI Series - 20 Amp Portable (Cord) Series
272
PGFI Series
20 Amp Portable Series (Cord) GFCI / ELCI
INTRODUCTION
The LineGard™ 20 Amp Portable Series is an industrial grade ground fault circuit interrupter designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products. This product is the “Go Anywhere” protection device. Rated for 20 amps and
available at 120 VAC, 240 VAC, 208 VAC, or 277 VAC (UL 1053 compliant), the device is also available with either manual (safe start) or
automatic reset configuration. Standard offerings include products with plug and connector or flying leads for field configuring which
can be constructed into stand-alone cord sets or equipment integrated power supply cords. The product series is well suited for wet
location use with an achieved NEMA 4X rating.
Note that any power cord integrated with this device becomes OSHA compliant for portable power usage in confined space: OSHA 29
CFR 1926.404(b)(1)(ii) and 29 CFR 1926.405(a)(2)(ii)(G). Additionally, this product meets the requirements of NEC 590.6(a) & (b).
• Powerandfaultstatusindicators
• Electro-mechanicallylatchedcontactswillnot
de-latch under rough service usage
• ChemicalandUVresistantenclosure
• ClassAcULus943listed
• NEMA4Xrated(indoor/outdooruse)
• Doubleinsulateduserinterfaceforaddedsafety
• Availableinautomaticormanualresetconfigurations*
• Availablewithwiringdevicesorflyingleads
• 2-yearmanufacturer’swarranty
SPECIFICATIONS
Listing Type cULus Listed Class A
UL 943
CSA 22.2 No. 144
Rated Supply Voltage 120 VAC, 240 VAC, 208 VAC,
277 VAC (UL 1053 compliant)
Rated Current Up to 20 Amps or rating of wiring device
and/or cable
Trip Level, Class A 5mA +/– 1mA (UL 943)
Operating Frequency 60 Hz
Reset Type1Automatic or Manual
Ground Trip Current 4 mA to 6 mA
Overload Current 90 Amps @ 125VAC
Insulation Voltage 1,500 VRMS for 1 minute
Endurance Operations 3000 operations
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
2. Integrated or replacement cable must be indoor/outdoor 3-conductor cable of type
ST, SJT, SE, SJE, SO or SJO