FLT-PLUS CTRL-1.5/I Order No.: 2818931
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2818931
PHOENIX CONTACT Deutschland GmbH Page 3 / 6
http://www.phoenixcontact.de Feb 4, 2011
Nominal discharge surge current In (8/20) µs 50 kA
Nominal discharge surge current In (8/20) µs (L-N) 50 kA
Nominal discharge surge current In (8/20) µs (L-
PEN)
50 kA
Lightning test current (10/350) µs, charge 25 As
Lightning test current (10/350) µs, specific energy 625.00 kJ/Ω
Lightning test current (10/350) µs, peak value limp 50 kA
100% lightning impulse sparkover voltage
(1.2/50)µs
≤ 1.5 kV
Protection level Up≤ 1.5 kV
Protection level UP (L-N) ≤ 1.5 kV
Protection level UP (L-PEN) ≤ 1.5 kV
Response time ≤ 100 ns
Response time (L-N) ≤ 100 ns
≤ 100 ns
Max. required backup fuse with branch wiring 250 A (gL)
Short-circuit resistance IP with max. backup fuse
(effective)
50 kA (At 400 V AC)
Short-circuit current self-quenching 50 kA (400 V)
Follow current quenching capacity If (L-N) 50 kA (At 400 V AC)
Follow current quenching capacity If (L-PE) 50 kA (At 400 V AC)
Connection, protective circuit
Type of connection Screw connection
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M6
Tightening torque 8 Nm
Stripping length 19 mm
Conductor cross section stranded min. 16 mm²
Conductor cross section stranded max. 35 mm²
Conductor cross section solid min. 10 mm²
Conductor cross section solid max. 50 mm²
Conductor cross section AWG/kcmil min. 6
Conductor cross section AWG/kcmil max 1