straps
Compact Operating Instructions SINAMICS G120
Power Module PM240-2, FSA, FSB, FSC
Mains, Motor and Brake terminals
The Power Modules are fitted with detachable terminals. It can
be removed from the Power Module by pressing the release
catch. The connectors are not interchangeable.
Tightening torques:
FSA: 0.5 Nm ( 4 lbf.in)
FSB: 0.6 Nm ( 5 lbf.in)
FSC: 1.3 Nm (12 lbf.in)
① Mains connector
② Motor connector
③ DC Link connector
④ Release catch
Cable cross sections
FSA: 1.5 … 2.5 mm2 16 … 14 AWG
FSB: 1.5 … 6 mm2 16 … 10 AWG
FSA: 6 … 16 mm2 10 … 6 AWG
150 % for 3 s
110 % for 57 s
200 % for 3 s
150 % for 57 s
100 % for 240 s 100 % for 240 s
Permissible overload for operation
according „Low Overload“ (LO)
Overloads
Permissible overload for operation
according „High Overload“ (HO)
HO base load: 100 % HO power
100 % HO current
LO base load: 100 % LO power
100 % LO current
%
300240
1801200
100
200
60 t[s]
%
300240
1801200
100
150
60 t[s]
For United States / Canadian installations (UL/cUL): In order that the system is UL/cUL-compliant, use
UL/cUL-certified J-type fuses. Use 75° C copper wire only.
Additional requirements for Canadian compliance:
400 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 480 V
(phase to ground), 480 V (phase to phase), suitable for overvoltage category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
200 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 240 V
(phase to ground), 240 V (phase to phase), suitable for overvoltage category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the
power cables.
Siemens AG,
Frauenauracher Str. 80,
DE-91056 Erlangen
Issue 09/2016
Screened cables, filtered units (class A)
Screened cables, unfiltered units,
EMI Standard not fullfilled
Unscreened cables, filtered or unfiltered units
EMI Standard not fullfilled
3 AC 380 V … 480 V ± 10 % up to 2000 m installation
altitude. 1 AC / 3 AC 200 V ... 240 V ± 10 % up to 2000 m installation altitude.
3 AC 0 V … input voltage * 0.93
0 Hz … 550 Hz, depending on the control mode
without line reactor; 0.85 with line reactor
Less than rated input current
Pulse frequency (factory setting)
4 kHz. Can be increased in 2 kHz steps up to 16 kHz. Increasing the pulse frequencies leads to an output current reduction.
ctromagnetic compatibility
The devices are suitable for second environment category C2 in accordance with IEC61800
conditions are fulfilled: The motor cable is a shielded cable with low capacitance and is not longer than 50 m. The pulse frequency does
not exceed 4 kHz, the current does not exceed the LO input value. For details, refer to the Hardware Installation Manual.
devices are suitable for second environment category C
Compound braking, Dynamic braking with integrated chopper plus external Braking resistor
Push through units: IP54 / UL type 12 when mounted on a flat surface of an enclosure
Motor overload protection
This equipment is capable of providing internal motor overload protection according to UL508C. The protection level is 115
400 % full load current of the equipment. This is adjusted via parameter P640 and assumes the equipment has had basic motor
commissioning for the motor used as described in the documentation.
0 °C … 40 °C (32 °F … 104 °F) without
derating / up to 60 °C (140 °F) with
derating / up to 60 °C (140 °F) with
Installation altitude above sea level
Up to 1000 m (3300 ft) without derating
/ Up to 4000 m (13000 ft) with derating
Suitable for environmental class 3C2 according to
3 against damaging chemical substances
For open type equipment according
pollution degree level 2. Protection against conductive pollution is required e.g. using an IP54
cabinet.
For enclosed type/Push Through equipment according pollution degree level 3.
term storage in the transport packaging according to Class
1 : Transport in the transport packaging according to
Class 2M3 of IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
term storage in the transport packaging according to Class 1M2 to
1 : Transport in the transport packaging according to
Class 2M3 to IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
200 V Units: Uk 2 %, for lower values, a line reactor must be used.
400 V Units: Uk 1 %, for lower values, a line reactor must be used.
Short Circuit Current Rating
Suitable for use on a circuit capable of delivering not more than 65 kA rms symetrical amperes; 480 Vac maximum when protecte
Class J or R/C (JFHR2) semico
nductor fuses only as stated
Short Circuit Current Rating
Suitable for use on a circuit capabl
e of delivering not more than 40
kA rms symetrical amperes;
0 Vac maximum when protected by
Class J or R/C (JFHR2) semiconductor fuses only
1) according to UL, operation with temperatures > 50 °C (122 °F) is not permitted at all
(LO)
input
Size
current
current
PM240-2, Built in units, 3 AC 380 V … 480 V
PM240-2, Push through units, 3 AC 380 V … 480 V
PM240-2, Built in units, 1 AC/3 AC 200 V … 240 V
PM240-2, Built in units, 3 AC 200 V … 240 V
PM240-2, Push through units, 1 AC/3 AC 200 V … 240 V
PM240-2, Push through units, 3 AC 200 V … 240 V
*) _: A = filtered unit, U = unfiltered unit