Switches & Pilot Devices Signaling Lights Relays & Sockets Timers Contactors Terminal Blocks Circuit Breakers
661
800-262-IDEC (4332) • USA & Canada
ø30mm - TWTD Series
Switches & Pilot Devices
Specifications
Conforming to Standards EN60947-1, EN60947-5-1, VDE0660-200, UL508, CSA C22-2 No.14
Approvals
CSA: pushbuttons and selector switches: A600 pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbut-
tons with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
UL: pushbuttons and selector switches: A600 pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbuttons
with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
TÜV: pushbuttons and selector switches: A600=P600 (NO, NC)/Q600 (NO-EM, NC-LB) pilot lights and illuminated pushbuttons, direct supply
pilot lights and illuminated pushbuttons with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
Operating Temperature Operation: –25 to +50°C (without freezing)
Storage: –40 to +70°C (without freezing)
Vibration Resistance 10 to 55Hz, 98m/sec2 (10g) conforming to IEC6068-2-6
Shock Resistance 980m/sec2 (100g) conforming to IEC6068-2-7
Electric Shock Protection Class 0 conforming to IEC60536
Degree of Protection
IP65 (from front of the panel) (conforming to IEC60529)
IP54 (key switches)
Type 1, 2, 3, 3R, 3S, 4, 4X, 5, 12, 13 (conforming to NEMA ICS6-110)
Mechanical Life Momentary pushbuttons: 5,000,000 (900 operations per hour)
All other switches: 500,000
Pollution Degree
(conforming to IEC60947-1)
3 for switches not using a transformer
2 for switches using a transformer
Mechanical-Electrical Specifications
Rated Operational Characteristics
AC-15: A600 or Ue = 250V, le = 3A (NO, NC, NO-EM, NC-LB)
DC-13: P600 or Ue = 125V, le = 1.1A (NO, NC)
DC-13: Q600 or Ue = 125V, le = 0.9A (NO-EM, NC-LB)
Rated Insulation Voltage 600V
Rated Switching Overvoltage Less than 4kV, conforming to IEC60947-1
Rated Impulse Withstanding Voltage 4kV for contact circuit
2.5kV for lamp circuit
Rated Thermal Current 10 Amp
Minimum Switching Capacity 5 mA at 3V AC/DC
Contact Operation Slow break NC or NO, self-cleaning
Operating Force
Flush and extended pushbuttons—with 1NO or 1NC contact: 6.2±2N (momentary),
7.0±2N (maintained)
Additional contacts—1NO or 1NC: +3.2N (momentary), + 3.3N (maintained)
Terminal Referencing Conforming to CENELEC EN50005
Recommended Terminal Torque 0.8 N m (7.1 in lb.)
External Short-Circuit Protection 10A 250V fuse conforming to IEC60269-1
Applicable Wire Size Minimum 1 x 22 AWG, max. 2 x 14 AWG or 1 x 12 AWG
Contact Resistance Initial contact resistance of 50mΩ or less
Contact Gap 4mm (NO and NC)
2mm (NO-EM and NC-LB)
Lamp Ratings Incandescent: 1 W
LEDs: 6V: 17mA, 12V: 11mA, 24V: 11mA, / 120, 240V: 10mA
Maximum Inrush Current 40 A (40 msec)
Contact Material Silver
Contact Ratings
Contact Ratings by Utilization Category IEC 60947-5-1 AC-15 (A600)
DC-13 (P600)
Contact Ratings by Utilization Category
Operational Voltage 24V 48V 50V 110V 220V 440V
Operation Current
AC 50/60 Hz AC-12 Control of resistive loads & solid state loads 10A — 10A 10A 6A 2A
AC-15 Control of electromagnetic loads (> 72VA) 10A — 7A 5A 3A 1A
DC DC-12 Control of resistive loads & solid state loads 8A 5A — 2.2A 1.1A —
DC-13 Control of electromagnets 5A 2A — 1.1A 0.6A —