General Information
The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
Protection IP 20 NEMA 1
Rail DIN3-TH35
Wire stripping length 17 mm 0.669 in
Screw clamp Screw rail contact
(Maximum value)
Operating tool
Flat screwdriver
6.5 mm 0.256 in 5.5 mm 0.217 in
Torque 2.65 Nm 23.5 lb.in 1.6 Nm 14.2 lb.in
± 0.15 Nm ± 1.33 lb.in ± 0.15 Nm ± 1.33 lb.in
Mechanical endurance
of disconnect system
Material Specifications
Insulating material Polyamide
IRC 600 V
Flammability UL94 V0
NF F 16 101 I2F2
Needle ame test IEC 60695-11-5 Compliant
Connecting capacity per clamp
1 Rigid conductor 6-35 mm² 10-0 AWG
1 Flexible conductor without ferrule 6-35 mm² 10-0 AWG
1 Flexible conductor with ferrule
Ferrule maximum outer diameter 14 mm 0.551 in
Multi Connecting capacity per clamp
2 Rigid conductors
2 Flexible conductors without ferrule
2 Flexible conductors with twin ferrule
Don't mix solid and flexible conductors in the same clamp
Don't mix solid or flexible conductors of different sizes in the same clamp
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Cross section
Rated cross section 35 mm² 0 AWG
Maximum Cross section Manufacturer data 35 mm² Manufacturer data 0 AWG
Gauge A9 / 10 mm / 0.394 in / IEC 60947-7-1
Electrical characteristics
Current
Rated current IEC 60947-7-1
Field and factory wiring Cat.2 UL 1059
Factory wiring Cat.1 UL 1059
CSA-C-22.2 n° 158
Rated short-time withstand current 1 s (Icw) 4200 A
Short-time withstand current 0.5 s Manufacturer data
5 s Manufacturer data
10 s Manufacturer data
30 s Manufacturer data
1 mn Manufacturer data
Rated short circuit withstand CSA-C-22.2 n° 158
Max. current (45° temperature increase) / Max. cross section (mm²) Manufacturer data 35 mm²
Maximum short circuit current (1s) Manufacturer data 4200 A