Features
■ Low peak clamping voltage even during
severe current surges
■ Ability to repeatedly protect against surge
currents in excess of 10,000 amperes
■ Convenient mounting and grounding to any
fl at surface or to Din 1 (TS-32) or DIN-3
(TS-35) rail
■ Cable shields are passed through and
may be either grounded or not grounded at
the protector
■ Vibration-proof screw-type clamp terminals
■ Flame-resistant epoxy-fi lled housing
1800 Series – Signal and Dataline Protector
Specifi cations are subject to change without notice.
Customers should verify actual device performance in their specifi c applications
Bourns 1800 Series Signal and Dataline Protectors are designed to protect sensitive electronic circuits and components from damaging surge
voltages and currents. Their extremely fast response and low clamping voltages make them particularly suitable for the protection of signal
and data lines associated with computer, data communication, instrumentation, broadcasting and industrial controls. They may be used
directly with EIA standard interfaces RS-232, RS-422, RS-423, RS-485 and with 20 mA and 50 mA instrumentation loops. Model 1800 Series
Signal and Dataline Protectors are fast, rugged and capable of protecting against fast rising voltage transients as well as the severe current
surges associated with lightning discharges.
Method of Operation
Bourns 1800 Series are heavy-duty, multi-staged protectors. A solid-state section intercepts the leading edge of the surge with sub-
nanosecond response time. Within microseconds a 3-pole common chambered Gas Tube capable of handling 20,000 ampere lightning
currents operates and crowbars the surge to ground. The protector remains in the crowbar state until the surge has passed and line voltages
return to safe levels, then automatically restores the line to normal operation. There is no need for resetting a breakeror replacing a fuse.
Application
Protectors are generally placed at each end of a signal or data line or current loop. In the case of daisy-chain confi gurations (such as RS-485),
protectors are placed at each node. 1820 models provide both line-to-ground and line-to-line protection and are designed to use on differen-
tial signals (such as RS-422 or RS-485) and 4-20 mA current loops. 1810 models provide line-to-ground protection for two separate circuits
and are designed for use on ground referenced signals (such as RS-232) where the return wire is grounded at the protector. The 1811 and
1821 models provide the same protection modes for high frequency applications.
Related Bourns Protectors
For outdoor applications with 1/2 inch NPT ports (such as fi eld-mounted 4-20 mA transmitters), please refer to Bourns 1669 Series Protector.
In this application, the mixed use of an 1800 Series Protector at the controller and a 1669 Series Protector at the fi eld is recommended.
Characteristics @ 25 °C
Surge Life
>100 operations with 200 Amps ...................................................................................................... 10 x 1000 µsec
>10 operations with 10,000 Amps ................................................................................................... 8 x 20 µsec
DC Leakage Current at Rated L/G Voltage ........................................................................................... >10 µAmps
Signal/Data Attenuation at Maximum Data Rate................................................................................... 3 db with 600 Ω termination
Operating Temperature .......................................................................................................................... -40 ºC to + 60 ºC
Response Time ...................................................................................................................................... 50 pico-seconds
Wire Size ................................................................................................................................................ 22-14 AWG
INTERFACE OPERATING
CHARACTERISTICS
Peak Max.
Signal Data
Voltage Rate
L/L L/G
BASE
MODEL
NUMBER
(see below
for Clamp
designation)
PROTECTIVE CHARACTERISTICS
Peak Clamping Voltages LOAD
CURRENT
TYPICAL
CAPACITANCE
L/G L/L
SERIES
RESISTANCE
Each Line L/L
(Input to output)
@ 5000 Amps,
8x20 µsec
Surge and Voltage
Rate-of-Rise of
100 kV / µsec
L/L L/G
@ 1000 Amps,
8x20 µsec
Surge and Voltage
Rate-of-Rise of
500 V / µsec
L/L L/G
(Volts) (Volts) (MHz) (Volts) (Volts) (Volts) (Volts) (mA) (pF) (pF) (Ohms)
20 10 10 1810-10-XX 50 25 42 21 220 2200 1200 10
10 10 4 1820-10-XX 25 25 21 21 220 3300 3300 10
20 10 50 1811-10-XX 60 30 52 26 350 45 45 10
10 10 50 1821-10-XX 30 30 26 26 350 65 65 10
30 15 8 1810-15-XX 70 35 56 28 180 1500 750 15
15 15 3 1820-15-XX 35 35 28 28 180 2300 2300 15
30 15 45 1811-15-XX 80 40 64 32 300 45 45 15
15 15 45 1821-15-XX 40 40 64 32 300 65 65 15
56 28 9 1810-28-XX 110 55 90 45 150 1100 600 22
28 28 4 1820-28-XX 55 55 45 45 150 1800 1800 22
56 28 40 1811-28-XX 120 60 45 45 250 45 45 22
28 28 40 1821-28-XX 60 60 45 45 250 65 65 22
100 50 10 1810-50-XX 178 89 156 89 100 500 300 51
50 50 4 1820-50-XX 89 89 45 45 100 800 800 51