Technical Datasheet Catalogue Page
1SNK 161 020 D0201 1SNK 161 020 S0201
ZS35-PE Screw Clamp Terminal Block
35 mm²
Ground
0 AWG
16 mm 0.630 in Spacing Features and Benefits
Reliable electrical and mechanical contact with the rail that exceeds the
requirements of IEC 60947-7-2 terminal block standard.
34 1.34"
59 2.32"
63.3 2.49"
3D CAD outline drawings available on "Control Product 3D" portal
Ordering Details Type Order Code EAN Code Pack(ing) Weight g (1 pce)
Green-Yellow ZS35-PE 1SNK 516 150 R0000 3472595161508 20 81.80
Declarations and Certificates Document Part Number
CE
UE Directive 1SND 225 094 C1003
CB
Third Party Certificate 1SND 161 027 A0200
RoHS
RoHS 1SND 230 491 F0203
Atex Declaration 1SND 225 085 C1003
1
General Information
The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
Protection IP 20 NEMA 1
Rail DIN3-TH35
Wire stripping length 17 mm 0.669 in
Screw clamp Screw rail contact
(Maximum value)
Operating tool
Flat screwdriver
6.5 mm 0.256 in 5.5 mm 0.217 in
Torque 2.65 Nm 23.5 lb.in 1.6 Nm 14.2 lb.in
± 0.15 Nm ± 1.33 lb.in ± 0.15 Nm ± 1.33 lb.in
Mechanical endurance
of disconnect system
Material Specifications
Insulating material Polyamide
IRC 600 V
Flammability UL94 V0
NF F 16 101 I2F2
Needle ame test IEC 60695-11-5 Compliant
Connecting capacity per clamp
1 Rigid conductor 6-35 mm² 10-0 AWG
1 Flexible conductor without ferrule 6-35 mm² 10-0 AWG
1 Flexible conductor with ferrule
Ferrule maximum outer diameter 14 mm 0.551 in
Multi Connecting capacity per clamp
2 Rigid conductors
2 Flexible conductors without ferrule
2 Flexible conductors with twin ferrule
Don't mix solid and flexible conductors in the same clamp
Don't mix solid or flexible conductors of different sizes in the same clamp
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Cross section
Rated cross section 35 mm² 0 AWG
Maximum Cross section Manufacturer data 35 mm² Manufacturer data 0 AWG
Gauge A9 / 10 mm / 0.394 in / IEC 60947-7-1
Electrical characteristics
Current
Rated current IEC 60947-7-1
Field and factory wiring Cat.2 UL 1059
Factory wiring Cat.1 UL 1059
CSA-C-22.2 n° 158
Rated short-time withstand current 1 s (Icw) 4200 A
Short-time withstand current 0.5 s Manufacturer data
5 s Manufacturer data
10 s Manufacturer data
30 s Manufacturer data
1 mn Manufacturer data
Rated short circuit withstand CSA-C-22.2 n° 158
Max. current (45° temperature increase) / Max. cross section (mm²) Manufacturer data 35 mm²
Maximum short circuit current (1s) Manufacturer data 4200 A
2
Short Circuit Current Rating (SCCR) SA UL 1059 supplement SCCR UL 1059
With the following congurations:
Maximum voltage
Suitable conductor wire range
Fuse rating
Fuse designation
Fuse manufacturer name
Fuse type
Short circuit current
Voltage
Rated voltage IEC 60947-1
Rated voltage UL 1059
Use Group UL 1059 C
Rated voltage CSA-C-22.2 n° 158
Rated voltage Ex e IEC/EN 60079-11
Rated impulse withstand voltage 8000 V
Dielectric test voltage 2200 V
Pollution degree IEC 60947-1 3
Overvoltage category IEC 60947-1 III
Dissipated power
Maximum dissipated power at rated current IEC
Rated power dissipation at an ambient temperature of 23 °C - IEC 60947-7-3
Overload and short-circuit protection
Separate arrangement
1 fuse and 4 feed-through blocks
Exclusive short-circuit protection
Separate arrangement
Overload and short-circuit protection
Compound arrangement
5 fuse blocks
Exclusive short-circuit protection
Compound arrangement
Temperature range
Ambient temperature min/max Storage -55 +110 °C -67 +230 F
Installing -5 +40 °C -23 +104 F
Service IEC 60068-2-1 -55 +110 °C -67 +230 F
EN 60079-7 -55 +85 °C
Current Derating curve for continuous service temperature
3
Environmental Characteristics
Additional climatic tests
Dry heat IEC 60068-2-2 Compliant
Conditions Temperature +100 °C
Duration of test 96 h
Cyclic damp heat IEC 60068-2-30 Compliant
Conditions Temperature +55 °C
Number of cycles 2
Cold IEC 60068-2-1 Compliant
Conditions Temperature -40 °C
Duration of test 96 h
Z/ABDM climatic sequence IEC 60068-2-61 Compliant
Conditions Dry heat Duration of test / Temperature 16 h +85 °C
Cyclic damp heat Number of cycles / Temperature 1 +55 °C
Cold Duration of test / Temperature 2 h -25 °C
Corrosion
Salt mist IEC 60068-2-11 Compliant
Conditions Duration of test 96 h
Concentration 5 %
SO2 ISO 6988 Compliant
Conditions Duration of test 48 h
Concentration 0.2 dm³
Sulfur dioxide IEC 60068-2-42
Conditions Duration of test
Hydrogen sulfur IEC 60068-2-43
Conditions Duration of test
Flowing mixed gas corrosion test IEC 60068-2-60
Conditions Number of the test method
Duration of test
Vibrations
Vibrations IEC 60068-2-6 Compliant
Conditions Frequency range 10-55 Hz
Number of cycles 10
Amplitude
Acceleration 10 m/s²
Ramdom vibrations and climatic sequence IEC 60068-2-64
Conditions Duration of test
Frequency range
Acceleration
Climatic cycles
Step 1 -> Temperature / Duration of test
Step 2 -> Temperature / Duration of test
Temperature variation per minute
4
ZS35-PE Terminal Block Accessories Compatibility
Description Type Order Code
Pack
(ing)
Weight Technical Datasheet
pieces g(1 pce) PDF
1
End Stops
BAZH1 1SNK 900 102 R0000 20 23.90 1SNK 160 026 D0201
2
Circuit Separators
CS-R1 1SNK 900 103 R0000 20 5.20 1SNK 160 018 D0201
3
Protecting Covers
CO 1SNK 900 604 R0000 1 300.00 1SNK 160 020 D0201
4
Protecting Cover Kits
KCO 1SNK 900 624 R0000 1 47,8 1SNK 160 028 D0201
5
Terminal Block Markers
MC812 1SNK 160 000 R0000 22 0.09 1SNK 160 009 D0201
UMH 1SNK 900 611 R0000 10 0.20 1SNK 160 001 D0201
PROCAP8 1SNK 900 613 R0000 20 1.00 1SNK 160 013 D0201
SAT8 1SNK 900 616 R0000 5 6.00 1SNK 160 013 D0201
5