Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12 2
Switching Power Supply
Type SPD 960W 3 phases
DIN rail mounting
Input data
Rated input voltage 400 - 500VAC
Voltage range
AC 340 - 575VAC
DC 480 - 820VDC
Rated input current
(Vi: 340VAC, Io nom) Typ. 2.4A
Inrush current
Vi nom, Io nom 24V/48V models 30 - 35A
Cold start 24L model 50 - 60A
Power dissipation
Vi: 400 VAC, Io nom 24V Model 98W
48V Model 55W
Frequency range 47- 63Hz
Leakage current
Input-Output 0.25mA
Input-FG 3.5mA
Controls and Protections
Overload 120-140%
Input fuse T5A/500VAC internal/phase
Output short circuit Hiccup mode
Power ready output
(only 24V model) On threshold ≥17.6 -19.4VDC
Elettrical isolation 500VDC
Contact rating at 60vdc 0.3A
Over voltage protection VDC
Min. Max.
24V Model 30 33
48V Model 60 68
Internal surge voltage protection
Varistor
(IEC 61000-4-5)
General data (@ nominal line, full load, 25°C )
Ambient temperature -40°C to 71°C
Derating (>61°C to +71°C) 3.5%/°C
Ambient humidity 20 ~ 90%RH
Storage -40°C to +85°C
Protection degree IP20
Cooling Free air convection
Pollution degree 2
MTBF (Bellcore issue 6 @ 40°C, GB)
24V Model 352000 Hours
24L Model 381000 Hours
48V Model 390000
Case material Metal
Dimensions LxWxD mm(inch) 126.2(4.97) x 275.8(10.86) x 118.8(4.68)
Weight 3400g
Norms and Standards
Vibration resistance meet IEC 60068-2-6
(Mounting by rail: 10-500Hz,
2G, along X, Y, Z each Axis,
60 min for each Axis)
Shock resistance meet IEC 60068-2-27
(15G, 11ms, 3 Axis, 6 faces,
3 times for each face)
UL / cUL UL508 listed, UL60950-1,
Recognized, ISA 12.12.01
(Class 1, Division 2,
Groups A, B, C and D)
TUV EN 60950-1, CB scheme
EN 61558-1,
EN 61558-2-17
(meet EN 60204)
CCC
GB4943, GB9254, GB17625.1
CE EN 61000-6-3, EN 55022
Class B, EN 61000-3-2,
EN 61000-3-3,
EN 61000-6-2,
EN 55024, EN 61000-4-2
Level 4, EN 61000-4-3
Level 3, EN 61000-4-4
Level 4, EN 61000-4-5 L-N
Level 3, L/N-FG Level 4,
EN 61000-4-6 Level 3,
EN 61000-4-8 Level 4,
EN 61000-4-11,
ENV 50204 Level 2,
EN 61204-3