Repeat accuracy +/- 0.5 % IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale 25 °C IEC 61812-1
Insulation resistance 100 MOhm 500V DC IEC 60664-1
Recovery time 100ms on de-energisation
Immunity to microbreaks 10ms
Power consumption in VA 3VA 240 V AC
Power consumption in W 2W 240 V DC
Switching capacity in VA 1250VA
Minimum switching current 10mA 5 V DC
Maximum switching current 5A
Maximum switching voltage 250V AC
Electrical durability 100000cycles, 2A 24 V, DC-1
100000cycles, 5A 250 V, AC-1
Mechanical durability 10000000cycles
Rated impulse withstand voltage 5kV 1.2…50µs IEC 60664-1
Power on delay 200ms
Creepage distance 4 kV/3 IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data MTTFd = 194 years
B10d = 180000
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED Green LED backlight steady)dial pointer indication
Yellow LED steady)output relay energised
Yellow LED steady)power ON
Width 0.89in (22.5mm)
Net Weight 0.22lb(US) (0.1kg)
Environment
Dielectric strength 2.5kV 1 mA/1 minute 50 Hz between relay output and power supply basic insulation IEC 61812-1
Standards IEC 61812-1
UL 508
Directives 2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
Product certifications CCC
CSA
GL
China RoHS
RCM
CE
EAC
UL
Ambient air temperature for operation -4…140°F (-20…60°C)
Ambient air temperature for storage -40…158°F (-40…70°C)
IP degree of protection Housing IP40 IEC 60529
IP50 front face: conforming to IEC 60529
Terminals IP20 IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Vibration resistance 20 m/s² 10…150Hz)IEC 60068-2-6
Shock resistance 15 gn not operating 11ms IEC 60068-2-27
5 gn in operation 11ms IEC 60068-2-27
Relative humidity 95% 77…131°F (25…55°C)
Electromagnetic compatibility Fast transients immunity test 1 kV capacitive connecting clip)level 3 IEC 61000-4-4
Surge immunity test 1 kV differential mode)level 3 IEC 61000-4-5
Surge immunity test 2 kV common mode)level 3 IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
2