Specifications are subject to change without notice (01.12.99) 1
Plug Output Time range Supply:
24 VAC/DC & 115-230 VAC
Circular SPDT 0.1 s - 10 h S 103 156 924
Circular DPDT 0.1 s - 10 h S 103 166 924
Timers
Time ranges: 0.1 s to 10 h
4 selectable functions: - Delay on operate
- Interval timer
- Interval timer, delay on release
- Recycler
Easy time and function setting
Knob-adjustable time setting
Automatic and manual start functions
Repeatability: 0.2%
Output: 5 A SPDT or DPDT relay
Plug-in module, S-housing
LED-indication for relay and power supply ON
24 VAC/DC and 115 to 230 VAC power supply
Cadmium-free contacts
Timer in accordance with IEC 61812-1
Product Description
Multi-function, multi-voltage
timer with 6 selectable time
ranges from 0.1 s up to 10 h
for standard 11-pin circular
sockets. Used as a general
timer in industrial applica-
tions.
Ordering Key
Housing
Type/function
Output
Power supply
Type Selection
Time Specifications
Time ranges
Selectable by DIP-switch 0.1 - 1 s
1 - 10 s
0.1 - 1 m
1 - 10 m
0.1 - 1 h
1 - 10 h
Setting accuracy 5%
Repeatability 0.2%
Time variation
Within rated power supply 0.05%/V
and ambient temperature 0.2%/°C
Reset
Manual reset of time and/or relay Interconnect pins 5 & 2
Pulse duration 100 ms
Power supply interruption 200 ms
Output Specifications
Output S 103 156 924 SPDT relay
S 103 166 924 DPDT relay
Rated insulation voltage
250 VAC (rms) (cont./elect.)
Contact ratings (AgNi) µ (micro gap)
(IEC 60947-5-1/IEC 60337)
Resistive loads
AC 1
5 A/250 VAC
DC 1
5 A/24 VDC
Small inductive loads
AC 15
5 A/250 VAC
DC 13
2 A/24 VDC
Mechanical life 30 x 106operations
Electrical life AC 1 105operations
(at max. load)
Operating frequency 7200 operations/h
Insulation voltage
Rated insulation voltage 2.0 kVAC (rms) (cont./elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
Multi-function
Type S 103
S 103 156 924
Supply Specifications
Power supply AC connection
Overvoltage cat. III (IEC 60664)
Rated operational voltage
Through pins 2 & 10 115-230 VAC, -15 to +15%
50/60 Hz, -5/+5 Hz
or pins 2 & 10 24 VAC, -15 to +15%
(interconnect pins 6 & 10)
50/60 Hz, -5/+5 Hz
Voltage interruption 40 ms
Rated insulation voltage None
Rated impulse withstand volt. 4 kV (1.2/50 µs) (pin 2 & 10)
Power supply DC connection
Overvoltage cat. III (IEC 60664)
Rated operational voltage
Through pins 2 & 10 924 24 VDC, -15 to +15%
(interconnect pins 6 & 10) (pin 2 positive)
Voltage interruption 40 ms
Rated insulation voltage None
Rated impulse withstand volt. 1 kV (1.2/50 µs) (pin 2 & 6)
Rated operational current
AC supply 75 mA @ 230 VAC
40 mA @ 115 VAC
55 mA @ 24 VAC
DC supply 35 mA @ 24 VDC
2Specifications are subject to change without notice (01.12.99)
S 103
Mode of Operation
Function 1
Delay on operate
The time period starts when
pins 5 and 2 are interconnect-
ed.
At the end of the set delay
the relay will operate and will
not release until pins 5 and 2
are interconnected again, or
power supply is interrupted.
The time period will autostart
when pins 5 and 2 are con-
stant connected.
Function 2
Interval timer
The relay operates and the
time period starts when pins 5
and 2 are interconnected. At
the end of the set delay the
relay releases. The relay will
operate again when pins 5
and 2 are interconnected. For
autostart connect pins 5 and
2 before power supply is ap-
plied. A recovery period of 200
ms should be allowed before
reapplying power supply.
Function 3
Interval timer
Delay on release
Power supply must be con-
stantly applied. When inter-
connecting pins 5 and 2 the
relay will operate. When pins
5 and 2 are disconnected, the
time period starts, and when
the set time period has expir-
ed, the relay releases. If pins 5
and 2 are connected again
before the time period has
expired, the time is reset and
the time period restarts when
the interconnection between
pins 5 and 2 is interrupted.
Function 4
Recycler
ON-time period first
When power supply is ap-
plied the relay operates and
the time period starts. At the
end of the first set time pe-
riod, the relay releases for the
set time period. This
sequence continues with
equal ON- and OFF-time peri-
ods until power supply is
interrupted.
Recycler
OFF-time period first
When pins 5 and 2 are inter-
connected the recycler func-
A1
N
115-230V 24V (-)
16 18
3
1
6
5
4
2
15A2 A3
115-230V
L
24V (+)
S
Y1
10
@ 24V
Wiring Diagrams
Operation Diagram
Function 2. Relay ON
Function 3. Relay ON
Function 1. Relay ON
Reset (interconnect 5 & 2)
Power supply
Function 4. Relay ON
Accessories
SocketS 411
Hold down springHF
Mounting rack SM 13
Socket cover BB 4
General Specifications
Power ON delay 200 ms
Power OFF delay 200 ms
Indication for
Power supply ON LED, green
(flashing during timing)
Output ON LED, yellow
Environment
Degree of protection IP 20
Pollution degree 2 (IEC 60664)
Operating temperature -20° to +50°C (-4° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Weight 100 g
Approvals UL, CSA
CE-marking Yes
EMC Electromagnetic
Compatibility
Immunity Acc. to EN 50082-2
Emission Acc. to EN 50081-1
Timer specifications Acc. to IEC 61812-1
15
26 28
9
11
8
25
A1 16 18
3
1
5
42
115-230V
L
24V (+)
S
Y1
N
115-230V 24V (-)
6
A2 A3
10
@ 24V
Functions selectable by DIP-switch
A
B
A
B
A
B
A
B
Function and Time Setting
DIP-switch
selector
x 1
sec.
min.
hrs.
x 0.1
A
B
Shown example:
min. x 0.1, function 2
ON OFF
S 103 156 924 S 103 166 924