Type XII Contacts 114- 10005
Rev J 3 of 8Tyco Electronics Corporation
3.3. Chemical Exposure
Do not store contacts near any chemicals listed below as they may cause stress corrosion cracking in the
contacts.
Alkalies Carbonates Phosphates Citrates Tartrates
Amines Citrates Sulfides Nitrites
Ammonia Nitrites Sulfur Compounds
3.4. Cutoff Tab
Cutoff tabs are the remaining portion of the carrier strip after the contact is cut from the strip. The following
dimensional requirements will ensure proper application for these contacts.
1. The cutoff tab must not exceed the dimension shown in Figure 3.
2. The burr resulting from the cutoff tab shearing must not exceed the dimension shown in Figure 3.
3.5. Terminating
Select the contact to be crimped for the wire size being used. Crimp the contact according to the instructions
packaged with that tooling (refer to Section 5, TOOLING).
3.6. Crimped Contact Requirements
A. Effective Crimp Length
For optimum crimp effectiveness, the crimp must be within the area shown in Figure 3 and must meet the
crimp dimensions provided in the table in Figure 2. Effective crimp length is defined as that portion of the
wire barrel, excluding bellmouth(s), fully formed by the crimping tool. Instructions for adjusting, repairing,
and inspecting tools are packaged with the tools.
Each crimp dimension represents the functional range of a wire/contact combination. There are tool designs available
to meet various application requirements. The developed crimp configuration is unique for each tool design and is
acceptable provided the crimp height is within the functional range. For crimp dimensions of a specific tool, refer to
instruction sheet packaged with manual tools and applicator log packaged with power tools.
B. Wire Conductor Location
After crimping, the end of the wire conductor must be flush with or extend 1.27 mm [.050 in.] from the front
end of the contact wire barrel. Both the insulation and the conductor must be visible between the insulation
barrel and wire barrel. Care must be taken not to allow the wire insulation to be crimped in the wire barrel.
RefertoFigure3.
C. Contact Assist Spring
The contact assist spring on female contacts must be straight and not deformed.
D. Wire Barrel Seam
The seam between the two sides of the wire barrel must be completely closed and there must be no
evidence of loose wire strands or wire strands visible in the seam.
E. Wire Barrel Flash
Wire barrel flash is the formation that may appear on both sides of the wire barrel as the result of the
crimping process. It must not exceed the dimension provided in Figure 3.
F. Wire Barrel and Insulation Barrel Crimp
The crimp applied to the wire barrel and insulation barrel of the contact is the most compressed area and
is most critical in ensuring optimum electrical and mechanical performance of the crimped contact. The
contact wire barrel and insulation barrel height and width must be within the dimensions provided in
Figure 3.
G. Bellmouths
The rear bellmouth length must be within 0.51 to 1.27 mm [.020 to .050 in.] and the front bellmouth must
not exceed 0.51 mm [.020 in.]. Refer to Figure 3.
NOTE