CSM_CS1W-CLK_DS_E_5_1
1
SYSMAC CS-series Controller Link Units
CS1W-CLK
New Controller Link Units, Now
with 4,000 Send Words
The Controller Link is an FA network that can send
and receive large amounts of data easily and at high
speed. The Controller Link supports data links that
enable sharing data between PLCs and computers
and a message service that enables sending and
receiving data whenever required.
With Wired Controller Link Units, systems can be
flexibly built by using Repeater Units to enable T-
branches, long-distance wiring, and converting part of
the network to optical cable.
Features
Large-capacity data links are easily achieved without programming simply by setting data link tables.
Up to 20,000 *1 send/receive words can be set per node for Units (up to 62,000 words for Boards).
Data links can be performed with up to 4,000 *2 words per node while ensuring data concurrency.
User-set data link tables can be changed while data links are operating. *3
Errors for the entire system can be monitored by using error diagnosis support software and a variety of status flags.
With the token ring mode of Optical Ring Controller Link Units/Boards, duplex communications paths enable communications to continue
normally even if the cable becomes disconnected.
Detecting locations of disconnection greatly shortens time required for maintenance.
Installing Controller Link Units in a CS1D system enables Duplex Communications Units to further enhance reliability. *4
*1. Supported for unit version 1.2 or later.
*2. CS1W-CLK@3 and 3G8F7-CLK@3 are supported.
*3. Supported for CS1W-CLK@3, 3G8F7-CLK@3, and models ending with "-V1" (CS1W-CLK12-V1 *5 and CS1W-CLK52-V1 *5 with lot numbers
0306@@_@@@ or later ).
*4. Supported for CS1W-CLK13/CLK12-V1 *5/CLK53/CLK52-V1 *5 and CS1D Duplex and Simplex Systems.
*5. Discontinuation models in July 2012.
CS1W-CLK23 CS1W-CLK13 CS1W-CLK53
2
CS1W-CLK
System Configuration
Wired Controller Link Units
A: Wired Controller Link Unit (1): Twisted-pair cable
B: Wired Controller Link Support Board (2): Optical cable
C: Wire-to-Optical Repeater Unit
D: Wire-to-Wire Repeater Unit
*At 500 kbits/s
Optical Controller Link Units
A: Optical Ring Controller Link Unit
B: Optical Ring Controller Link Support Board
(1): Optical cable
Basic Wiring (Daisy Chain Connections) T-Branch Wiring and Partial Conversion to
Optical Cable
Long-distance Wiring
Token Ring Mode Token Bus Mode
AA
B
1 km Max. *
AB
A
(1)
AA
B
AA
A
B
DC
(2)
C
(1)
(1)
(1)
AA
BA
D
1 km Max. *
1 km Max. * 1 km Max. *
D
(1) (1)
(1)
AA
AAA
B
B
(1)
AA
AAA
B
B
(1)
CS1W-CLK
3
Ordering Information
Controller Link Units
*1. Use the following special cable for shielded, twisted-pair cable.
ESVC0.5×2C-13262 (Bando Electric Wire : Japanese Company)
ESNC0.5×2C-99-087B (Nihon Electric Wire & Cable Corporation : Japanese Company)
ESPC 1P×0.5mm2 (Nagaoka Electric Wire Co.,Ltd. : Japanese Company)
Li2Y-FCY2×0.56qmm (Kromberg & Schubert, Komtec Department : German Company)
1×2×AWG-20PE+Tr.CUSN+PVC (Draka Cables Industrial : Spanish Company)
#9207 (Belden : US Company)
*2. When using a wire-to-optical (H-PCF) cable, use a H-PCF cable (for both Controller Link and SYSMAC LINK) or a H-PCF optical fiber cable
with connector.
*3. When using a wire-to-optical (GI) cable, use a GI optical cable that matches the specifications.
Accessories
The Optical Fiber Cable Bracket is included in CS1W-CLK13 and CS1W-CLK53.
Unit
classifi-
cation
Product
name
Specifications No. of unit
numbers
allocated
Current
consumption
(A)
Model Standards
Communications
cable
Communications
type
Duplex
support
Max. Units
mountable per
CPU Unit
5 V
DC
26 V
DC
CS1
CPU
Bus Unit
Controller
Link
Unit Wired shielded
twisted-pair cable
*1
Data links and
message service
No 8 1 0.33 CS1W-CLK23
UC1, N, L,
CE
Controller
Link
Unit Optical ring H-PCF
cable
*2
Yes. Unit
duplexing
and cable
loop back are
supported.
Non-duplex: 8,
Duplex: 11
(6 Units
comprising 3
sets of Duplex
Units + 5
Non-duplex
Units)
10.52CS1W-CLK13
Controller
Link
Unit
Optical ring GI cable
*310.65CS1W-CLK53
4
CS1W-CLK
Controller Link Support Boards
*The CD-ROM contains the following software.
Controller Link (PCI) Driver
FinsGataway Version 2003 (PCI-CLK Edition)
FinsGataway Version 3 (PCI-CLK Edition)
Setup Diagnostic Utility
C Library
Repeater Units
Using Repeater Units enables T-branches and long-distance wiring for Wired Controller Link networks, 62-node configurations, and converting
part of the network to optical cable.
Note: 1. When using wire-to-optical (H-PCF) cable, use a H-PCF cable (for both Controller Link and SYSMAC LINK) or a H-PCF optical fiber cable
with connector.
2. When using wire-to-optical (GI) cable, use a GI optical cable (for Controller Link).
Relay Terminal Block
Controller Link Units can be replaced without stopping the communications of the entire network if a Relay Terminal Block is installed in advance
on the Unit in a Wired Controller Link network. Relay Terminal Blocks cannot be used on Controller Link Support Boards.
Duplex Optical Fiber Cable (H-PCF Cable)
This cable is used to connect Units in active mode (ACT) and standby mode (STB) in a CS1D Duplex System.
*Discontinuation models in July 2012.
Product name
Specifications
Accessories Model Standards
Communications
cable Communications type
Controller Link
Support Board
for PCI Bus
Wired shielded
twisted-pair cable
Data links and message
service
CD-ROM × 1 *
INSTALLATION GUIDE (W467) × 1
Communications connector × 1
3G8F7-CLK23-E
CE
H-PCF optical model CD-ROM × 1 *
INSTALLATION GUIDE (W467) × 1
Optical Fiber Cable Bracket × 1
Power supply connector × 1
3G8F7-CLK13-E
GI optical model 3G8F7-CLK53-E
Name Specifications Model Standards
Controller Link
Repeater Unit Wire-to-Wire Model CS1W-RPT01
UC1, CE
Wire-to-Optical (H-PCF) Model (See note 1.) CS1W-RPT02
Wire-to-Optical (GI) Model (See note 2.) CS1W-RPT03
Name Specifications Model Standards
Relay Terminal Blocks for
Wired Controller Link Units
Used for Wired Controller Link Units (set of 5) CJ1W-TB101
Name Application Specifications Model Standards
Duplex Optical Fiber Cable CS1W-CLK13 or
CS1W-CLK12-V1 * in a CS1D system
H-PCF cable for connecting Duplex Controller Link Units
Cable length: 50 cm CS1D-CN051
CS1W-RPT01
PWR
T/R1
T/R2
SL1
TER SW
TER SW
ON
SL2
DC24V
INPUT
1 BAUD
2 RA
TE
SW1
CS1W-CLK
5
H-PCF Cables and Optical Connectors
*1. Discontinuation models in July 2012.
*2. Full-lock Optical Connectors (Crimp-cut) (S3200-COCF2071) cannot be used with the CS1W-SLK11. Use a Half-lock Cable (S3200-
COCF2571) or a H-PCF Optical Fiber Cable with Connector (S3200-CN@@@-@@-@@).
H-PCF Optical Fiber Cables with Connectors (Black Composite Cables with Two-Optical Lines and Two Power Supply Lines)
Optical connectors for H-PCF Optical Cables with Connectors are adhesive polished.
Cable Length
The following cable lengths are available: 2 m, 5 m, 15 m, and 20 m. For lengths of 21 m or more, contact your OMRON sales representative.
Model Numbers
Name Application/construction Specifications Model Standards
Optical Fiber Cables
Controller Link,
SYSMAC LINK,
SYSBUS 1. Optical fiber single-core cord
2. Tension member
(plastic-sheathed wire)
3. Filler (plastic)
4. Filler surrounding signal wires
(plastic, yarn, or fiber)
5. Holding tape (plastic)
6. Heat-resistant PV sheath
Two-core optical
cable with tension
member
Black 10 m S3200-HCCB101
Black 50 m S3200-HCCB501
Black 100 m S3200-HCCB102
Black 500 m S3200-HCCB502
Black 1000 m S3200-HCCB103
Orange 10 m S3200-HCCO101
Orange 50 m S3200-HCCO501
Orange 100 m S3200-HCCO102
Orange 500 m S3200-HCCO502
Orange 1000 m S3200-HCCO103
Optical
Connectors
(Crimp-cut)
Controller Link: CS1W-CLK13
CS1W-CLK12-V1 *1
3G8F7-CLK13-E
3G8F7-CLK12-EV1 *1
CS1W-RPT02
SYSMAC LINK: CS1W-SLK11
3G8F7-SLK11-E
C200HW-SLK13/14
Half lock S3200-COCF2571
Controller Link: CS1W-CLK13
CS1W-CLK12-V1 *1
3G8F7-CLK13-E
3G8F7-CLK12-EV1 *1
CS1W-RPT02
SYSMAC LINK: 3G8F7-SLK11-E
Full lock S3200-COCF2071
*2
Application Appearance Model Standards
Controller Link,
SYSMAC LINK
S3200-CN@@@-20-20
S3200-CN@@@-20-25
S3200-CN@@@-25-25
1
2
4
3
5
6
@@@
@@@
201
501
102
152
202
Length
2 m
5 m
10 m
15 m
20 m
20
25
Number Connector lock
Half-lock
Full-lock
(1) 2 m, 5 m, 10 m, 15 m, or 20 m
S3200-CN@@@
@@@
-20-25
1. 2. 3. 3. Specify the
cable length
in meters.
(2) 21 m or longer
S3200-CN-20-20
1.
2. Cable length 3. Connectors (both ends)
1. H-PCF
Optical Fiber Cable
Cable length
6
CS1W-CLK
Optical Connector Assembly Tool
Note: There is a risk of quality problems when using cables assembled by typical users, so we recommend purchasing cables with preattached
connectors or having a qualified technician assemble the cables.
GI Optical Cables
A qualified technician must select, assemble, and install GI Optical Fiber Cable, so always let an optical cable specialist handle the GI cable.
Usable Optical Cables and Optical Connectors
Optical fiber types: Graded, indexed, multi-mode, all quartz glass, fiber (GI-type AGF cable)
Optical fiber construction (core diameter/clad diameter): 62.5/125 μm or 50/125 μm
Optical fiber optical characteristics of optical fiber: Refer to the tables.
Optical connector: ST connector (IEC-874-10)
50/125-μm AGF Cable
Lf is fiber length in km, Ta is ambient temperature, and
λ is the peak wavelength of the test light source.
62.5/125-μm AGF Cable
Lf is fiber length in km, Ta is ambient temperature, and
λ is the peak wavelength of the test light source.
International Standards
The standards indicated in the Standards column are those current for UL, CSA, cULus, cUL, NK, and Lloyd standards and EC Directives as
of the end of July 2007. The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA,
UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
Ask your OMRON representative for the conditions under which the standards were met.
Mountable Racks
*1. Discontinuation models in July 2012.
*2. Optical Ring Controller Link Units support 11 Units maximum for duplex (6 Units comprising 3 sets of Duplex Units + 5 Non-duplex Units).
*3. Optical Ring Controller Link Units support 7 Units maximum for duplex (6 Units comprising 3 sets of Duplex Units + 1 Non-duplex Unit).
Name Applicable Unit Model Manufacturer Standards
Optical
Fiber
Assembly
Tool
(See note.)
This tool is used on site for mounting crimp-cut connectors and hard
plastic-clad silica optical fiber for optical transmission systems of
SYSMAC C-series SYSBUS, SYSMAC LINK, and Controller Link.
CAK-0057 Sumitomo Electric
Industries, Ltd.
Item
Minimum Standard Maximum
Conditions
Numerical
aperture (N.A) 0.21 −−
Transmission
loss (dB) −−
3.0Lf 0.5 km Lf
λ = 0.8 μm
Ta = 25°C
3.0Lf+0.2 0.2 km Lf
0.5 km
3.0Lf+0.4 Lf 0.2 km
Connection
loss (dB) −−1.0 λ = 0.8 μm, one location
Transmission
bandwidth
(MHz-km)
500 −−λ = 0.85 μm (LD)
Item
Minimum Standard Maximum
Conditions
Numerical
aperture (N.A) 0.28 −−
Transmission
loss (dB) −−
3.5Lf 0.5 km Lf
λ = 0.8 μm
Ta = 25°C
3.5Lf+0.2 0.2 km Lf
0.5 km
3.5Lf+0.4 Lf 0.2 km
Connection
loss (dB) −−1.0 λ = 0.8 μm, one location
Transmission
bandwidth
(MHz-km)
200 −−λ = 0.85 μm (LD)
Model
CS1 System CS1D System
CPU Rack
Expansion
Backplane (including
Long-distance
Expansion Rack)
SYSBUS
Remote
I/O
Slave
Rack
C200HX/HG/
HE
Expansion I/O
Rack
CPU Rack Expansion
Backplane
CS1W-BC CS1W-BI CS1D-BC CS1D-BI
@@3@@2@@3@@2052 042D 082S 092 082D
CS1W-CLK23
CS1W-CLK13
CS1W-CLK53
Unit version 2.0
8 Units (per CPU Unit)
Not
supported Not supported
8 Units (per CPU Unit)
CS1W-CLK21-V1
CS1W-CLK12-V1
*
1
CS1W-CLK52-V1
Unit version 1.2 8 Units *2 (per CPU Unit)
CS1W-CLK21-V1
CS1W-CLK12-V1
*
1
CS1W-CLK52-V1
Pre-Ver. 1.2 4 Units (per CPU Unit) 4 Units *3 (per CPU Unit)
CS1W-CLK
7
Communications Specifications
*1. Discontinuation models in July 2012.
*2. The maximum distance between nodes depends on the processing method for connectors and cables.
*3. With wired models, the maximum number of nodes is 32 if Repeater Units are not used. A Repeater Unit is required when building a network
with more than 32 nodes. If a Repeater Unit is used, be sure to use only the following Controller Link Units or Boards and set the Wired Network
62 Node Enable Bit in the DM Parameter Area software switches at all nodes.
CS1W-CLK23/CLK21-V1 *1
CJ1W-CLK23/CLK21-V1 *1
3G8F7-CLK23-E/CLK21-EV1 *1
*4. CX-Net in CX-Programmer version 3.1 or earlier can be used only in a system with a maximum of 32 nodes (node address 1 to 32). If a system
is to be used with a maximum of 62 nodes (node addresses 1 to 62), use CX-Net in CX-Programmer version 3.2 or higher or the CX-Integrator.
*5. If duplex Controller Link Units are used, the effective maximum number of nodes will be 62 (i.e., the maximum number of nodes in standby
mode (STB)).
*6. CS-series PLCs do not have a Link Area, but LR000 to LR199 are automatically converted CIO 1000 to CIO 1199.
*7. Only when a CS1W-CLK13/12-V1 *1/53/52-V1 *1 installed in a CS1D system is used in token ring mode.
Items Specifications
Model
CS1W-CLK23
3G8F7-CLK23-E
CS1W-CLK21-V1 *1
3G8F7-CLK21-EV1 *1
CS1W-CLK13
3G8F7-CLK13-E
CS1W-CLK12-V1 *1
3G8F7-CLK12-EV1 *1
CS1W-CLK53
3G8F7-CLK53-E
CS1W-CLK52-V1 *1
3G8F7-CLK52-EV1 *1
Type Wired (shielded twisted-pair cable) Optical Ring (H-PCF cable) Optical Ring (GI cable)
Communications
method N:N token-bus method N:N token-ring method (token-ring mode)
N:N token-bus method (token-bus mode)
Code Manchester code
Modulation Baseband code
Synchronization Flag synchronization (conforms to HDLC frames)
Transmission path
format Multidrop method (bus type) Ring method (token-ring mode)
Daisy-chain method (token-ring mode)
Transmission speed
The following are the maximum
transmission distances depending on
the transmission speed.
2 Mbits/s: 500 m
1 Mbits/s: 800 m
500 kbits/s: 1 km
2 Mbits/s
Maximum
transmission distance 20 km 30 km
Maximum distance
between nodes
Not specified. (Maximum transmission
distance must be satisfied for the
entire system.)
Crimp-cut: 800 m
Adhesive polishing: 1 km *2
62.5/125 μm: 2 km
50/125 μm: 1 km
Medium Specified shielded twist-pair cable
Two signal wires, one shield H-PCF cable (two-core optical cable) GI cable (two-core optical cable:
62.5/125 μm, 50/125 μm)
Node connection
method
PLC: Connection to terminal block
Computer: Connection using special
(supplied) connector
Connection using special connector
(full-lock connector or half-lock
connector)
Connection using ST connector
Maximum number of
nodes 32 or 62 nodes *3 *4 62 *5
Applicable
Programming Devices CX-Integrator in CX-One, CX-Net in CX-Programmer *4, and Programming Console
Communications
functions Data links and message service
Number of data link
words
Send words per node: 4,000 words max. (CS1W-CLK@3), 1,000 words max. (All other Units)
Number of send/receive words per node: 12,000 words max. (Pre-Ver. 1.2)
20,000 words max. (unit Ver. 1.2 or later)
Total number of send words per network: 62,000 words max.
Data link areas PLC: Bit areas (CIO Area, Work Area, Link Area *6), Data Memory (DM), Extended DM Area (EM)
Computer: FinsGateway event memory
Message length 2,012 bytes max. (including the header)
RAS functions
Polling node backup function
Self-diagnosis function (hardware
checking at startup)
Echoback test and broadcast test
(using the FINS command)
Watchdog timer
Error log function
Polling node backup function
Self-diagnosis function (hardware checking at startup)
Echoback test and broadcast test (using the FINS command)
Watchdog timer
Error log function
Node bypass function
Transmission path duplication (for ring method in token-ring mode only)
Disconnect detection and notification (token-ring mode only)
Node connection configuration data reading (for ring method in token-ring
mode only)
Duplex operation of Communications Units *7
Error control Manchester code check
CRC check (CCITT X16+X12+X5+1)
8
CS1W-CLK
Individual Specifications
Controller Link Units
*Discontinuation models in July 2012.
Controller Link Support Boards (for PCI Bus), New Models
Note: 1. Install the software from CD Ver. 3.10 or higher if the operating system is Windows 7 (32bit) or Windows Vista.
2. Install FinsGateway version 3 if the operating system is Windows NT 4.0 (Service pack 3 or higher), Windows ME, or Windows 98SE. In
that case, however, the new functions of Controller Link Support Boards for the PCI Bus cannot be used (i.e., automatic data link creation
with 1:N allocation, changing data link tables with active data links, 62-node setting for wired models, and maximum of 4000 send words).
Controller Link Support Boards (for PCI Bus), Old Models
*1. Discontinuation models in July 2012.
*2. Install FinsGateway version 3 if the operating system is Windows NT 4.0 (Service pack 3 or higher), Windows ME, or Windows 98SE. In that
case, however, the new functions of Controller Link Support Boards for the PCI Bus cannot be used (i.e., automatic data link creation with 1:N
allocation, changing data link tables with active data links, 62-node setting for wired models, and maximum of 4000 send words).
Item Specifications
Model CS1W-CLK23
CS1W-CLK21-V1 *CS1W-CLK13
CS1W-CLK12-V1 *CS1W-CLK53
CS1W-CLK52-V *
Supported PLC All CS-series CPU Units
Number of mountable Units Unit version 1.2 or later: 8 Units max., Pre-Ver. 1.2: 4 Units max.
Installation site Install onto a CPU Backplane or CS-series Expansion Backplane (classified as a CPU Bus Unit).
Storage location for network parameters
and manually set data tables CPU Bus Unit Area (in the CPU Unit parameter area)
Storage location for routing tables CPU Unit parameter area
Weight 220 g 300 g
(excluding mounting bracket)
300 g
(excluding mounting bracket)
Current
consumption
5 V in PLC 0.33 A 0.52 A 0.65 A
26 V in PLC −−−
External 24 V 0.20 A 0.26 A
Item Specifications
Models 3G8F7-CLK23-E 3G8F7-CLK13-E 3G8F7-CLK53-E
Applicable computers
IBM PC/AT or compatible
CPU: Intel Celeron 400 MHz or better
Main memory: 128 MB minimum
One or more PCI bus slots (PCI bus revision 2.0 or higher, power supply: 5 V)
Available hard disk space: 70 MB min.
CD-ROM drive: One required for installation
Display: VGA (640 × 480 (pixels) min.)
(Other conditions conform to the OS.)
Compatible OS
FinsGateway Version 2003 (See note 1.)
Windows 7 (32bit) Professional
Windows 7 (32bit) Home Premium
Windows Vista Business
Windows Vista Home Premium
Windows XP Professional
Windows XP Home Edition
Windows 2000 Professional
FinsGateway Version 3 (See note 2.)
Windows XP Professional
Windows XP Home Edition
Windows 2000 Professional
Windows NT 4.0 (Service Pack 3 or higher)
Windows ME
Windows 98SE
Weight 104 g
120 g (excluding mounting bracket) 124 g (excluding mounting bracket)
Current
consumption
5 V in PLC 0.35 A 0.54 A 0.60 A
External 24 V 0.35 A 0.35 A
Item Specifications
Models *13G8F7-CLK21-EV1 3G8F7-CLK12-EV1 3G8F7-CLK52-EV1
Applicable computers
IBM PC/AT or compatible
CPU: Intel Celeron 400 MHz or better
Main memory: 128 MB minimum
One or more PCI bus slots (PCI bus revision 2.0 or higher, power supply: 5 V)
Available hard disk space: 70 MB min.
CD-ROM drive: One required for installation
Display: VGA (640 × 480 (pixels) min.)
(Other conditions conform to the OS.)
Compatible OS *2
FinsGateway Version 2003
Windows XP Professional
Windows XP Home Edition
Windows 2000 Professional
FinsGateway Version 3
Windows XP Professional
Windows XP Home Edition
Windows 2000 Professional
Windows NT 4.0 (Service Pack 3 or higher)
Windows ME
Windows 98SE
Weight 104 g
120 g (excluding mounting bracket) 124 g (excluding mounting bracket)
Current
consumption
5 V in PLC 0.35 A 0.54 A 0.60 A
External 24 V 0.35 A 0.35 A
CS1W-CLK
9
Repeater Units
Repeater Units are used to expand the Controller Link network for wired models. For Wired-to-optical Repeater Units, always use a set of two (1:1).
Optical Ring Controller Link Units and Boards cannot be connected to the optical cable section between Repeater Units.
External Interfac
CS1W-CLK23/CS1W-CLK21-V1 *
*Discontinuation models in July 2012.
Definition of Terminal Block Pin Names for Communications Cables
Crimp Terminals
Use crimp terminals (M3) having the dimensions shown below.
Item Specifications
Model CS1W-RPT01 CS1W-RPT02 CS1W-RPT03
Supported Units and Boards All wired Controller Link Units and Boards
Note: If a maximum of 62 nodes is used, models that support 62 nodes must be used.
Transmission path Wire-to-wire Wire-to-optical (H-PCF) Wire-to-optical (GI)
Transmission path format Multi-drop
Tree 1:1 1:1
Installation Repeater Units are not mounted to the PLC. They are mounted separately with screws or on a DIN
Track.
Weight 126 g 113 g
(excluding mounting bracket)
116 g
(excluding mounting bracket)
Allowable power supply voltage range 20.4 to 26.4 VDC (24 VDC 15 V to +10%)
Current consumption 0.06 A at 24 VDC 0.06 A at 24 VDC 0.07 A at 24 VDC
Inrush current 2.5 A max. (24 VDC with rise time of 5 ms)
Marking Notation Signal name Line color
BD H Communications data, high Black
@BD L Communication data, low White
None SHLD Shield None
LED Indicators
Display the Unit and network status.
Unit Number Switch
One rotary switch. The unit number of the Unit on the PLC is set in single-digit
hexadecimal.
Node Address Switches
Two rotary switches. The node address of the Unit on the Controller Link Network
is set in 2-digit decimal.
Baud Rate Switches
A four-pin DIP switch. The following setting is made.
Pins 1 and 2: Baud rate
Pins 3 and 4: Not used (always OFF).
Terminating Resistance Switch
A slide switch. Use this switch to set the terminating resistance to ON for nodes at
both ends of the Controller Link Network.
Terminal Block for the Communications Cable
Terminals to connect to the Controller Link Network communications cable
(twisted-pair cable).
6.2 mm max. 6.2 mm max.
10
CS1W-CLK
CS1W-CLK13/CS1W-CLK12-V1 *
*Discontinuation models in July 2012.
Crimp Terminals
Use crimp terminals (M3) having the dimensions shown below.
CS1W-CLK53/CS1W-CLK52-V1 *
*Discontinuation models in July 2012.
Crimp Terminals
Use crimp terminals (M3) having the dimensions shown below.
LED Indicators
Display the Unit and network status.
Unit Number Switch
One rotary switch. The unit number of the Unit on the PLC is set in single-digit
hexadecimal.
Node Address Switches
Two rotary switches. The node address of the unit on the Controller Link Network
is set in 2-digit decimal.
Optical Connectors
Connect to communications cables (H-PCF fiber optical cables) for the Controller
Link network.
Power Supply Terminal Block
Connect to a backup power supply for the node bypass function.
6.2 mm max. 6.2 mm max.
LED Indicators
Display the Unit and network status.
Unit Number Switch
One rotary switch. The unit number of the Unit on the PLC is set in single-digit
hexadecimal.
Node Address Switches
Two rotary switches. The node address of the unit on the Controller Link Network
is set in 2-digit decimal.
Optical Connectors
Connect to communications cables (GI optical cables) for the Controller Link network.
Power Supply Terminal Block
Connect to a backup power supply for the node bypass function.
6.0 mm max. 6.0 mm max.
CS1W-CLK
11
Differences in Specifications of New and Old Models
Controller Link Units
Note: 1. For wired models, the maximum number of nodes is 32 if Repeater Units are not used.
2. Use models with lot numbers 0306@@ (June 2003 production) or later to enable duplexing in a CS1D System using the Pre-Ver. 1.2
CS1W-CLK12-V1 or CS1W-CLK52-V1.
3. Old models and new models can be used mixed on the same network. In that case, however, build the system using the specifications
for the old models. The data link send/receive words can be separately set to their maximums when new and old models are mixed.
Controller Link Support Boards (for PCI Bus)
Note: 1. For wired models, the maximum number of nodes is 32 if repeater units are not used.
2. Old models and new models can be used mixed on the same network. In that case, however, build the system using the specifications
for the old models. The data link send/receive words can be separately set to their maximums when new and old models are mixed.
3. FinsGateway Version 2003 is compatible with Windows 7 (32bit) (CD Ver.3.10 or higher), Windows Vista (CD Ver.3.10 or higher),
Windows XP and Windows 2000. For Windows NT4.0 (Service Pack 3 or higher), Windows ME, or Windows 98SE, use FinsGateway
Version3. (With FinsGateway Version 3, only functions supported by the 3G8F7-CLK21/CLK12/CLK52 can be used.)
Model
CS1W-CLK23
CS1W-CLK13
CS1W-CLK53
Note: The following models are
discontinued.
CS1W-CLK21-V1
CS1W-CLK12-V1
CS1W-CLK52-V1
Note: The following models are
discontinued.
CS1W-CLK21-V1
CS1W-CLK12-V1
CS1W-CLK52-V1
Note: The following models are
discontinued.
CS1W-CLK21
CS1W-CLK12
CS1W-CLK52
Unit version 2.0 Unit version 1.2 Pre-Ver. 1.2 Pre-Ver. 1.2
Number of data link
send words (data link
areas that are created
for a single node in a
single PLC)
20,000 words max. 12,000 words max.
Number of send words
per node (total of area 1
and area 2)
4,000 words max.
(user-set links only) 1,000 words max.
Data link areas Allocation setting can be performed for same areas in
areas 1 and 2.
Allocation setting can be performed for same areas in
areas 1 and 2.
Max. Units mountable
per PLC 8 4
Automatic data link
setting Choose from equality layout or 1:N allocations (common type, 1:1, chain type) Supported for equality
layout only.
Changing data link
allocations during
active data links
Supported (Data link tables can be changed during active data links.) Not supported.
Maximum connectable
nodes 62 nodes (See note 1.)
Wired model: 32 nodes
Optical ring model: 62
nodes
Duplex support Supported (optical ring model only) (See note 2.) Not supported
Mixed use Yes (See note 3.)
Compatible support
software
CX-Integrator for CX-One
V2.1or higher, or CX-Net for
CX-Programmer Ver. 7.2 or
higher
CX-Net for CX-Programmer
Ver. 5.0 or higher
CX-Net for CX-Programmer
Ver. 3.2 or higher
CX-Net for CX-Programmer
Ver. 1.0 or higher
Model
3G8F7-CLK23-E
3G8F7-CLK13-E
3G8F7-CLK53-E
Note: The following models are
discontinued.
3G8F7-CLK21-EV1
3G8F7-CLK12-EV1
3G8F7-CLK52-EV1
Note: The following models are
discontinued.
3G8F7-CLK21-E
3G8F7-CLK12-E
3G8F7-CLK52-E
Number of data link send/
receive words (data link
areas for sending/receiving
that are created for a single
node in a single computer)
62,000 words max. 32,000 words max.
Send words per node 4,000 words max.
(user-set links only) 1,000 words max.
Changing data link
allocations during active
data links
Supported. (Data link tables can be changed during active data links.) Not supported.
Maximum connectable nodes 62 nodes (See note 1.) Wired model: 32 nodes
Optical ring model: 62 nodes
Mixed use Yes (See note 2.)
Compatible FinsGateway
(See note 3.)
FinsGateway Version 2003.21 or
higher (In CD Ver. 3.00 or higher)
FinsGateway Version 2003.00 or
higher (In CD Ver. 2.00 or higher)
FinsGateway Version 3.00 or higher
(In CD Ver. 1.00 or higher)
Compatible support software
CX-Integrator for CX-One Ver. 2.1
or higher, or CX-Net for
CX-Programmer Ver. 7.2 or higher
CX-Net for CX-Programmer Ver.
3.2 or higher CX-Net for Ver. 1.0 or higher
12
CS1W-CLK
Usage Precautions
Old models and new models can be used mixed on the same network. In that case, however, build the system using the specifications for the
old models. The data link send/receive words can be separately set to their maximums when new and old models are mixed.
Repeater Units can be used to expand a Wired Controller Link Network. For Wired-to-optical Repeater Units, always use a set of two (1:1).
Optical Ring Controller Link Units and Boards cannot be connected to the optical cable section between Repeater Units.
Connect Repeater Units so that there are no more than two stages between any two nodes. One set of two Wire-to-Optical Repeater Units is
counted as one stage.
CS1W-CLK
13
Dimensions (Unit: mm)
CS1W-CLK23/CS1W-CLK21-V1 *
CS1W-CLK13/CS1W-CLK12-V1 *
CS1W-CLK53/CS1W-CLK52-V1 *
Note: The dimensions in parentheses are for the CS1W-CLK53 (including the terminal cover).
*Discontinuation models in July 2012.
10135
130
10135
130
101
130
35
10
(13.5)
14
CS1W-CLK
Related Manuals
Cat. No. Models Name Application Description
W309
CS1W-CLK23
CS1W-CLK21-V1
CJ1W-CLK23
CJ1W-CLK21-V1
C200HW-CLK21
CVM1-CLK21
CQM1H-CLK21
CS1W-RPT01/02/03
Controller Link Units
Operation Manual
Used when information
regarding operating
procedures for Wired
Controller Link Units is
needed.
Describes operating procedures
for Controller Link Units.
Controller Link Units can
connect to Wired Controller Link
Units.
W422
3G8F7-CLK12-V1
3G8F7-CLK52-V1
3G8F7-CLK21-V1
Controller Link Support Boards for PCI Bus
Installation Guide
(3G8F7-CLK12/21/52-V1)
Used when information
regarding setup procedures
for Controller Link Support
Boards for PCI bus
connections is needed.
Describes the setup method for
the Controller Link Support
Boards for PCI bus connections.
W467
3G8F7-CLK13
3G8F7-CLK12-V1
3G8F7-CLK53
3G8F7-CLK52-V1
3G8F7-CLK23
3G8F7-CLK21-V1
Controller Link Support Board for PCI Bus
Installation Guide
(3G8F7-CLK13/12-V1/53/52-V1/23/21-V1)
Used when information
regarding setup procedures
for Controller Link Support
Boards for PCI bus
connections is needed.
Describes the setup method for
the Controller Link Support
Boards for PCI bus connections.
W383
3G8F7-CLK13
3G8F7-CLK12-V1
3G8F7-CLK53
3G8F7-CLK52-V1
3G8F7-CLK23
3G8F7-CLK21-V1
Controller Link Support Boards for PCI Bus
Operation Manual
Used when information
regarding setup procedures
for Controller Link Support
Boards for PCI bus
connections is needed.
Describes the setup method for
the Controller Link Support
Boards for PCI bus connections.
W370
CS1W-CLK13
CS1W-CLK12-V1
CVM1-CLK12
CS1W-CLK53
CS1W-CLK52-V1
CVM1-CLK52
Optical Ring Controller Link Units
Operation Manual
Used when information
regarding operating
procedures for Optical Ring
Model Controller Link Units is
needed.
Describes the operating
procedures for Controller Link
Units. Controller Link Units can
connect to Controller Link
Networks (Optical Ring System
for H-PCF Cable, or GI Cable) .
Refer to this manual for
information regarding the
discontinued CS1W-CLK11
Optical Bus Controller Link Unit.
W464 CXONE-AL@@C-V@/
AL@@D-V@CX-Integrator Operation Manual
Used when network setup or
network monitoring needs to
be performed.
Describes the operating
procedures for the
CX-Integrator.
W463 CXONE-AL@@C-V@/
AL@@D-V@CX-One FA Integrated Tool Package
Setup Manual
Used when installing
software from the CX-One.
Provides an overview of the FA
Integration Tool Package
CX-One, and describes the
CX-One installation procedures.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2012.7
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2012 All Right Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
CS1W-CLK21-V1 3G8F7-CLK52-EV1 CVM1-CLK52 CS1W-SLK11 CS1W-CLK52-V1 CS1W-CLK53 CS1W-CLK13
CS1W-CLK23