709
Dimensions are shown for
reference purposes only. Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change. www.tycoelectronics.com
Technical support:
Refer to inside back cover.
P&B
Catalog 1308242
Issued 3-03 (PDF Rev. 9-03)
Coil Data @ 25°C
Voltage: From 6 to 120VDC, and 6 to 240VAC, 50/60 Hz.
Nom. Power: DC coils - 0.9 watt; 0.5 watt minimum operate @ 25°C.
AC coils - 1.2 VA; 0.55 VA minimum operate @ 25°C.
Max. Power: DC coils - 2.0 watts @ 25°C.
Duty Cycle: Continuous.
Initial Breakdown Voltage: 500V rms, 60 Hz.
Operate Data @ 25°C
Must-Operate Voltage: DC: 75% of nominal voltage.
AC: 85% of nominal voltage.
Operate Time: 13 milliseconds typical @ nominal voltage (excluding
bounce).
Release Time: 6 milliseconds typical @ nominal voltage (excluding
bounce).
Environmental Data
Temperature Range: -45°C to +70°C operate.
-60°C to +130°C storage.
Mechanical Data
Mountings: #3-48 stud, sockets with printed circuit or solder terminals,
or bracket plate with #6-32 threaded stud.
Termination: Printed circuit or solder/socket terminals.
Enclosures: See Ordering Information table.
Weight: 1.6 oz. approx. (45g).
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product
part number. It is recommended that users also seek out the pertinent
approvals files of the agencies/laboratories and review them to ensure the
product meets the requirements for a given application.
KHA series
General Purpose
Dry Circuit to 5A
Multicontact
AC or DC Relay
KHAU
Features
• Miniature size from 2 pole to 4 pole.
• KHAU is produced on an automated line, while KHU is produced
manually. Form, fit and function of the two versions are identical.
• Various applications include process control, photocopier, and data
processing.
• Push-to-test and indicator options available.
• Various contact materials available for specific load requirements.
Contact Data @ 25°C
Arrangements: 2 Form C (DPDT), 4 Form C (4PDT).
Expected Life: 10 million operations, mechanical; 100,000 operations min.
at rated loads. Ratings are based on tests of relays with
ungrounded frames.
Initial Breakdown Voltage: 500V rms, 60 Hz., between open contacts.
1240V rms, 60 Hz., between all other
elements.
Contact Ratings Resistive Rating
Minimum Maximum
1Silver 100mA @ 3A @
12VAC/12VDC 120VAC/28VDC
2* Silver-cadmium 500mA @ 5A @
oxide 12VAC/12VDC 120VAC/28VDC
3Gold-silver-nickel 10mA @ 2A @
12VAC/12VDC 120VAC/28VDC
6Bifurcated cross bar, Dry circuit 1A @
gold overlay silver 120VAC/28VDC
8Gold diffused silver 50mA @ 3A @
12VAC/12VDC 120VAC/28VDC
Note: Relays should only carry a maximum of 15 amps continuously for all poles combined.
Contact
Code Material
Coil Data DC Coils AC Coils
Resistance Nominal Resistance Nominal
Nominal in Ohms Inductance in Ohms AC Current
Voltage ±10% @ in Henrys ±15% in mA
250C
5 32 .072 — —
6 40 .08 10.5 200
12 160 .28 43 100
24 650 1.0 160 52
48 2,600 4.5 668 25
110 * 11,000 17.0 — —
120 * — — 3,900 11.0
240 — — 12,000 6.0
*Note: For 220 and 240VDC, use series dropping 5W resistor of 11,000Ω.