SITOP power supply
SITOP PSU100S
Operating Instructions
SITOP PSU100S 24 V/2.5 A
6EP1332
-2BA20
SITOP PSU100S 24 V/5 A
6EP1333
-2BA20
SITOP PSU100S 24 V/10 A
6EP1334
-2BA20
SITOP PSU100S 24 V/20 A
6
EP1336-2BA10
SITOP
PSU100S 12 V/7 A
6EP1322
-2BA00
SITOP PSU100S 12 V/14 A
6EP1323
-2BA00
07.2014
C98130
-A7589-A1-5-7629
Overview
Safety instructions
1
Description, device design,
dimension drawing
2
Mounting/removal
3
Mounting position, mounting
clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Ambient conditions
8
Applications
9
Environment
10
Service & Support
11
Siemens AG
Industry Sector
Postfach
48 48
90026 NÜRNBERG
GERMANY
C98130-A7589-A1-5-7629
08/2014 Subject to change
Copyright © Siemens AG 2014.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 3
Overview
Description
The 1-phase SITOP PSU100S from the SITOP smart product line is a powerful, regulated
standard power supply for automated machines and systems. In addition to a high efficiency,
these low-profile power supply units have an outstanding overload behavior.
The key benefits of the product include:
Wide-range input, which allows them to be connected to almost any 1-phase line supply
around the world
Output voltage can be adjusted in the range 22.2 (24)...28 V or 11.5…15.5 V
Brief overload capability of 150% for 5 s/min (extra power)
Continuous overload capability of 120% up to an ambient temperature of +45° C
Integrated signaling contact for "24 V OK" or "12 V OK"
Ambient temperature -25 (0)...+70 °C
To increase the system availability, these reliable power supplies can be expanded using
SITOP supplementary modules (redundancy module, selectivity module, buffer module),
as well as SITOP DC-UPS modules.
Overview
SITOP PSU100S
4 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Ordering data
The following device options are available:
Regulated SITOP PSU100S power supply
Type
Order number
1-phase 120/230 V AC input,
24 V/2.5 A DC output
6EP1332-2BA20
1-phase 120/230 V AC input,
24 V/5 A DC output
6EP1333-2BA20
1-phase 120/230 V AC input,
24 V/10 A DC output
6EP1334-2BA20
1-phase 120/230 V AC input,
24 V/20 A DC output
6EP1336-2BA10
1-phase 120/230 V AC input,
12 V/7 A DC output
6EP1322-2BA00
1-phase 120/230 V AC input,
12 V/14 A DC output
6EP1323-2BA00
Accessories
Item
Order number
Device identification labels 10 mm × 7 mm, pastel turquoise
3RT1900-1SB10
Device identification labels 20 mm × 7 mm, pastel turquoise
3RT1900-1SB20
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 5
Table of contents
Overview................................................................................................................................................. 3
1 Safety instructions ................................................................................................................................... 7
2 Description, device design, dimension drawing........................................................................................ 9
2.1 Device description .......................................................................................................................... 9
2.2 Connections and terminal designation ......................................................................................... 10
2.3 Potentiometer ............................................................................................................................... 11
2.4 Status displays and signaling ....................................................................................................... 12
2.5 Block diagram .............................................................................................................................. 13
2.6 Dimensions and weight ................................................................................................................ 14
3 Mounting/removal ................................................................................................................................. 17
4 Mounting position, mounting clearances ................................................................................................ 19
4.1 Standard mounting position ......................................................................................................... 19
4.2 Other mounting positions ............................................................................................................. 22
4.2.1 6EP1332-2BA20 .......................................................................................................................... 22
4.2.2 6EP1333-2BA20 .......................................................................................................................... 24
4.2.3 6EP1334-2BA20 .......................................................................................................................... 26
4.2.4 6EP1336-2BA10 .......................................................................................................................... 28
4.2.5 6EP1322-2BA00 .......................................................................................................................... 30
4.2.6 6EP1323-2BA00 .......................................................................................................................... 32
5 Installation ............................................................................................................................................ 35
5.1 Line-side connection .................................................................................................................... 35
5.2 Output-side connection ................................................................................................................ 37
6 Technical data ...................................................................................................................................... 39
6.1 Input ............................................................................................................................................. 39
6.2 Output .......................................................................................................................................... 41
6.3 Efficiency ...................................................................................................................................... 47
6.4 Closed-loop control ...................................................................................................................... 50
6.5 Protection and monitoring ............................................................................................................ 51
6.6 MTBF ........................................................................................................................................... 51
6.7 Mechanical system ...................................................................................................................... 52
6.8 Accessories .................................................................................................................................. 53
6.9 Dimension drawing ...................................................................................................................... 53
Table of contents
SITOP PSU100S
6 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
7 Safety, approvals, EMC ........................................................................................................................ 55
7.1 Safety .......................................................................................................................................... 55
7.2 Test voltage ................................................................................................................................. 56
7.3 Approvals .................................................................................................................................... 57
7.4 EMC ............................................................................................................................................ 58
8 Ambient conditions ................................................................................................................................ 59
9 Applications .......................................................................................................................................... 61
9.1 Parallel connection to increase power rating .............................................................................. 61
9.2 Parallel connection for redundancy ............................................................................................. 63
9.3 Series connection for increased voltage ..................................................................................... 64
9.4 Overload protection in the 24 V output circuit ............................................................................. 65
9.5 Protection against short-time voltage dips .................................................................................. 66
9.6 Protecting against longer power failures ..................................................................................... 67
10 Environment ......................................................................................................................................... 69
11 Service & Support ................................................................................................................................. 71
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 7
Safety instructions
1
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
Safety instructions
SITOP PSU100S
8 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 9
Description, device design, dimension drawing
2
2.1
Device description
SITOP PSU100S is a primary-clocked power supply for connection to a 1-phase AC line
supply. An electronically regulated DC voltage that can be set via a potentiometer is
available at the output of the device. The output of the device is isolated, no-load proof and
short-circuit proof. The LED display indicates the operating status. The operating state of the
device can be processed via the signaling contact.
Line input
DC output
Signaling contacts
Potentiometer 22.2…28 / 24...28 V / 11.5…15.5 V
Indicator light (output voltage OK)
DIN rail slider
Natural convection
Clearance above/below
Figure 2-1 Design
Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP PSU100S
10 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
2.2
Connections and terminal designation
The line input terminals can be used to establish the connection to supply voltage. The
output terminals are used to connect to the loads to be supplied (see also Section
Installation (Page 35)).
The operating state of the device can be processed via the signaling contact (function
and contact rating, see Chapter Status displays and signaling (Page 12)).
Connections and terminal designations
Line input L1, N, PE One screw terminal each
Output + 2 screw terminals
Output 2 screw terminals
Signaling contact 13, 14 One screw terminal each
*1)
Do not subject the end stop to higher loads
Figure 2-2 Terminal data for 6EP1332-2BA20, 6EP1333-2BA20, 6EP1334-2BA20, 6EP1322-
2BA00, 6EP1323-2BA00
*1)
Do not subject the end stop to higher loads
Figure 2-3 Terminal data for 6EP1336-2BA10
Description, device design, dimension drawing
2.3 Potentiometer
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 11
2.3
Potentiometer
The potentiometer on the front of the device is used to adjust the output voltage. The
output voltage is set to the rated value at the factory and can be set within certain limits; for
example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-4 Potentiometer
Type
Factory setting
Adjustment range
6EP1322-2BA00
6EP1323-2BA00
12 V 11.5...15.5 V
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
24 V 22.2...28 V
6EP1336-2BA10 24 V 24...28 V
NOTICE
Thermal overload possible
When adjusting the output voltage to greater than the rated voltage, the output current must
be derated by 4 %/V, or the permissible ambient temperature must be taken into account
with 3° C/V.
Note
It is only permissible t
o use an insulated screwdriver when actuating the potentiometer.
For notes on actuating the potentiometer (screwdriver, torque), refer to Figure 2-2 Terminal
data for 6EP1332-2BA20, 6EP1333-2BA20, 6EP1334-2BA20, 6EP1322-2BA00, 6EP1323-
2BA00 (Page 10) and Figure 2-3 Terminal data for 6EP1336-2BA10 (Page 10).
Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU100S
12 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
2.4
Status displays and signaling
6EP1322-2BA00, 6EP1323-2BA00, 6EP1332-2BA20
6EP1333-2BA20, 6EP1334-2BA20, 6EP1336-2BA10
Status display
LED green for 24 V O.K. or 12 V O.K.
Signaling contact Relay contact (NO contact, contact rating 30 V AC / 0.5 A, 60 V DC / 0.3 A, 30 V DC / 1 A)
for 24 V O.K. or 12 V O.K.
Figure 2-5 Status displays and signaling
Signaling
6EP1322-2BA00
6EP1323-2BA00
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
LED lights up green
Signaling contact ,
contacts 13-14 closed
Normal operation,
Output voltage
>10 V ±0.5 V
Normal operation,
Output voltage
>20 V ±0.5 V
Normal operation,
Output voltage
>20 V ±0.5 V
LED dark
Signaling contact ,
contacts 13-14 open
(inactive position)
Overload operation or power
supply voltage missing
Overload operation or power
supply voltage missing
Overload / hiccup operation,
power supply missing or the
device has tripped due to
overtemperature (reset
possible with power OFF for
approx. 30 min)
Description, device design, dimension drawing
2.5 Block diagram
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 13
2.5
Block diagram
Figure 2-6 Block diagram
Description, device design, dimension drawing
2.6 Dimensions and weight
SITOP PSU100S
14 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
2.6
Dimensions and weight
Figure 2-7 Dimension drawing 6EP1332-2BA20
Figure 2-8 Dimension drawing 6EP1333-2BA20, 6EP1322-2BA00
Description, device design, dimension drawing
2.6 Dimensions and weight
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 15
Figure 2-9 Dimension drawing 6EP1334-2BA20, 6EP1323-2BA00
Figure 2-10 Dimension drawing 6EP1336-2BA10
6EP1332-2BA20
6EP1333-2BA20
6EP1322-2BA00
6EP1334-2BA20
6EP1323-2BA00
6EP1336-2BA10
Dimensions
(W × H × D) in mm
32.5 × 125 × 120 50 × 125 × 120 70 × 125 × 120 115 × 145 × 150
Weight
Approx. 0.3 kg
Approx. 0.4 kg
Approx. 0.7 kg
Approx. 2.4 kg
Description, device design, dimension drawing
2.6 Dimensions and weight
SITOP PSU100S
16 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 17
Mounting/removal
3
WARNING
Installing the device in a housing or a control cabinet
SITOP PSU100S power supplies are built-in units. They must be installed in a housing or
control cabinet where only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails according to
EN 60715.
Mounting
To mount the device, position it with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place. If this is too difficult, press slider
at the same time, as described under "Removal".
Removal
To remove, pull up the slider using a screwdriver and disengage the device at the bottom
edge of the standard mounting rail (see Removal diagram (Page 17)). Then you can remove
the device from the upper edge of the standard mounting rail.
Figure 3-1 Removal
WARNING
Use in hazardous zones
If the device is to be used in a hazardous zone (Ex II 3G Ex nA nC IIC T4 Gc) it must be
installed in a distributor box with degree of protection IP54 or higher.
Mounting/removal
SITOP PSU100S
18 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 19
Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is designed for installation on standard EN 60715 35×7.5/15 mounting rails. The
device must be mounted vertically to ensure proper cooling, and with the input terminals and
output terminals at the bottom.
A clearance of at least 50 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.
Output current as a function of the ambient temperature and mounting height
Figure 4-1 6EP1332-2BA20: Output current in the standard mounting position
Figure 4-2 6EP1333-2BA20: Output current in the standard mounting position
Mounting position, mounting clearances
4.1 Standard mounting position
SITOP PSU100S
20 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Figure 4-3 6EP1334-2BA20: Output current in the standard mounting position
Figure 4-4 6EP1336-2BA10: Output current in the standard mounting position
Figure 4-5 6EP1322-2BA00: Output current in the standard mounting position
Mounting position, mounting clearances
4.1 Standard mounting position
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 21
Figure 4-6 6EP1323-2BA00: Output current in the standard mounting position
Figure 4-7 Mounting height derating
Details see chapter Ambient conditions (Page 59)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
22 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
4.2
Other mounting positions
For mounting positions that deviate from the standard mounting position, derating factors
(reduction of the output power or the permissible ambient temperature) must be observed in
accordance with the following diagrams.
Note
In the case of mounting positions
that deviate from the standard mounting position, reduced
mechanical resistance of the devices against vibration and shock must be expected.
Particularly when installing on a vertically fastened standard mounting rail, additional
measures may be required,
e.g. to prevent the device from slipping on the standard
mounting rail.
4.2.1
6EP1332-2BA20
Figure 4-8 Mounting position (1)
Figure 4-9 Mounting position (2)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 23
Figure 4-10 Mounting position (3)
Figure 4-11 Mounting position (4)
Figure 4-12 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
24 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
4.2.2
6EP1333-2BA20
Figure 4-13 Mounting position (1)
Figure 4-14 Mounting position (2)
Figure 4-15 Mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 25
Figure 4-16 Mounting position (4)
Figure 4-17 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
26 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
4.2.3
6EP1334-2BA20
Figure 4-18 Mounting position (1)
Figure 4-19 Mounting position (2)
Figure 4-20 Mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 27
Figure 4-21 Mounting position (4)
Figure 4-22 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
28 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
4.2.4
6EP1336-2BA10
Figure 4-23 Mounting position (1)
Figure 4-24 Mounting position (2)
Figure 4-25 Mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 29
Figure 4-26 Mounting position (4)
Figure 4-27 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
30 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
4.2.5
6EP1322-2BA00
Figure 4-28 Mounting position (1)
Figure 4-29 Mounting position (2)
Figure 4-30 Mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 31
Figure 4-31 Mounting position (4)
Figure 4-32 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
32 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
4.2.6
6EP1323-2BA00
Figure 4-33 Mounting position (1)
Figure 4-34 Mounting position (2)
Figure 4-35 Mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 33
Figure 4-36 Mounting position (4)
Figure 4-37 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100S
34 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 35
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
The SITOP PSU100S power supply is designed for connection to a 1-phase AC line supply
(TN or TT system according to VDE 0100 T 300 / IEC 364-3) with a rated voltage of
120/230 V AC, 50/60 Hz.
Figure 5-1 Line connection (examples 6EP1334-2BA20 and 6EP1336-2BA10)
The line supply is connected using terminals L1, N and PE (see Figure 5-1 Line connection
(examples 6EP1334-2BA20 and 6EP1336-2BA10) (Page 35)), and must be implemented
according to IEC 60364 and EN 50178 . A protective device (miniature circuit-breaker or
circuit-breaker) and a disconnection unit for the power supply must be provided. A ground-
fault circuit interrupter is not permissible against indirect contact as the only protective
measure. This is true for the complete line supply protected by the ground-fault circuit
interrupter.
Installation
5.1 Line-side connection
SITOP PSU100S
36 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Protection
SITOP PSU100S
Recommended line-side protection
6EP1332-2BA20 Miniature circuit breaker (IEC 898) characteristic C, 3 A
6EP1333-2BA20
Miniature circuit breaker (IEC 898) characteristic C, 6 A
6EP1334-2BA20
Miniature circuit breaker (IEC 898) characteristic C, 10 A
6EP1336-2BA10 Miniature circuit breaker (IEC 898) characteristic C, 10 A
or
circuit breaker 3RV2411-1JA10 (120 V)
or
3RV2411-1FA10 (230 V)
6EP1322-2BA00
Miniature circuit breaker (IEC 898) characteristic C, 6 A
6EP1323-2BA00
Miniature circuit breaker (IEC 898) characteristic C, 10 A
The protective conductor of the line supply must be connected at the PE terminal.
Other country-specific regulations may have to be observed when installing the device.
Installation
5.2 Output-side connection
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 37
5.2
Output-side connection
At its output, the SITOP PSU100S power supply provides an isolated (= non-grounded)
SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load,
overload, and short-circuit proof. If an overload occurs, the electronic current limitation limits
the output current to a maximum value (refer to chapter Technical data (Page 39)).
Figure 5-2 Connecting the output voltage (examples 6EP1334-2BA20 and 6EP1336-2BA10)
The output voltage is connected via the + and - terminals at the output of the power supply
(see Figure 5-2 Connecting the output voltage (examples 6EP1334-2BA20 and 6EP1336-
2BA10) (Page 37)). Ensure that the output cables are dimensioned correctly for the
maximum output current rms value and fused accordingly.
Note
If the safety concept of the plant or system specifies that the DC output circuit should be
grounded (PELV), then it is permissible that the output voltage of the SITO
P power supply is
grounded. In this case, ideally, the grounding at the output should be directly connected from
terminal "
-" of the power supply to a suitable connection point of the protective conductor
system (PE) of the plant or system.
Installation
5.2 Output-side connection
SITOP PSU100S
38 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 39
Technical data
6
Note
Technical data is applicable for a rated input voltage, rated load and +25° C ambient
temperature (if nothing else is specified).
6.1
Input
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Input
1-phase, AC
Rated voltage
Ue rated
120 / 230 V
Voltage range
85-132 / 170-264 V
85-132 / 176-264 V
automatic range
switchover
Yes
Connect/shutdown
threshold, typical
80 V / 61 V 77 V / 63 V 70 V / 66 V 80 V/78 V or
160 V/155 V
Power failure buffering
at Ia rated, min
20 ms 20 ms 20 ms 20 ms
Power-failure buffering
at 93 / 187 V
at 120 / 230 V
Rated line frequency
50/60 Hz
Line frequency range
47...63 Hz
Input current / at rated
value of input voltage
120 V
1.25 A 2.34 A 4.49 A 7.5 A
Input current / at rated
value of input voltage
230 V
0.74 A 1.36 A 1.91 A 3.5 A
Switch-on current
limitation (+25 °C),
max.
33 A 40 A 60 A 11 A
I²t, at 120 V AC, max
0.1 A
2
s
0.3 A
2
s
1.6 A
2
s
2.5 A
2
s
I²t, at 230 V AC, max.
0.4 A
2
s
1.0 A
2
s
5.6 A
2
s
10 A
2
s
Integrated input fuse
Fuse T 3.15 A
Fuse T 3.15 A
Fuse T 6 A
Fuse T 10 A
Technical data
6.1 Input
SITOP PSU100S
40 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Protection in the line
feeder cable (IEC 898)
Recommended: Circuit
breaker, C
characteristic, 3 A
Recommended: Circuit
breaker, C
characteristic, 6 A
Recommended: Circuit
breaker, C
characteristic, 10 A
Recommended: Circuit
breaker, C
characteristic, 10 A
or
Circuit breaker
3RV2411-1JA10
(120 V) or 3RV2411-
1FA10 (230 V)
Overvoltage strength
2.3 × Ue rated, 1.3 ms
6EP1322-2BA00
6EP1323-2BA00
Input
1-phase, AC
Rated voltage Ue rated
120 / 230 V
Voltage range
85-132 / 170-264 V
automatic range switchover
Yes
Connect/shutdown threshold,
typical
82 V / 66 V 66 V / 63 V
Power failure buffering at
Ia rated, min
20 ms 20 ms
Power-failure buffering
at 93 / 187 V
Rated line frequency 50/60 Hz
Line frequency range 47...63 Hz
Input current / at rated value of
input voltage 120 V
1.73 A 3.24 A
Input current / at rated value of
input voltage 230 V
0.99 A 1.41 A
Switch-on current limitation
(+25 °C), max.
45 A 60 A
I²t, at 120 V AC, max.
0.3 A
2
s
1.6 A
2
s
I²t, at 230 V AC, max.
1.0 A
2
s
5.6 A
2
s
Integrated input fuse
Fuse T 3.15 A
Fuse T 6 A
Protection in the line feeder
cable (IEC 898)
Recommended: Circuit breaker,
C characteristic, 3 A
Recommended: Circuit breaker,
C characteristic, 6 A
Overvoltage strength
2.3 × Ue rated, 1.3 ms
Technical data
6.2 Output
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 41
Figure 6-1 Power-failure buffering
6.2
Output
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Output
Regulated, isolated DC voltage
Rated voltage value
Ua rated DC
24 V
Total tolerance, static ±
3 %
3 %
3 %
3 %
Static line regulation,
approx. ±
0,1 % 0,1 % 0,1 % 0,5 %
Static load regulation,
approx. ±
1 % 1 % 1 % 1 %
Residual ripple
Peak-peak, max.
150 mV 150 mV 150 mV 150 mV in the load
range >100 mA
300 mV in the load
range up to 100 mA
Spikes peak-peak, max.
(bandwidth, 200 MHz)
240 mV 240 mV 240 mV 240 mV
Adjustment range
22.8...28.0 V
24...28.0 V
Product function / output
voltage can be adjusted
Yes
Output voltage setting
Remark
Using a potentiometer
Max. 480 W
Status display
LED green for 24 V O.K.
Signaling
Relay contact (NO contact, rating 60 V DC /0.3 A) for 24 V O.K.
Response when
switching on/off
Overshoot of Ua<720 mV No overshoot of Ua
(soft start), with the
exception of a
capacitive load
Starting delay, max.
300 ms
300 ms
300 ms
1.5 s
Technical data
6.2 Output
SITOP PSU100S
42 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Start delay, typ.
200 ms
160 ms
150 ms
500 ms
Voltage rise
120 V / 230 V AC max.
100 ms 100 ms 100 ms 500 ms
Voltage rise
120 V / 230 V AC typ.
15 ms 15 ms 20 ms 50 ms
Rated current Ia rated
2.5 A
5 A
10 A
20 A
Current range
Remark
0...2.5 A
3 A to +45° C
+60 to +70 °C;
derating:
3 % Ia rated/K
0...5 A
6 A to +45° C
+60 to +70 °C;
derating:
3 % Ia rated/K
0...10 A
12 A to +45° C
+60 to +70 °C;
derating:
3 % Ia rated/K
0...20 A
24 A to +45° C
+60 to +70 °C;
derating:
5 % Ia rated/K
Output active power /
typical
60 W 120 W 240 W 480 W
Overload capability
(Extra Power)
3.75 A for 5 s/min 7.5 A for 5 s/min 15 A for 5 s/min 30 A for 5 s/min
Short-time overload
current / for a short
circuit when powering up
/ typical
9 A 18 A 33 A 35 A
Duration of the overload
capability, overcurrent /
for a short circuit while
powering up
Remark
800 ms
once-only
800 ms
once-only
800 ms
once-only
100 ms
every 2.5 s
Short-time overload
current / for a short
circuit in operation /
typical
9 A 18 A 33 A 35 A
Duration of the overload
capability, overcurrent /
for a short circuit in
operation
Remark
800 ms
once-only
800 ms
once-only
800 ms
once-only
100 ms
every 2.5 s
Can be connected in
parallel to increase the
power rating
Yes
Number of devices that
can be connected in
parallel to increase the
power rating, units
2
Output characteristic see diagram, output
characteristic for
6EP1332-2BA20
(Page 44)
see diagram, output
characteristic for
6EP1333-2BA20
(Page 45)
see diagram, output
characteristic for
6EP1334-2BA20
(Page 45)
see diagram, output
characteristic for
6EP1336-2BA20
(Page 45)
Capacitive load, max.
2 mF/A
Technical data
6.2 Output
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 43
6EP1322-2BA00
6EP1323-2BA00
Output Regulated, isolated DC voltage
Rated voltage value Ua rated
DC
12 V
Total tolerance, static ±
3 %
3 %
Static line regulation, approx. ±
0,1 %
0,1 %
Static load regulation, approx. ±
1 %
1 %
Residual ripple
Peak-peak, max.
150 mV 150 mV
Spikes peak-peak, max.
(bandwidth, 200 MHz)
240 mV 240 mV
Adjustment range
11.5...15.5 V
Product function / output voltage
can be adjusted
Yes
Output voltage setting
Using a potentiometer
Status display
LED green for 12 V O.K.
Signaling
Relay contact (NO contact, rating 60 V DC /0.3 A) for 12 V O.K.
Response when switching on/off
Overshoot of Ua<360 mV
Starting delay, max.
300 ms
300 ms
Start delay, typ.
180 ms
170 ms
Voltage rise
120 V / 230 V AC max.
100 ms 100 ms
Voltage rise
120 V / 230 V AC typ.
10 ms 10 ms
Rated current Ia rated
7 A
14 A
Current range
Remark
0...7 A
+55...+70 °C derating:
5 % Ia rated/K
0...14 A
+55...+70 °C derating:
5 % Ia rated/K
Output active power / typical
84 W
168 W
Overload capability (Extra
Power)
10.5 A for 5 s/min 21 A for 5 s/min
Short-time overload current / for
a short circuit when powering up
/ typical
26 A 48 A
Duration of the overload
capability, overcurrent / for a
short circuit while powering up
Remark
800 ms
once-only
800 ms
once-only
Short-time overload current / for
a short circuit in operation /
typical
26 A 48 A
Technical data
6.2 Output
SITOP PSU100S
44 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
6EP1322-2BA00
6EP1323-2BA00
Duration of the overload
capability, overcurrent / for a
short circuit in operation
Remark
800 ms
once-only
800 ms
once-only
Can be connected in parallel to
increase the power rating
Yes
Number of devices that can be
connected in parallel to increase
the power rating, units
2
Output characteristic see diagram, output
characteristic for 6EP1322-
2BA20 (Page 46)
see diagram, output
characteristic for 6EP1323-
2BA20 (Page 46)
Capacitive load, max.
2 mF/A
Figure 6-2 Startup delay/voltage rise
Figure 6-3 Output characteristic 6EP1332-2BA20
Technical data
6.2 Output
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 45
Figure 6-4 Output characteristic 6EP1333-2BA20
Figure 6-5 Output characteristic 6EP1334-2BA20
Figure 6-6 Output characteristic 6EP1336-2BA10
Technical data
6.2 Output
SITOP PSU100S
46 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Figure 6-7 Output characteristic 6EP1322-2BA00
Figure 6-8 Output characteristic 6EP1323-2BA00
The device supplies a constant output voltage until the current limit is reached. In the event
of an overload, the output current and the output voltage are reduced.
When the output voltage falls below approx. 10 V, the 6EP1336-2BA10 device switches off,
and automatically restarts. This response is repeated as long as the overload condition is
present.
Technical data
6.3 Efficiency
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 47
6.3
Efficiency
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Efficiency at Ua rated, Ia rated
120 V / 230 V AC approx.
83 % / 85 % 86 % / 87 % 89 % / 90 % 89 % / 90 %
Power loss at Ua rated, Ia rated
120 V / 230 V AC approx.
11 W / 10 W 18 W / 16 W 27 W / 25 W 59 W / 53 W
Power loss when idling
120 V / 230 V AC approx.
1.7 W / 1.2 W 1.8 W / 1.3 W 3.0 W / 2.4 W 4.1 W / 3.6 W
6EP1322-2BA00
6EP1323-2BA00
Efficiency at Ua rated, Ia rated
120 V / 230 V AC approx.
82 % / 83 % 86 % / 87 %
Power loss at Ua rated, Ia rated
120 V / 230 V AC approx.
16 W / 15 W 27 W / 15 W
Power loss when idling
120 V / 230 V AC approx.
1.5 W / 1.0 W 2.8 W / 2.3 W
Figure 6-9 Efficiency 6EP1332-2BA20
Technical data
6.3 Efficiency
SITOP PSU100S
48 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Figure 6-10 Efficiency 6EP1333-2BA20
Figure 6-11 Efficiency 6EP1334-2BA20
Technical data
6.3 Efficiency
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 49
Figure 6-12 Efficiency 6EP1336-2BA10
Figure 6-13 Efficiency 6EP1322-2BA00
Technical data
6.4 Closed-loop control
SITOP PSU100S
50 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Figure 6-14 Efficiency 6EP1323-2BA00
6.4
Closed-loop control
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
6EP1322-2BA00
6EP1323-2BA00
Dyn. line regulation
(Ue rated ±15%), max.
0.3 % Ua 0.3 % Ua 0.3 % Ua
Dyn. load regulation
(Ia: 10/90/10 %), max.
±5 % Ua - ±15 % UA
Dyn. load regulation
(Ia: 10/90/10 %), typ.
- ±3 % Ua -
Load-step settling time
10 to 90 %, max.
1 ms 10 ms 1 ms
Load-step settling time
10 to 90 %, typ.
- 2 ms -
Load-step settling time
90 to 10 %, max.
1 ms 10 ms 1 ms
Load-step settling time
90 to 10 %, typ.
- 2 ms -
Technical data
6.5 Protection and monitoring
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 51
6.5
Protection and monitoring
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Output overvoltage
protection
in the case of an internal fault Ua < 33 V Yes, according to
EN 60950-1
Current limitation
Typ.
Remark
3.75 A
Overload capability
with 150 % Ia rated up
to 5 s/min
7.5 A
Overload capability
with 150 % Ia rated up
to 5 s/min
15 A
Overload capability
with 150 % Ia rated up
to 5 s/min
21.5 A (>45 °C)
25.5 A (<45 °C)
Overload capability
with 150 % Ia rated up
to 5 s/min
Short-circuit protection Yes, current is statically limited Electronic trip,
automatic restart
(hiccup)
Continuous short-
circuit current rms
value, approx.
3.4 A 7.3 A 14.6 A 7 A
Overload / short-circuit
display
-
6EP1322-2BA00
6EP1323-2BA00
Output overvoltage protection
< 20 V
< 20 V
Current limitation, typ.
Remark
10.5 A
Overload capability with
150 % Ia rated up to 5 s/min
21 A
Overload capability with
150 % Ia rated up to 5 s/min
Short-circuit protection Yes, current is statically limited
Continuous short-circuit current
rms value, approx.
8.8 A 16.4 A
Overload / short-circuit display
-
6.6
MTBF
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1322-2BA00
6EP1323-2BA00
6EP1336-2BA10
Mean Time Between Failures SN29500:
> 1600000 h
at 40 °C, rated load, 24 h operation
SN29500:
> 500000 h (typ. 700000 h)
at 40° C, rated load, 24 h operation
Technical data
6.7 Mechanical system
SITOP PSU100S
52 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
6.7
Mechanical system
6EP1332-2BA20
6EP1333-2BA20
6EP1322-2BA00
6EP1334-2BA20
6EP1323-2BA00
6EP1336-2BA10
Connection system
Screw-type terminal
Connections / line
supply
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² solid/finely stranded L1, N, PE: 1 screw
terminal each for
0.2 ... 4 mm²
solid/finely stranded
Connections / output +, -: 2 screw terminals each for 0.5 ... 2.5 m +, -: 2 screw terminals
each for 0.2 ... 4 m
Connections / auxiliary
contacts
Signaling contact: 2 screw terminals for 0.5 mm ... 2.5 mm² 13, 14 (signaling
contact): 1 screw
terminal each for
0.14 ... 1.5 mm²
Width of the housing
32.5 mm
50 mm
70 mm
115 mm
Height of the housing
125 mm
125 mm
125 mm
145 mm
Depth of the housing
120 mm
120 mm
120 mm
150 mm
Installation width
32.5 mm
50 mm
70 mm
120 mm
Mounting height
225 mm
225 mm
225 mm
245 mm
Weight, approx.
0.32 kg
0.5 kg
0.8 kg
2.4 kg
Product feature of the
housing / housing that
can be lined up next to
one another
Yes
Type of mounting /
panel mounting
No
Type of mounting / rail
mounting
Yes
Type of mounting /
S7-300 rail mounting
No
Mounting
Can be snapped onto standard EN 60715 35x7,5/15 mounting rails
Technical data
6.8 Accessories
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 53
6.8
Accessories
Accessories
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
6EP1322-2BA00
6EP1323-2BA00
Electrical accessories
Redundancy module, buffer module
Mechanical accessories Device identification labels
10 mm × 7 mm, pastel turquoise
3RT1900-1SB10
Device identification labels
20 mm × 7 mm, pastel turquoise
3RT1900-1SB20
6.9
Dimension drawing
See chapter Dimensions and weight (Page 14)
CAD data that can be downloaded from the Internet:
6EP1332-2BA20
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00727)
6EP1333-2BA20
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00730)
6EP1334-2BA20
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00733)
6EP1336-2BA10
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00720)
6EP1322-2BA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00736)
6EP1323-2BA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00739)
Technical data
6.9 Dimension drawing
SITOP PSU100S
54 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 55
Safety, approvals, EMC
7
7.1
Safety
6EP1332-2BA20, 6EP1333-2BA20, 6EP1334-2BA20,
6EP1336-2BA10, 6EP1322-2BA00, 6EP1323-2BA00
Primary/secondary galvanic isolation
Yes
Galvanic isolation SELV output voltage Ua according to EN 60950-1 and EN 50178
Transformer according to EN 61558-2-16
Protection class
Class I
Degree of protection (EN 60529)
IP20
Leakage current, typ.
1 mA
Leakage current, max.
3.5 mA
Test voltage
See Table 7-1 Test voltage (Page 56)
Safety, approvals, EMC
7.2 Test voltage
SITOP PSU100S
56 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
7.2
Test voltage
Figure 7-1 Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another (L, N)
Connect the output terminals, signaling contact and PE with one another
Test (C)
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1 Test voltage
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 VDC
2200 VDC
700 VDC
60 s
3000 VAC
1500 VAC
500 VAC
Production test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Field test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Remark:
Tripping current for DC measurement: 0
mA
Tripping current for AC measurement: <100 mA
Safety, approvals, EMC
7.3 Approvals
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 57
7.3
Approvals
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
6EP1322-2BA00
6EP1323-2BA00
CE marking Yes, (2004/108/EG and 2006/95/EG)
CSA approval
Yes, CSA C22.2 No. 60950-1, cCSAus (ANSI/ISA 12.12.01)
UL/cUL approval
cULus-listed (UL 508, CSA 22.2 No. 107.1), File E197259
Explosion protection ATEX EX II 3G Ex nA nC IIC T4 Gc;
cCSAus Class I, Div. 2, GROUPS A, B, C, D, T4
CB approval
Yes
CB-Scheme
IEC 60950-1
SEMI F47 compliance
Not tested
fulfilled
Not tested
Marine approvals Germanischer Lloyd (GL),
BV marine
Germanischer Lloyd (GL) Germanischer Lloyd (GL)
Safety, approvals, EMC
7.4 EMC
SITOP PSU100S
58 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
7.4
EMC
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1322-2BA00
6EP1323-2BA00
6EP1336-2BA10
Electrostatic
discharge
EN 61000-4-2 8 kV contact, 8 kV air 8 kV contact, 8 kV air
Electromagnetic
fields
EN 61000-4-3 80…1,000 MHz 10 V/m
1400…2,000 MHz 10 V/m
2000…2700 MHz 10 V/m
895…905 MHz and 1.89 GHz 10 V/m
80…1,000 MHz 15 V/m
1000…2700 MHz 10 V/m
High-speed transient
disturbance variables
(burst)
EN 61000-4-4 2 kV at line connections
1 kV at DC output
4 kV at line connections
2 kV at DC output
Surge voltages EN 61000-4-5 2 kV symmetrical at the line connections
4 kV asymmetrical at the line connections
500 V symmetrical/asymmetrical on DC output cables
High-frequency fields
EN 61000-4-6
10 V; 0.15…80 MHz
10 V; 0.15…80 MHz
Magnetic fields
EN 61000-4-8
Not applicable
30 A/m; 50 Hz
Voltage dips EN 61000-4-11 100% for 20 ms,
60% for 200 ms,
30% for 500 ms
100% for 20 ms,
60% for 200 ms,
30% for 500 ms
Voltage interruptions
EN 61000-4-11
100% for 5000 ms
100% for 5000 ms
Emitted interference
EN 55022
Class B
Class B
Line harmonics
limitation
EN 61000-3-2 Class A Class A
Generic standards
EN 61000-6-2
Immunity for industrial environments
EN 61000-6-3
Emission for residential areas
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 59
Ambient conditions
8
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1322-2BA00
6EP1323-2BA00
6EP1336-2BA10
Ambient temperature -25 ... +70 °C with natural convection
(self convection)
Derating for 24 V versions:
from +60°C: 3 % Ia, rated/K;
from Ua>24 V: -10...+50 °C
from Ue<100 V and lower, output
power is reduced depending on the
ambient temperature
Derating for 12 V versions:
from +55 °C: 5 % Ia, rated/K
0 ... +70 °C with natural convection
(self convection)
Derating:
from +60°C: 5 % Ia, rated/K;
from Ue<100 V or Ue<200
V and lower,
output power is reduced depending on
the ambient temperature
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Transport and storage temperature -40 ... +85° C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, without condensation
Ambient conditions
SITOP PSU100S
60 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1322-2BA00
6EP1323-2BA00
6EP1336-2BA10
Mechanical stressing in operation Tested according to:
EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 58.4 Hz
2 g acceleration in the range 8.4150 Hz
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s2 , test duration 11 ms
Damaging gases Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
1080 ... 795 hPa (-1000 ... +2000 m)
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5 % / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 4-7 Mounting height derating (Page 21)
Overvoltage category:
III to 2000 m (EN 50178)
II from 2000 m to 6000 m (EN 50178)
II to 2000 m (EN 60950-1)
I from 2000 m to 6000 m (EN 60950-1)
Storage:
1080 ... 660 hPa (-1000 ... +3500 m)
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 61
Applications
9
9.1
Parallel connection to increase power rating
To increase the power rating, two SITOP PSU100S power supplies of the same type can be
directly connected in parallel.
The following must be observed:
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external connection point (terminal strip) if possible.
The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 50 mV. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 50 mV.
Figure 9-1 Parallel connection
Note
It is not permissible to take into account simultaneous overload capability (Extra
-
Power 150%
for 5
s/min) of several power supplies connected in parallel when configuring the power
supply system.
Applications
9.1 Parallel connection to increase power rating
SITOP PSU100S
62 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
NOTICE
Protective circuit for the parallel connection of more than two power supplies
For connection of more than two power supplies in parallel, additional measures must be
taken to prevent high backward feeding currents in the event of a secondary device fault.
For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-conform circuit-
breaker) must be installed between each "+" terminal of the power supply and the common
connection point.
Applications
9.2 Parallel connection for redundancy
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 63
9.2
Parallel connection for redundancy
Connecting several SITOP PSU100S power supplies in parallel for redundancy purposes is
required if especially high demands are placed regarding the availability of a reliable 24 V
power supply.
Using the SITOP PSE202U redundancy module, two 24 V power supplies of the same type
up to 20 A can be decoupled (Figure 9-2 Redundant configuration with two power supplies
and SITOP PSE202U redundancy module (Page 63)). When one of the devices fails, then
the other automatically takes over the power supply. If one of the power supplies fails, then
this is signaled using an LED on the redundancy module as well as an isolated relay contact.
When dimensioning the system, it must be ensured that n+1 redundant connected power
supplies can handle the total power requirement of the remaining n power supplies.
Note
For a high reliability of the supply, it is recommended that the redundant switched power
supplies are fused separately on the line
-side and, if possible, be connected to different
power supply networks.
Figure 9-2 Redundant configuration with two power supplies and SITOP PSE202U redundancy
module
You can find additional information at:
SITOP PSE202U manual (http://support.automation.siemens.com/WW/view/en/42248598)
Applications
9.3 Series connection for increased voltage
SITOP PSU100S
64 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
9.3
Series connection for increased voltage
To achieve an output voltage of 48 V DC, two 24 V SITOP PSU100S power supplies of the
same type can be connected in series. In this case, connect the "-" terminal of the first power
supply to the "+" terminal of the second power supply. The "+" terminal of the first power
supply and the "-" terminal of the second power supply are routed to the load.
Depending on the grounding point of the secondary output voltages, voltages of +48 V,
±24 V or -48 V can be realized.
In the case of an asymmetric load distribution, it is not possible to guarantee correct
functionality.
WARNING
SELV is not guaranteed in the case of a fault
When connecting two power supplies in series, the continuous, permissible SELV voltage
of a maximum of 60 VDC according to EN 60950-1 cannot be guaranteed in the case of a
fault.
Figure 9-3 Series connection
Applications
9.4 Overload protection in the 24 V output circuit
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 65
9.4
Overload protection in the 24 V output circuit
If overload occurs, the electronic current limiting of the SITOP PSU100S power supply limits
the output current to a maximum value (refer to chapter Technical data (Page 39)). The
output cables are protected against a thermal overload if they are dimensioned
corresponding to the maximum rms output current, or protected using additional components
(for example, miniature circuit breaker, fuses).
However, a load circuit that fails as a result of overload, for instance, should frequently be
reliably and quickly identified and specifically switched off before the power supply goes into
current-limiting mode (in current-limiting mode, the supply voltage would also be reduced for
all of the remaining 24 V loads).
The SITOP PSE200U selectivity module with 4 channels (versions with adjustable output
current range for each channel from 0.5-3 A and 3-10 A) is available; this monitors the 24 V
branches for overloading and short-circuiting (Figure 9-4 Electronic protection of 24 V loads
using the SITOP PSE200U selectivity module (Page 65)). Brief current peaks, e.g. as a
result of a high inrush current, are permitted, and branches with a longer overload are
switched into a no-current condition. This is also ensured for cables in a high-ohmic
condition and for short-circuits that slowly develop over time.
When a channel fails, the fault is signaled using a group signal contact or as a single
channel signal, and the branch of the module involved is displayed using an LED.
For variants with single-channel signaling, function blocks for evaluation purposes are
available for SIMATIC S7-1200/1500/300/400, for STEP 7 Classic and TIA Portal at no
charge.
You can find additional information at:
SITOP PSE200U selectivity module manuals
(http://support.automation.siemens.com/WW/view/en/10807226/130000)
Figure 9-4 Electronic protection of 24 V loads using the SITOP PSE200U selectivity module
Applications
9.5 Protection against short-time voltage dips
SITOP PSU100S
66 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
9.5
Protection against short-time voltage dips
For a drop in the line-side supply voltage, the SITOP PSU100S power supply still maintains
the output voltage for a short time in the millisecond range (see Chapter Technical data
(Page 39)).
For line supplies that manifest frequent brief voltage dips, in order to increase the power
supply reliability, it may make sense to increase the line buffering time in the device using an
additional SITOP PSE201U buffer module.
The SITOP PSE201U buffer module, based on electrolytic capacitors, is connected in
parallel to the 24 V power supply output (Figure 9-5 Buffering brief power failures using the
SITOP PSE201U buffer module (Page 66)). The buffer time is 200 ms at 40 A up to 1.6 s for
a load current of 5 A. This time can be increased a multiple number of times by connecting
buffer modules in parallel; the maximum buffer time is 10 s.
You can find additional information at:
SITOP PSE201U manual (http://support.automation.siemens.com/WW/view/en/41129219)
Figure 9-5 Buffering brief power failures using the SITOP PSE201U buffer module
Applications
9.6 Protecting against longer power failures
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 67
9.6
Protecting against longer power failures
Sudden and longer failures of the line supply voltage can result in undefined states and
significant danger as a result of the associated failure of the plant or system control. The
SITOP power supply product portfolio includes various DC-UPS solutions to prevent the
failure of the 24 V power supply voltage.
Power supply failures up into the minutes range can be buffered using the maintenance-free
SITOP UPS500 DC-UPS modules based on capacitors (Figure 9-6 24 V buffering to allow
the saving of process data and controlled shutdown of PCs (Page 67)).
Figure 9-6 24 V buffering to allow the saving of process data and controlled shutdown of PCs
Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply
integrated into PC-based automation solutions. This supports further processing of the status
signals and safely running down the PC.
You can find additional information at:
DC UPS with capacitors manual
(http://support.automation.siemens.com/WW/view/en/48932766/133300)
Applications
9.6 Protecting against longer power failures
SITOP PSU100S
68 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Using DC UPS SITOP UPS1600 and SITOP UPS100 battery modules, buffer times in the
range of hours can be implemented. Intelligent battery management using Energy Storage
Link automatically detects the UPS1100 energy storage device, and ensures optimum
temperature-controlled charging and continuous monitoring. The UPS1600 can be flexibly
integrated into the widest range of automation applications with its digital inputs/outputs as
well as optional USB interface or Ethernet/PROFINET port.
Figure 9-7 24 V buffering with SITOP UPS1600 to maintain communication, signaling functions,
sensor measured values and position values
For open, PC-based automation systems, configuration and monitoring is realized using the
SITOP UPS Manager PC software, which is available at no charge. This allows PC
responses to the operating states of the DC UPS to be freely selected and offers
comprehensive diagnostic functions.
For TIA-based automation systems, the UPS1600 is engineered using the TIA Portal.
Special function blocks for SIMATIC S7-300/400/1200 and S7-1500 available at no charge
make it easy to integrate operating and diagnostics information into STEP 7 user
programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no
charge.
You can find additional information at:
DC UPS SITOP UPS1600/UPS1100 Manual
(http://support.automation.siemens.com/WW/view/en/84977415)
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 69
Environment
10
The device is in conformance with RoHS.
As a rule, only non-silicon precipitating materials are used.
Disposal guidelines
Packaging and packaging aids can and should always be recycled. The product itself may
not be disposed of as domestic refuse.
Environment
SITOP PSU100S
70 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
SITOP PSU100S
Operating Instructions, 07.2014, C98130-A7589-A1-5-7629 71
Service & Support
11
Technical support
Technical support for all IA/DT products can be accessed through the following
communication channels:
Phone: + 49 (0) 911 895 7222
E-Mail (mailto:support.automation@siemens.com)
Internet:
Online support request form (http://www.siemens.de/automation/support-request)
Technical documentation on the Internet
Operating instructions and manuals for SITOP are available in the Internet:
Operating instructions/manuals (http://www.siemens.de/sitop/manuals)
SITOP power supply homepage
General news about our power supplies is available in the Internet at the SITOP homepage:
SITOP (http://www.siemens.de/sitop)
Information material
SITOP information can be downloaded from the Internet:
Information and download center (http://www.siemens.de/sitop-infomaterial)
CAx data
2D/3D data and circuit diagram macros can be downloaded from the Internet:
Siemens image database (http://www.siemens.de/sitop-cax)
Request all CAx data via the CAx download manager:
CAx shopping cart (http://www.siemens.de/cax)
SITOP Selection Tool
Simply and quickly select the optimum the power supply or DC-UPS:
SITOP Selection Tool (http://www.siemens.de/sitop-selection-tool)
Online catalog and ordering system
The online catalog and the online ordering system are available through the Industry Mall
homepage:
Industry Mall (http://www.siemens.com/industrymall/de)
Service & Support
SITOP PSU100S
72 Operating Instructions, 07.2014, C98130-A7589-A1-5-7629
Contact persons
If you have any questions regarding the use of our products, then contact the Siemens
contact person in your regional Siemens sales office.
You can find these addresses as follows:
On the Internet (http://www.siemens.de/automation/partner)
In Catalog CA 01