https://www.phoenixcontact.com/us/products/2688349
09/03/2014Page1/5
I/O module-AXL F DO16/1 1H-2688349
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
AxiolineF digital output module, 16outputs, 24VDC, 500mA, 1-wire connection method (including bus base
module and connector connectors)
Product description
The module is designed for use within an Axioline˽F station.
It is used to output digital signals.
The outputs are protected against short circuit and overload. 
Product Features
16 digital outputs
24 V DC, 500 mA
Connection of actuators in single-wire technology
Minimum update time of < 100 μs
Device rating plate stored
Diagnostic and status indicators
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 180.0 GRM
Custom tariff number 85389091
Country of origin Germany
Technical data
Dimensions
Width 35 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH35-7.5 DIN rail is used (according to
EN60715).
https://www.phoenixcontact.com/us/products/2688349
09/03/2014Page2/5
I/O module-AXL F DO16/1 1H-2688349
Technical data
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Connection data
Designation AxiolineF connector
Connection method Push-in technology
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 1.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 16
Stripping length 8 mm
General
Weight 134 g
Note on weight specifications with connectors and bus base module
Mounting type DIN rail
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN61000‑4‑2/IEC61000‑4‑2 Criterion B; 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN61000‑4‑3/IEC61000‑4‑3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN61000‑4‑4/IEC61000‑4‑4 Criterion B, 2kV
Noise immunity test in accordance with EN 61000-6-2 Transient surge
voltage (surge) EN61000‑4‑5/IEC61000‑4‑5 Criterion B; DC supply lines:
±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN61000‑4‑6/IEC61000‑4‑6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3 Radio interference
properties EN 55022 Class B
https://www.phoenixcontact.com/us/products/2688349
09/03/2014Page3/5
I/O module-AXL F DO16/1 1H-2688349
Technical data
General
Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Diagnostics messages I/O supply failure configurable
Short-circuit / overload of the digital outputs Yes
Interfaces
Designation AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Axioline potentials
Communications power UBus 5 V DC (via bus base module)
Current consumption from UBus max. 120 mA
Supply of digital output modules UO24 V DC
Current consumption from UO8 A (external fuse)
Digital outputs
Output name Digital outputs
Connection method Push-in technology
1-wire
Number of outputs 16
Protective circuit Short-circuit protection, overload protection of the outputs Electronic
Output voltage 24 V
Nominal output voltage 24 V DC
Maximum output current per channel 500 mA
Maximum output current per module 8 A (external fuse)
Nominal load, inductive max. 12 VA (1.2 H; 48 Ω; with nominal voltage)
Nominal load, lamp max. 12 W (at nominal voltage)
Nominal load, ohmic max. 12 W (48 Ω; with nominal voltage)
Classifications
eCl@ss
eCl@ss 4.0 27240404
eCl@ss 4.1 27240404
eCl@ss 5.0 27242204
eCl@ss 5.1 27242604
eCl@ss 6.0 27242604
https://www.phoenixcontact.com/us/products/2688349
09/03/2014Page4/5
I/O module-AXL F DO16/1 1H-2688349
Classifications
eCl@ss
eCl@ss 7.0 27242604
eCl@ss 8.0 27242604
ETIM
ETIM 3.0 EC001599
ETIM 4.0 EC001599
ETIM 5.0 EC001599
UNSPSC
UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 39121311
UNSPSC 12.01 39121311
UNSPSC 13.2 39121311
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
https://www.phoenixcontact.com/us/products/2688349
09/03/2014Page5/5
I/O module-AXL F DO16/1 1H-2688349
Approvals
cULus Listed
Drawings
Connection diagram
OUT13 OUT16
OUT1 OUT4
00
10
20
30
01
11
21
31
02
12
22
32
03
13
23
33
Dimensioned drawing
35 54
122,4
126,1
Block diagram
D
UO
E1
m
C
2x
DO 1...16
U
24 V
O
UBus
Axio bus
Output circuit
32030200 33
33
03 320200
02
12
22
32
03
13
23
33
16x
Internal wiring of the terminal points
Diagram
0,1 0,2 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,1 2,2 2,3 2,40,3 0,4
0
0,05
0,1
0,15
0,2
0,25
0,3
0,35
0,4
0
12
3
45
1=0,5A
2=0,4A
3=0,3A
4=0,2A
5=0,1A
Inductance[H]
Energy consumption [J]
Onlywithexternalfreerunningcircuit
Maximum energy consumption of the outputs when switching off inductive
loads
The diagram shows the maximum amount of energy that may be fed back
into the corresponding output groups (outputs 1 to 4, 5 to 8, 9 to 12, 13
to 16) for each switch off procedure when switching off an inductive load
without external freewheeling circuit.
The current data refers to the ohmic DC voltage component of the inductive
load.
Note: Restrict freewheeling voltage to a maximum of -15V when using
an external freewheeling circuit. The external freewheeling circuit has no
function in the event of a higher negative voltage.
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com