CATALOG
NUMBER
CURRENT
RATIO
ACCURACY
AT 60 Hz
BURDEN
VA at 60 Hz
7**—101 100:5 +2% 2.5
7**—151 150:5 +1% 5.0
7**—201 200:5 +1% 5.0
7**—251 250:5 +1% 5.0
7**—301 300:5 +1% 12.5
7**—401 400:5 +1% 15.0
7**—501 500:5 +1% 25.0
7**—601 600:5 +1% 30.0
7**—751 750:5 +1% 30.0
7**—801 800:5 +1% 35.0
7**—102 1000:5 +1% 35.0
7**—122 1200:5 +1% 35.0
7**—152 1500:5 +1% 40.0
7**—162 1600:5 +1% 45.0
**Note: When ordering, prefix Cat No. with model designation required i.e. 7SFT—501, 76RL—501, etc.
Models 7SHT, 7RT and 7RL Shown
Current Transformer
Current Transformer
Model 7
Window Diameter 2.50”
APPLICATION:
With ammeters, wattmeters, and cross current
compensation.
FREQUENCY:
50-400 Hz.
INSULATION LEVEL:
600 Volts, 10 kV BIL full wave.
Flexible leads are UL 1015, 105oC., CSA approved.
#16 AWG, 24” long.
Non-standard length to be specified.
Terminals are brass studs No. 8-32 with one
flatwasher, lockwasher and regular nut.
SFT and SHT case styles also available as SFL and
SHL with leads.
Mounting bracket kit 0221B00182 when required
for Model 7SHT.
Approximate weight 1.5 lbs.