MasterPLUS
Accepts the output fuse module, for the easy
and space efficient protection of output
circuits
EMR: 6 to 125 VAC/DC, 125 and 220 VDC,
230 VAC and 24...240 V AC/DC supply
SSR: 24 - 125 VAC/DC, 6 to 220 VDC,
230 VAC and 24...240 V AC/DC supply
Special 125 V AC/DC and 230 V AC leakage
current suppression types (39.31.3, 39.61.3 EMR
and 39.30.3, 39.60.3 SSR)
Screw terminal and Push-in terminal
MasterTIMER
Timer adjustment via top mounted rotary
knob accessible after assembly
Control signal terminal
DIP-switch for selection of 4 time scales and 8
functions
Output with fuse module option
EMR and SSR: 12 to 24 VAC/DC supply
Screw terminal and Push-in terminal
Common features
Space saving 6.2mm wide
Connections for 16-way jumper link
Integral coil indication and protection circuit
Secure retention and easy ejection by plastic
clip
Dual screw head (blade+cross) terminals and
Push-in terminals versions
35mm rail mounting (EN 60715)
1 CO 6 A 250 VAC
High switching capability
1 solid state output (options 0.1 A 48 VDC,
2 A 24 VDC, 2 A 240 VAC)
Silent, high speed switching, long electrical life
EMR SSR
Electromechanical Relays Solid State Relays
39.41/39.71 39.40/39.70
39.11/39.01 39.10/39.00
39.21/39.51 39.20/39.50
39.81/ 39.91 39.80/39.90
MasterBASIC
For general use in any type of system
EMR: 6 to 24 and 125 V AC/DC,
230 V AC upply
SSR: 6 to 24 V DC, 125 V AC/DC,
230 V AC supply
Screw terminal and Push-in terminal
Page 4 Page 5
Page 8 Page 9
Page 10 Page 11
Page 12 Page 13
MasterINPUT
Jumper link option for the quick and easy
distribution of supply voltage to proximity
switches and similar input devices
EMR: 6 to 24 V and 125 VAC/DC,
230 VAC supply
SSR: 6 - 24 VDC, 24 - 125 VAC/DC,
230 VAC supply
Screw terminal and Push-in terminal
39.31 - 39.31.3/39.61 - 39.61.3 39.30 - 39.30.3/39.60 - 39.60.3
Page 6 Page 7
MasterOUTPUT
Jumper link option for the quick and easy
distribution of supply voltage to output side
and its connection to electromagnetic valves
and similar output devices
EMR: 6 to 24 V and 125 VAC/DC,
230 VAC supply
SSR: 6 to 24 VDC, 125 VAC/DC,
230 VAC supply
Screw terminal and Push-in terminal
I-2015, www.findernet.com
B
MasterINTERFACE 39 Series - Relay interface modules 39
SERIES
MasterBASIC
39.11 - 39.10 - 39.01 - 39.00
For general interface use in any type of
system and application.
Can be used for input interface applications
between auxiliary contacts, sensors etc. and
controllers, PLCs’ or motors. Or for output
interface between PLC’s controllers and
relays, solenoids etc.
PLC - Output PLC - Output
Output devices Output devices
MasterPLUS
39.31 - 39.30 - 39.31.3 - 39.30.3 - 39.61 - 39.60 - 39.61.3 - 39.60.3
This special version provides extra protection for the output circuit thanks to the replaceable
fuse module.
For general interface use in any type of system and application.
Can be used for input interface applications between auxiliary contacts, sensors etc. and
controllers, PLCs’ or motors. Or for output interface between PLC’s controllers and relays,
solenoids etc.
PLC - Input PLC - Input
Input devices Input devices
Fuse module
093.63
2
Fuse module
093.63
I-2015, www.findernet.com
39
SERIE S Typical Applications
B
MasterINPUT
39.41 - 39.40 - 39.71 - 39.70
These models allow the full termination of
input device to the interface without the need
for additional terminals - saving component
cost, time and panel space.
Quick and easy distribution of supply voltage
through the jumper link on the Bus-Bar (BB)
connection.
Ideal for interface applications between the
auxiliary contacts, sensors, limit switches and
Controllers or PLC’s.
MasterOUTPUT
39.21 - 39.20 - 39.51 - 39.50
These models allow the full termination of
output device to the interface without the
need for additional terminals - saving
component cost, time and panel space.
Quick and easy distribution of supply voltage
through the jumper link on the Bus-Bar (BB)
connection.
Ideal for interface applications between the
PLC’s or Controllers and output devices such
as electomagnetic valves or motors etc..
MasterTIMER
39.81 - 39.80 - 39.91 - 39.90
Slim and Multifunction Timed Interface
modules.
Output devices Output devices
PLC - Output PLC - Output
PLC - Input PLC - Input
Input devices Input devices
3
Fuse module
093.63
I-2015, www.findernet.com
B
Typical Applications 39
SERIES
39.11/39.01
Features
MasterBASIC - EMR
1 Pole interface module, 6.2mm wide,
ideal for PLC and electronic systems
Common connection possible with optional
jumper links (terminals A1, A2 and 11)
UL Listing (certain relay/socket combinations)
1 CO (SPDT)
6/10
250/400
1,500
300
0.185
6/0.2/0.12
500 (12/10)
AgNi
6 - 12 - 24 - 110...125
220...240
See page 16
(0.8...1.1)UN
0.6 UN
0.1 UN
(0.8...1.2)UN
10 · 106
60 · 103
5/6
6 (8 mm)
1,000
–40…+70
IP 20
6 A electromechanical relay
6 to 24 and 125 VAC/DC and 230 VAC
supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/Maximum switching voltage
Rated load AC1
Rated load AC15 (230 VAC)
Single phase motor rating (230 VAC)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
Standard contact material
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Holding voltage
Must drop-out voltage
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
Insulation between coil and contacts (1.2/50 µs)
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
For outline drawing see page 20, 21
39.11
Screw terminal
39.01
Push-in terminal
4
A
VAC
VA
VA
kW
A
mW (V/mA)
VAC/DC
VAC (50/60 Hz)
VA (50 Hz)/W
cycles
cycles
ms
kV
VAC
°C
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
5
39.10/39.00
Features
1 Pole interface module, 6.2mm wide,
ideal for PLC and electronic systems
Common connection possible with optional
jumper links (terminals A1, A2 and 13+)
UL Listing (certain relay/socket combinations)
0.1 or 2 A solid state relay
6 to 24 VDC, 125 V AC/DC and 230 VAC
supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
Output specification (SSR)
Contact configuration
Rated current/Maximum peak current (10 ms)
Rated voltage/Maximum blocking voltage
Switching voltage range
Repetitive peak off-state voltage
Minimum switching current
Max. “OFF-state” leakage current
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Must drop-out voltage
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
Approvals relay (according to type)
For outline drawing see page 20, 21
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
1 NO (SPST-NO)
2/20 DC 0.1/0.5 DC 2/40 AC
24/33 DC 48/60 DC 240/— AC
(1.5…24) DC (1.5…48) DC (12…275) AC
— 600
1 0.05 22
0.001 0.001 1.5
0.12 1 1.6
110...125
220...240
6 - 12 - 24
See page 17
(0.8…1.1) UN
0.1 UN
0.2/0.6 0.04/0.11 12/12
2,500
–20…+55
IP20
39.10
Screw terminal
39.00
Push-in terminal
MasterBASIC - SSR
A
V
V
Vpk
mA
mA
V
V AC/DC
VAC (50/60 Hz)
VDC
VA (50 Hz)/W
ms
VAC
°C
I-2015, www.findernet.com
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
39.31/39.61 39.31.3/39.61.3
6
Features
1 Pole interface modules, 6.2mm wide,
ideal for PLC and electronic systems
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 24
Common connection possible with optional
jumper links (terminals A1, A2 and 11)
UL Listing (certain relay/socket combinations) 6 A electromechanical relay
6 to 125 VAC/DC, 125 and 220 VDC,
230 VAC, 24...240 V AC/DC supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
6 A electromechanical relay
Leakage current suppression version,
125 V AC/DC and 230 VAC supply
Screw terminal and push-in terminal
For outline drawing see page 20, 21
1 CO (SPDT) 1 CO (SPDT)
6/10 6/10
250/400 250/400
1,500 1,500
300 300
0.185 0.185
6/0.2/0.12 6/0.2/0.12
500 (12/10) 500 (12/10)
AgNi AgNi
6 - 12 - 24 - 60 - 110…125 - 24...240 110…125
220...240 220…240
110…125 - 220
See page 16 See page 16
(0.8…1.1) UN (0.8…1.1) UN
0.6 UN 0.6 UN
0.1 UN 0.3 UN
10 · 106 10 · 106
60 · 103 60 · 103
5/6 5/6
6 (8 mm) 6 (8 mm)
1,000 1,000
–40…+70 (+55 for 220 VDC) –40…+70
IP20 IP20
39.31 / 39.31.3
Screw terminal
39.61 / 39.61.3
Push-in terminal
MasterPLUS - EMR
Fuse module
093.63
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/Maximum switching voltage
Rated load AC1
Rated load AC15 (230 VAC)
Single phase motor rating (230 VAC)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
Standard contact material
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Holding voltage
Must drop-out voltage
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
Insulation between coil and contacts (1.2/50 µs)
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
A
VAC
VA
VA
kW
A
mW (V/mA)
VAC/DC
VAC (50/60 Hz)
VDC
VA (50 Hz)/W
cycles
cycles
ms
kV
VAC
°C
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
7
39.30/39.60 39.30.3/39.60.3
Features
1 Pole interface modules, 6.2mm wide,
ideal for PLC and electronic systems
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 24
Common connection possible with optional
jumper links (terminals A1, A2 and 13+)
UL Listing (certain relay/socket combinations) 0.1 or 2 A solid state relay
24 - 125 VAC/DC, 6 to 220 VDC and
230 VAC, 24...240 V AC/DC supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
0.1 or 2 A solid state relay
Leakage current suppression version,
125 V AC/DC and 230 VAC supply
Screw terminal and push-in terminal
For outline drawing see page 20, 21
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240 39.x0.3.xxx.9024 39.x0.3.xxx.7048 39.x0.3.xxx.8240
1 NO (SPST-NO) 1 NO (SPST-NO)
2/20 DC 0.1/0.5 DC 2/40 AC 2/20 DC 0.1/0.5 DC 2/40 AC
24/33 DC 48/60 DC 240/— AC 24/33 DC 48/60 DC 240/— AC
(1.5…24) DC (1.5…48)DC (12…275) AC (1.5…24) DC (1.5…48)DC (12…275) AC
— 600 600
1 0.05 22 1 0.05 22
0.001 0.001 1.5 0.001 0.001 1.5
0.12 1 1.6 0.12 1 1.6
24 - 110…125 - 24...240 110…125
220...240 220…240
6 - 12 - 24 - 60 - 110…125 - 220
See page 17 See page 17
(0.8…1.1) UN (0.8…1.1) UN
0.1 UN 0.3 UN
0.2/0.6 0.04/0.11 12/12 0.2/0.6 0.04/0.11 12/12
2,500 2,500
–20…+55 –20…+55
IP20 IP20
39.30 / 39.30.3
Screw terminal
39.60 / 39.60.3
Push-in terminal
MasterPLUS - SSR
Fuse module
093.63
Output specification (SSR)
Contact configuration
Rated current/Maximum peak current (10 ms)
Rated voltage/Maximum blocking voltage
Switching voltage range
Repetitive peak off-state voltage
Minimum switching current
Max. “OFF-state” leakage current
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Must drop-out voltage
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
Approvals relay (according to type)
A
V
V
Vpk
mA
mA
V
VAC/DC
VAC (50/60 Hz)
VDC
VA (50 Hz)/W
ms
VAC
°C
I-2015, www.findernet.com
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
8
39.41/39.71
Features
1 Pole interface module, 6.2mm wide,
ideal for PLC and electronic systems
Jumper link option for the quick and easy
distribution of supply voltage to proximity
switches and similar input devices (Bus-bar
connection BB)
Gold plated output contact as standard, for
better compatibility with low energy PLC
inputs
UL Listing (certain relay/socket
combinations)
1
1 CO (SPDT)
6/10
250/400
1,500
300
0.185
6/0.2/0.12
50 (5/2)
AgNi + Au
6 - 12 - 24 - 110…125
220...240
See page 16
(0.8…1.1) UN
0.6 UN
0.1 UN
10 · 106
60 · 103
5/6
6 (8 mm)
1,000
–40…+70
IP20
6 A electromechanical relay
6 - 12 - 24 - 125 VAC/DC and 230 VAC
supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
For outline drawing see page 20, 21
39.41
Screw terminal
39.71
Push-in terminal
MasterINPUT - EMR
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/Maximum switching voltage
Rated load AC1
Rated load AC15 (230 VAC)
Single phase motor rating (230 VAC)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
Standard contact material
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Holding voltage
Must drop-out voltage
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
Insulation between coil and contacts (1.2/50 µs)
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
A
VAC
VA
VA
kW
A
mW (V/mA)
VAC/DC
VAC (50/60 Hz)
VA (50 Hz)/W
cycles
cycles
ms
kV
VAC
°C
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
9
39.40/39.70
Features
1 Pole interface modules, 6.2mm wide,
ideal for PLC and electronic systems
Jumper link option for the quick and easy
distribution of supply voltage to proximity
switches and similar input devices (Bus-bar
connection BB)
UL Listing (certain relay/socket
combinations) 0.1 or 2 A solid state relay
6 - 12 - 24 VDC, 24 - 125 VAC/DC and
230 VAC supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
For outline drawing see page 20, 21
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
1 NO (SPST-NO)
2/20 DC 0.1/0.5 DC 2/40 AC
24/33 DC 48/60 DC 240/— AC
(1.5…24) DC (1.5…48) DC (12…275) AC
600
1 0.05 22
0.001 0.001 1.5
0.12 1 1.6
24 - 110...125
220...240
6 - 12 - 24
See page 17
(0.8…1.1) UN
0.1 UN
0.2/0.6 0.04/0.11 12/12
2,500
–20…+55
IP20
39.40
Screw terminal
39.70
Push-in terminal
MasterINPUT - SSR
Output specification (SSR)
Contact configuration
Rated current/Maximum peak current (10 ms)
Rated voltage/Maximum blocking voltage
Switching voltage range
Repetitive peak off-state voltage
Minimum switching current
Max. “OFF-state” leakage current
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Must drop-out voltage
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
Approvals relay (according to type)
A
V
V
Vpk
mA
mA
V
VAC/DC
VAC (50/60 Hz)
VDC
VA (50 Hz)/W
ms
VAC
°C
I-2015, www.findernet.com
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
10
39.21/39.51
Features
1 Pole interface modules, 6.2mm wide,
ideal for PLC and electronic systems
Jumper link option for the quick and easy
distribution of supply voltage to output side
(Bus-bar connection BB) and its connection to
electromagnetic valves and similar output
devices
UL Listing (certain relay/socket combinations)
1
1 NO (SPST-NO)
6/10
250/400
1,500
300
0.185
6/0.2/0.12
500 (12/10)
AgNi
6 - 12 - 24 - 110…125
220...240
See page 16
(0.8…1.1) UN
0.6 UN
0.1 UN
10 · 106
60 · 103
5/6
6 (8 mm)
1,000
–40…+70
IP20
6 A electromechanical relay
6 - 12 - 24 - 125 VAC/DC and 230 V AC
supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
For outline drawing see page 20, 21
39.21
Screw terminal
39.51
Push-in terminal
MasterOUTPUT - EMR
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/Maximum switching voltage
Rated load AC1
Rated load AC15 (230 VAC)
Single phase motor rating (230 VAC)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
Standard contact material
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Holding voltage
Must drop-out voltage
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
Insulation between coil and contacts (1.2/50 µs)
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
A
VAC
VA
VA
kW
A
mW (V/mA)
VAC/DC
VAC (50/60 Hz)
VA (50 Hz)/W
cycles
cycles
ms
kV
VAC
°C
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
11
39.20/39.50
Features
1 Pole interface modules, 6.2mm wide,
ideal for PLC and electronic systems
Jumper link option for the quick and easy
distribution of supply voltage to output side
(Bus-bar connection BB) and its connection to
electromagnetic valves and similar output
devices
UL Listing (certain relay/socket combinations) 0.1 or 2 A solid state relay
6 to 24 VDC, 125 VAC/DC and 230 VAC
supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
For outline drawing see page 20, 21
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
1 NO (SPST-NO)
2/20 DC 0.1/0.5 DC 2/40 AC
24/33 DC 48/60 DC 240/— AC
(1.5…24) DC (1.5…48) DC (12…275) AC
— 600
1 0.05 22
0.001 0.001 1.5
0.12 1 1.6
110...125
220...240
6 - 12 - 24
See page 17
(0.8…1.1) UN
0.1 UN
0.2/0.6 0.04/0.11 12/12
2,500
–20…+55
IP20
39.20
Screw terminal
39.50
Push-in terminal
MasterOUTPUT - SSR
Output specification (SSR)
Contact configuration
Rated current/Maximum peak current (10 ms)
Rated voltage/Maximum blocking voltage
Switching voltage range
Repetitive peak off-state voltage
Minimum switching current
Max. “OFF-state” leakage current
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Must drop-out voltage
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
Approvals relay (according to type)
A
V
V
Vpk
mA
mA
V
VAC/DC
VAC (50/60 Hz)
VDC
VA (50 Hz)/W
ms
VAC
°C
I-2015, www.findernet.com
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
12
39.81/39.91
Features
Slim timed interface module, 6.2mm wide,
ideal for space-saving timing solutions in panels
Timer adjustment via top mounted rotary
knob, accessible after assembly
Control signal terminal
DIP-switch for selection of 4 time scales and
8 functions
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 24
Common connection possible with optional
jumper links (terminals A1, A2 and 15)
UL Listing (certain relay/socket combinations)
1 CO (SPDT)
6/10
250/400
1,500
300
0.185
6/0.2/0.12
500 (12/10)
AgNi
12 - 24
See page 16
(0.8…1.1) UN
0.6 UN
0.1 UN
(0.1...3)s, (3...60)s, (1...20)min, (0.3...6)h
± 1
≤ 50
50
5
60 · 103
–20...+50
IP20
6 A electromechanical relay
12 - 24 VAC/DC supply
Screw terminal and push-in terminal
35mm rail (EN 60715) mounting
For outline drawing see page 20, 21
AI: On-delay
DI: Interval
GI: Pulse (0.5 s) delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
EE: Interval with control signal off
39.81
Screw terminal
39.91
Push-in terminal
MasterTIMER - EMR
Fuse module
093.63
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/Maximum switching voltage
Rated load AC1
Rated load AC15 (230 VAC)
Single phase motor rating (230 VAC)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
Standard contact material
Supply specification
Nominal voltage (UN)
Rated power AC/DC
Operating range
Holding voltage
Must drop-out voltage
Technical data
Specified time range
Repeatability
Recovery time
Minimum control impulse
Setting accuracy – full range
Electrical life at rated load AC1
Ambient temperature range
Protection category
Approvals relay (according to type)
A
VAC
VA
VA
kW
A
mW (V/mA)
VAC/DC
VA (50 Hz)/W
%
ms
ms
%
cycles
°C
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
13
39.80/39.90
Features
Slim timed interface module, 6.2mm wide,
ideal for space-saving timing solutions in panels
Timer adjustment via top mounted rotary
knob; accessible after assembly
Start terminal
DIP-switch for selection of 4 time scales and
8 functions
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 24
Common connection possible with optional
jumper links (terminals A1, A2 and 15+)
UL Listing (certain relay/socket combinations)
0.1 or 2 A solid state relay
12 - 24 VAC/DC supply
Screw terminal and push-in terminal
35 mm rail (EN 60715) mounting
For outline drawing see page 20, 21
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
1 NO (SPST-NO)
2/20 DC 0.1/0.5 DC 2/40 AC
24/33 DC 48/60 DC 240/— AC
(1.5…24) DC (1.5…48) DC (12…275) AC
600
1 0.05 22
0.001 0.001 1.5
0.12 1 1.6
12 - 24
See page 17
(0.8…1.1) UN
0.6 UN
0.1 UN
(0.1...3)s, (3...60)s, (1...20)min, (0.3...6)h
± 1
≤ 50
50
5
–20...+50
IP20
AI: On-delay
DI: Interval
GI: Pulse (0.5 s) delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
EE: Interval with control signal off
39.80
Screw terminal
39.90
Push-in terminal
MasterTIMER - SSR
Fuse module
093.63
Output specification (SSR)
Contact configuration
Rated current/Maximum peak current (10 ms)
Rated voltage/Maximum blocking voltage
Switching voltage range
Repetitive peak off-state voltage
Minimum switching current
Max. “OFF-state” leakage current
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)
Rated power
Operating range
Holding voltage
Must drop-out voltage
Technical data
Specified time range
Repeatability
Recovery time
Minimum control impulse
Setting accuracy – full range
Ambient temperature range
Protection category
Approvals relay (according to type)
A
V
V
Vpk
mA
mA
V
VAC/DC
VA (50 Hz)/W
%
ms
ms
%
°C
I-2015, www.findernet.com
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
14
Example: MasterPLUS 39 series screw terminal interface module, electromechanical relay output, 1 CO (SPDT), 24 VAC/DC coil.
Series
Type
1 = MasterBASIC, screw terminal
0 = MasterBASIC, push-in terminal
3 = MasterPLUS, screw terminal,
fuse-protectable output
6 = MasterPLUS, push-in terminal,
fuse-protectable output
4 = MasterINPUT, screw terminal
7 = MasterINPUT, push-in terminal
2 = MasterOUTPUT, screw terminal
5 = MasterOUTPUT, push-in terminal
8 = MasterTIMER multifunction,
screw terminal,
fuse-protectable output
9 = MasterTIMER multifunction,
push-in terminal,
fuse-protectable output
No. of poles
1 = 1CO (only EMR, except 39.21/51, 1NO)
0 = 1NO (only SSR)
Coil version, EMR / Input version, SSR
0 = AC (50/60Hz)/DC
3 = Leakage current suppression AC(50/60Hz)
7 = DCsensitive
8 = AC(50/60Hz)
Coil voltage, EMR / Input voltage, SSR
See page16
3 1 0 0 0
D: Special Version, EMR
0 = Standard
C: Options, EMR
6 = Standard
B: Contact circuit, EMR
0 = CO (except 39.21/51, 1 NO)
A: Contact material, EMR
0 = AgNi Standard
4 = AgSnO2
5 = AgNi + Au
ABCD: Output version, SSR
7048 = 0.1A - 48VDC
8240 = 2A - 230VAC
9024 = 2A - 24VDC
6 0
Ordering information
A B C D
... .
3 9 0 2 4
EMR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
SSR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Coil version A B C D
39.11/01 0.006 - 0.012 0- 4 - 5 0 6 0
0.024 - 0.125 - 8.230
39.31/61
0.006 - 0.012
0- 4 - 5 0 6 0
0.024 - 0.060
0.125 - 0.240 - 8.230
7.125 - 7.220
3.125 - 3.230
39.41/71
0.006 - 0.012
0 - 4 - 50 6 00.024 - 0.125
8.230
39.21/51
0.006 - 0.012
0- 4 - 5 0 6 00.024 - 0.125
8.230
39.81/91 0.012 - 0.024 0 0 6 0
Type Input version Output version, ABCD
39.10/00 7.006 - 7.012 7048 - 8240 - 9024
7.024 - 0.125 - 8.230
39.30/60
7.006 - 7.012
7048 - 8240 - 9024
7.024 - 7.060
7.125 - 7.220
0.024 - 0.125 - 0.240
8.230
3.125 - 3.230
39.40/70
7.006 - 7.012
7048 - 8240 - 90247.024 - 0.024 - 0.125
8.230
39.20/50
7.006 - 7.012
7048 - 8240 - 90247.024 - 0.125
8.230
39.80/90 0.012 - 0.024 7048 - 8240 - 9024
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules - Ordering information
B
15
Technical data
Contact specification (EMR)
F 39 - Electrical life (AC) v contact current H 39 - Maximum DC1 breaking capacity
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of 60·103can be expected.
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Cycles
Resistive load - cosϕ= 1
Inductive load - cosϕ= 0.4
DC voltage (V)
DC breaking current (A)
Insulation according to EN 61810-1
Nominal voltage of supply system VAC 230/400
Rated insulation voltage VAC 250 400
Pollution degree 3 2
Insulation between coil and contact set
Type of Insulation Reinforced
Overvoltage category III
Rated impulse voltage kV (1.2/50) µs 6
Dielectric strength VAC 4,000
Insulation between open contacts (EMR)
Type of disconnection Micro-disconnection
Dielectric strength VAC/kV (1.2/50) µs 1,000/1.5
Conducted disturbance immunity UN≤ 60 V UN= 125 V UN= 230 V
Fast transients (burst 5/50 ns, 5 kHz) according to EN 61000-4-4
at supply terminals kV 4 4 4
Voltage pulses (surge 1.2/50 s) according to EN 61000-4-5 at
supply terminals (differential mode) kV 0.8 2 4
Other data
Bounce time (EMR) : NO/NC ms 1/6
Vibration resistance (EMR,10..55 Hz): NO/NC g10/15
Power lost to the environment without contact current W 0.2 (24 V) – 0.4 (230 V)
with rated current W 0.6 (24 V) – 0.9 (230 V)
I-2015, www.findernet.com
Terminals
Screw terminal Push-in terminal
Wire strip length mm 10 8
Screw torque Nm 0.5
Solid and stranded cable Solid and stranded cable
Max. wire size mm21 x 2.5/2 x 1.5 1 x 2.5
AWG 1 x 14/2 x 16 1 x 14
Min. wire size mm21 x 0.2 1 x 0.2
AWG 1 x 24 1 x 24
B
39 Series - Relay interface modules - Technical data 39
SERIES
Coil specifications - Electromechnical Relay
Coil data DC, type 39.31/61
Coil data AC/DC, type 39.11/21/31/41/01/51/61/71
Coil data AC, type 39.11/21/31/41/01/51/61/71
Coil data leakage current suppression versions, type 39.31.3/61.3
Coil data AC/DC timer, type 39.81/91
16
The 39 Series interface modules (supply version 3) have built-
in leakage current suppression to address industry concerns
of the contacts not dropping-out when there is residual current
in the circuit; at (110...125)VAC/DC and (230...240)VAC.
This problem can occur, for example, when connecting the
interface modules to PLC‚s with triac outputs or when
connecting via relatively long cables.
(1) 60 VAC/DC for type 39.31/61 only
(2) 24...240 V AC/DC for type 39.31/61 only
Nominal
Voltage Coil code Operating range Must drop-out
voltage
Rated input
current at UN
Rated power
UNUmin Umax UrINat UN
V V V V mA W
125
(110...125) 7.125 88 138 12.5 4.6 0.6
220 7.220 176 242 22 3.0 0.6
Nominal
Voltage Coil code Operating range Must drop-out
voltage
Rated input
current at UN
Rated power
UNUmin Umax UrINat UN
V V V V mA VA/W
60.006 4.8 6.6 0.6 35 0.2/0.2
12 0.012 9.6 13.2 1.5 15 0.2/0.2
24 0.024 19.2 26.4 2.4 11 0.25/0.25
60(1) 0.060 48 66 6.0 5.7 0.35/0.35
125
(110…125) 0.125 88 138 12.5 5.6 0.7/0.7
240
(24…240)(2) 0.240 20.4 264 2.4 19 1.5/0.3
Nominal
Voltage Coil code Operating range Must drop-out
voltage
Rated input
current at UN
Rated power
UNUmin Umax UrINat UN
V V V V mA VA/W
230
(230...240) 8.230 184 264 23 4.3 1/0.4
Nominal
Voltage Coil code Operating range Must drop-out
voltage
Rated input
current at UN
Rated power
UNUmin Umax UrINat UN
V V V V mA VA/W
125
(110...125) 3.125 88 138 44 8.4 1.1/1
230
(230...240) 3.230 184 264 72 5.9 1.4/0.5
Nominal
Voltage Coil code
Operating range
(AC/DC)
Must drop-out
voltage Rated input current at UNRated power at UN
UNUmin Umax UrDC AC DC AC
V V V V mA mA W VA/W
12 0.012 9.6 13.2 1.2 15 23 0.2 0.3/0.2
24 0.024 19.2 26.4 2.4 11 19 0.25 0.4/0.3
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules - Technical data
B
17
Input specifications - Solid State Relay
Input data DC, type 39.10/20/30/40/00/50/60/70
Input data AC/DC, type 39.10/20/30/40/00/50/60/70
Input data AC, type 39.10/20/30/40/00/50/60/70
Input data leakage current suppression versions, type 39.30.3/60.3
Input data AC/DC timer, type 39.80/90
The 39 Series interface modules (supply version 3) have built-
in leakage current suppression to address industry concerns
of the contacts not dropping-out when there is residual current
in the circuit; at (110...125)VAC/DC and (230...240)VAC.
This problem can occur, for example, when connecting the
interface modules to PLC‚s with triac outputs or when
connecting via relatively long cables.
(1) 60 V DC, 125 V DC and 220 V DC for type 39.30/60 only
(2) 24 VAC/DC for type 39.30/40/60/70 only
(3) 24...240 V AC/DC for type 39.30/60 only
Nominal
Voltage Input code Operating range Must drop-out
voltage
Rated input
current at UN
Rated
power
UNUmin Umax UrINat UN
V V V V mA W
67.006 4.8 6.6 0.6 7.5 0.2
12 7.012 9.6 13.2 1.2 20.7 0.25
24 7.024 19.2 26.4 2.4 10.5 0.25
60 (1) 7.060 48 66 6.0 6.4 0.4
125 (1)
(110...125) 7.125 88 138 12.5 4.6 0.6
220 (1) 7.220 176 242 22 3.0 0.6
Nominal
Voltage Input code Operating range Must drop-out
voltage
Rated input
current at UN
Rated
power
UNUmin Umax UrINat UN
V V V V mA VA/W
24 (2) 0.024 19.2 26.4 2.4 17.5 0.4/0.3
125
(110...125) 0.125 88 138 12.5 5.5 0.7/0.7
240
(24...240)(3) 0.240 20.4 264 2.4 17.5 1.5/0.3
Nominal
Voltage Input code Operating range Must drop-out
voltage
Rated input
current at UN
Rated
power
UNUmin Umax UrINat UN
V V V V mA VA/W
230
(230...240) 8.230 184 264 23 4.2 1/0.4
Nominal
Voltage Input code Operating range Must drop-out
voltage
Rated input
current at UN
Rated
power
UNUmin Umax UrINat UN
V V V V mA VA/W
125
(110...125) 3.125 88 138 44 8.4 1.1/1
230
(230...240) 3.230 184 264 72 5.9 1.4/0.5
Nominal
Voltage Input code
Operating range
(AC/DC)
Must drop-out
voltage Rated input current at UNRated power at UN
UNUmin Umax UrDC AC DC AC
V V V V mA mA W VA/W
12 0.012 9.6 13.2 1.2 15 23 0.2 0.3/0.2
24 0.024 19.2 26.4 2.4 11 19 0.25 0.4/0.3
I-2015, www.findernet.com
B
39 Series - Relay interface modules - Technical data 39
SERIES
18
Functions NO contact/output
Supply voltage
LED
OFF
ON
ON
ON
Times scales
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
(0.1...3)s (3...60)s (1...20)min (0.3...6)h
Timer specifications
Open
Open
Open (timing to close in progress)
Closed
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radio-frequency electromagnetic field (80 ÷ 1,000 MHz) EN 61000-4-3 10 V/m
(1,400 ÷ 2,700 MHz) EN 61000-4-3 10 V/m
Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals EN 61000-4-4 4 kV
on control signal terminals EN 61000-4-4 4 kV
Surges (1.2/50 s) on supply and control
signal terminals
common mode EN 61000-4-5 2 kV
differential mode EN 61000-4-5 0.8 kV
Radio-frequency common mode
(0.15 ÷ 80 MHz)
on Supply terminals EN 61000-4-6 10 V
on control signal terminals EN 61000-4-6 3 V
Radiated and conducted emission EN 55022 class B
Other data
Bounce time (EMR) : NO/NC ms 1/6
Vibration resistance (EMR,10..55 Hz): NO/NC g10/15
Power lost to the environment without contact current W 0.3
with rated current W 0.8
I-2015, www.findernet.com
Terminals
Screw terminal Push-in terminal
Wire strip length mm 10 8
Screw torque Nm 0.5
Solid and stranded cable Solid and stranded cable
Max. wire size mm21 x 2.5/2 x 1.5 1 x 2.5
AWG 1 x 14/2 x 16 1 x 14
Min. wire size mm21 x 0.2 1 x 0.2
AWG 1 x 24 1 x 24
39
SERIE S 39 Series - Timed interface modules
B
19
(AI) On-delay
Apply power to timer. Output contacts transfer after
preset time has elapsed. Reset occurs when power is
removed.
(DI) Interval
Apply power to timer. Output contacts transfer
immediately. After the preset time has elapsed, contacts
reset.
Wiring diagram
(GI) Pulse (0.5s) delayed
Apply power to timer. Output contacts transfer after
preset time has elapsed. Reset occurs after a fixed time
of 0.5s.
(SW) Symmetrical flasher (starting pulse on)
Apply power to timer. Output contacts transfer
immediately and cycle between ON and OFF for as
long as power is applied. The ratio is 1:1 (time on =
time off).
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
U = Supply voltage S= Signal switch = Output contact
(BE) Off-delay with control signal
Power is permenently applied to the timer. The
output contacts transfer immediately on closure of the
Signal Switch (S). Opening the Signal Switch
initiates the preset delay, after which time the output
contacts reset.
(DE) Interval with control signal on
Power is permenently applied to the timer. On momentary
or maintained closure of Signal Switch (S), the output
contacts transfer, and remain so for the duration of
the preset delay, after which they reset.
(EE) Interval with control signal off
Power is permenently applied to the timer. On opening
of the Signal Switch (S) the output contacts transfer,
and remain so for the duration of the preset delay,
after which they reset.
(CE) On- and off-delay with control signal
Power is permenently applied to the timer. Closing the
Signal Switch (S) initiates the preset delay, after which
time the output contacts transfer. Opening the Signal
switch initiates the same preset delay, after which time
the output contacts reset.
*With DC supply,
positive polarity has to
be conneted to B1,
terminal (according to
EN 60204-1).
With control signal
Without control signal
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
*
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 24 VAC
B1 - A2 = 12 VDC
I-2015, www.findernet.com
B
39 Series - Timed interface modules 39
SERIES
20
Outline drawings - Screw terminal sockets
39.10 / 39.20
39.11 / 39.21
Screw terminal
39.30 / 39.30.3
39.31 / 39.31.3
Screw terminal
39.40
39.41
Screw terminal
39.80
39.81
Screw terminal
I-2015, www.findernet.com
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
21
I-2015, www.findernet.com
Outline drawings - Push-in terminal sockets
39.00 / 39.01
39.50 / 39.51
Push-in terminal
39.60 / 39.60.3
39.61 / 39.61.3
Push-in terminal
39.70
39.71
Push-in terminal
39.90
39.91
Push-in terminal
Main features
Push-in terminals
The push-in terminals permit the quick connection of solid wires or ferrules by their simple insertion into the terminal (A).
It is possible to open the terminal to extract the wire by first pushing down on the push-button using a screwdriver (C).
For stranded cable it is necessary first to open the terminal using the push button, both for the extraction (C) and insertion (B).
It is possible at any time to check the connection via the test aperture, using a 2mm diameter test probe (D).
ABCD
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
22
I-2015, www.findernet.com
Interface Module Code Coil voltage Relay Socket
MasterBASIC
39.11.0.006.0060 6 VAC/DC 34.51.7.005.0010 93.61.7.024
39.11.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.61.7.024
39.11.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.61.7.024
39.11.0.125.0060 (110...125)V AC/DC 34.51.7.060.0010 93.61.0.125
39.11.8.230.0060 (230...240)VAC 34.51.7.060.0010 93.61.8.230
MasterPLUS
39.31.0.006.0060 6 VAC/DC 34.51.7.005.0010 93.63.7.024
39.31.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.63.7.024
39.31.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.63.7.024
39.31.0.060.0060 60 VAC/DC 34.51.7.060.0010 93.63.7.060
39.31.0.125.0060 (110...125)VAC/DC 34.51.7.060.0010 93.63.0.125
39.31.0.240.0060 (24...240)V AC/DC 34.51.7.024.0010 93.63.0.240
39.31.8.230.0060 (230...240)VAC 34.51.7.060.0010 93.63.8.230
39.31.7.125.0060 (110...125)VDC 34.51.7.060.0010 93.63.7.125
39.31.7.220.0060 220 VDC 34.51.7.060.0010 93.63.7.220
39.31.3.125.0060 (110...125)VAC/DC 34.51.7.060.0010 93.63.3.125
39.31.3.230.0060 (230...240)VAC 34.51.7.060.0010 93.63.3.230
MasterINPUT
39.41.0.006.5060 6 VAC/DC 34.51.7.005.5010 93.64.7.024
39.41.0.012.5060 12 VAC/DC 34.51.7.012.5010 93.64.7.024
39.41.0.024.5060 24 VAC/DC 34.51.7.024.5010 93.64.7.024
39.41.0.125.5060 (110…125) VAC/DC 34.51.7.060.5010 93.64.0.125
39.41.8.230.5060 (230...240)VAC 34.51.7.060.5010 93.64.8.230
MasterOUTPUT 1 NO, 6 A only
39.21.0.006.0060 6 VAC/DC 34.51.7.005.0010 93.62.7.024
39.21.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.62.7.024
39.21.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.62.7.024
39.21.0.125.0060 (110…125) VAC/DC 34.51.7.060.0010 93.62.0.125
39.21.8.230.0060 (230...240)VAC 34.51.7.060.0010 93.62.8.230
MasterTIMER
39.81.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.68.0.024
39.81.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.68.0.024
Electromechanical Relay (1 Pole 6 A) & Screw Socket Combinations
Interface Module Code Input voltage Relay Socket
MasterBASIC
39.10.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.61.7.024
39.10.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.61.7.024
39.10.7.024.xxxx 24 VDC 34.81.7.024.xxxx 93.61.7.024
39.10.0.125.xxxx (110...125)V AC/DC 34.81.7.060.xxxx 93.61.0.125
39.10.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.61.8.230
MasterPLUS
39.30.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.63.7.024
39.30.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.63.7.024
39.30.7.024.xxxx 24 VDC 34.81.7.024.xxxx 93.63.7.024
39.30.7.060.xxxx 60 VDC 34.81.7.060.xxxx 93.63.7.060
39.30.7.125.xxxx (110...125)VDC 34.81.7.060.xxxx 93.63.7.125
39.30.7.220.xxxx 220 VDC 34.81.7.060.xxxx 93.63.7.220
39.30.0.024.xxxx 24 VAC/DC 34.81.7.024.xxxx 93.63.0.024
39.30.0.125.xxxx (110...125)VAC/DC 34.81.7.060.xxxx 93.63.0.125
39.30.0.240.xxxx (24...240)V AC/DC 34.81.7.024.xxxx 93.63.0.240
39.30.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.63.8.230
39.30.3.125.xxxx (110...125)VAC/DC 34.81.7.060.xxxx 93.63.3.125
39.30.3.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.63.3.230
MasterINPUT
39.40.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.64.7.024
39.40.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.64.7.024
39.40.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.64.7.024
39.40.0.024.xxxx 24 VAC/DC 34.81.7.024.xxxx 93.64.0.024
39.40.0.125.xxxx (110…125) VAC/DC 34.81.7.060.xxxx 93.64.0.125
39.40.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.64.8.230
MasterOUTPUT
39.20.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.62.7.024
39.20.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.62.7.024
39.20.7.024.xxxx 24 VDC 34.81.7.024.xxxx 93.62.7.024
39.20.0.125.xxxx (110…125) VAC/DC 34.81.7.060.xxxx 93.62.0.125
39.20.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.62.8.230
MasterTIMER
39.80.0.012.xxxx 12 VAC/DC 34.81.7.012.xxxx 93.68.0.024
39.80.0.024.xxxx 24 VAC/DC 34.81.7.024.xxxx 93.68.0.024
Solid State Relay (1 Pole 0.1 or 2 A) & Screw Socket Combinations
Example: .xxxx
.9024
.7048
.8240
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
23
I-2015, www.findernet.com
Interface Module Code Coil voltage Relay Socket
MasterBASIC
39.01.0.006.0060 6 VAC/DC 34.51.7.005.0010 93.60.7.024
39.01.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.60.7.024
39.01.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.60.7.024
39.01.0.125.0060 (110...125)V AC/DC 34.51.7.060.0010 93.60.0.125
39.01.8.230.0060 (230...240)VAC 34.51.7.060.0010 93.60.8.230
MasterPLUS
39.61.0.006.0060 6 VAC/DC 34.51.7.005.0010 93.66.7.024
39.61.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.66.7.024
39.61.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.66.7.024
39.61.0.060.0060 60 VAC/DC 34.51.7.060.0010 93.66.7.060
39.61.0.125.0060 (110...125)VAC/DC 34.51.7.060.0010 93.66.0.125
39.61.0.240.0060 (24...240) V AC/DC 34.51.7.024.0010 93.66.0.240
39.61.8.230.0060 (230...240)VAC 34.51.7.060.0010 93.66.8.230
39.61.7.125.0060 (110...125)VDC 34.51.7.060.0010 93.66.7.125
39.61.7.220.0060 220 VDC 34.51.7.060.0010 93.66.7.220
39.61.3.125.0060 (110...125)VAC/DC 34.51.7.060.0010 93.66.3.125
39.61.3.230.0060 (230...240)VAC 34.51.7.060.0010 93.66.3.230
MasterINPUT
39.71.0.006.5060 6 VAC/DC 34.51.7.005.5010 93.67.7.024
39.71.0.012.5060 12 VAC/DC 34.51.7.012.5010 93.67.7.024
39.71.0.024.5060 24 VAC/DC 34.51.7.024.5010 93.67.7.024
39.71.0.125.5060 (110…125) VAC/DC 34.51.7.060.5010 93.67.0.125
39.71.8.230.5060 (230...240)VAC 34.51.7.060.5010 93.67.8.230
MasterOUTPUT 1 NO, 6 A only
39.51.0.006.0060 6 VAC/DC 34.51.7.005.0010 93.65.7.024
39.51.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.65.7.024
39.51.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.65.7.024
39.51.0.125.0060 (110…125) VAC/DC 34.51.7.060.0010 93.65.0.125
39.51.8.230.0060 (230...240)VAC 34.51.7.060.0010 93.65.8.230
MasterTIMER
39.91.0.012.0060 12 VAC/DC 34.51.7.012.0010 93.69.0.024
39.91.0.024.0060 24 VAC/DC 34.51.7.024.0010 93.69.0.024
Electromechanical Relay (1 Pole 6 A) & Push-in Socket Combinations
Interface Module Code Input voltage Relay Socket
MasterBASIC
39.00.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.60.7.024
39.00.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.60.7.024
39.00.7.024.xxxx 24 VDC 34.81.7.024.xxxx 93.60.7.024
39.00.0.125.xxxx (110...125)V AC/DC 34.81.7.060.xxxx 93.60.0.125
39.00.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.60.8.230
MasterPLUS
39.60.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.66.7.024
39.60.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.66.7.024
39.60.7.024.xxxx 24 VDC 34.81.7.024.xxxx 93.66.7.024
39.60.7.060.xxxx 60 VDC 34.81.7.060.xxxx 93.66.7.060
39.60.7.125.xxxx (110...125)VDC 34.81.7.060.xxxx 93.66.7.125
39.60.7.220.xxxx 220 VDC 34.81.7.060.xxxx 93.66.7.220
39.60.0.024.xxxx 24 VAC/DC 34.81.7.024.xxxx 93.66.0.024
39.60.0.125.xxxx (110...125)VAC/DC 34.81.7.060.xxxx 93.66.0.125
39.60.0.240.xxxx (24...240)V AC/DC 34.81.7.024.xxxx 93.66.0.240
39.60.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.66.8.230
39.60.3.125.xxxx (110...125)VAC/DC 34.81.7.060.xxxx 93.66.3.125
39.60.3.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.66.3.230
MasterINPUT
39.70.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.67.7.024
39.70.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.67.7.024
39.70.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.67.7.024
39.70.0.024.xxxx 24 VAC/DC 34.81.7.024.xxxx 93.67.0.024
39.70.0.125.xxxx (110…125) VAC/DC 34.81.7.060.xxxx 93.67.0.125
39.70.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.67.8.230
MasterOUTPUT
39.50.7.006.xxxx 6 VDC 34.81.7.005.xxxx 93.65.7.024
39.50.7.012.xxxx 12 VDC 34.81.7.012.xxxx 93.65.7.024
39.50.7.024.xxxx 24 VDC 34.81.7.024.xxxx 93.65.7.024
39.50.0.125.xxxx (110…125) VAC/DC 34.81.7.060.xxxx 93.65.0.125
39.50.8.230.xxxx (230...240)VAC 34.81.7.060.xxxx 93.65.8.230
MasterTIMER
39.90.0.012.xxxx 12 VAC/DC 34.81.7.012.xxxx 93.69.0.024
39.90.0.024.xxxx 24 VAC/DC 34.81.7.024.xxxx 93.69.0.024
Solid State Relay (1 Pole 0.1 or 2 A) & Push-in Socket Combinations
Example: .xxxx
.9024
.7048
.8240
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
24
I-2015, www.findernet.com
Output fuse module for 39.31/30/81/80/61/60/91/90 types 093.63
- For 5 x 20 mm fuses up to 6 A, 250 V
- Easy visibility of the fuse condition through the window
- Quick connection to socket
Notes
Safety: Because the output circuit can be reinstated (point 3 below), even with the fuse removed, it is important not to
consider the removal of the fuse as a “safety disconnect”. Always isolate elsewhere before working on the circuit.
UL: According to UL508A, the fuse module cannot be installed in power circuits (in which it is mandatory that a fuse
certified according to UL category JDDZ be fitted). However, where the MasterInterface is connected as an output
interface to a PLC no such restrictions apply, and the fuse module can be usefully employed.
Multi-state fuse module
0. As delivered, the socket comes without a fuse module. However, the absent fuse is internally replaced with an electrical
link - which allows the interface relay to be used without a fuse module.
In this state, the peg/indicator is visually hidden and the connection is protected by a special cap.
093.63
Accessories
3. In order toreinstate the output circuit itisnecessary toeither re-insert the fuse module (complete with functional fuse),
or alternatively, return the peg/indicator to position 0by gently applying pressure in the direction of the arrow.
2. Ifthe fuse module is extracted (for example; because the fuse element has blown) the output circuitwill belocked open,
as this will generally be the “safe option”.
This state is indicated by the peg/indicator.
1. With fuse module inserted after removing the cap, the fuse is positioned electrically in series with the common output
terminal of the interface module (11 for EMR versions, 13+ for SSR versions, 15 for EMR timer, 15+ for SSR timer).
This state is indicated by the peg/indicator.
Approvals
(according to type):
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A
B
25
Accessories
Sheet of marker tags, plastic, 72 tags, 6x12 mm 060.72
060.72
093.62
Dual-purpose plastic separator (1.8 mm or 6.2 mm separation) 093.60
1. By breaking off the protruding ribs (by hand), the separator becomes only 1.8 mm thick; useful for the visual separation
of different groups of interfaces, or necessary for the protective separation of different voltages of neighbouring
interfaces, or for the protection of cut ends of jumper links.
093.60
2. Leaving the ribs in place provides 6.2mm separation. Simply cutting (with scissors) the relevant segment(s) permits the
interconnection across the separator of 2 different groups of interface relays, using the standard jumper link.
16-way jumper link 093.16 (blue) 093.16.0 (black) 093.16.1 (red)
Rated values 6 A - 250 V
Possibility of multiple connection, side by side
093.16
093.16.0
093.16.1
Approvals
(according to type):
I-2015, www.findernet.com
B
39 Series - Relay interface modules 0.1 - 2 - 6 A 39
SERIES
Terminal doubler (for socket Push-in only) 093.62
Total load 6 A - 300 V
Solid and stranded cable
Max. wire size mm2 2 x 1.5
AWG 2 x 16
Accessories
MasterADAPTER 093.68.14.1
The MasterADAPTER permits the easy connection of A1/A2 terminals of up to MasterINTERFACE modules to PLC outputs
via a 14-Pole ribbon cable, plus simple 2-wire power supply connection.
Technical data
Rated current (per signal path) A 1
Minimum required supply power W 3
Nominal voltage (UN) VDC 24
Operating range (0.8...1.1) UN
Control logic
Positive switching (to A1)
Power supply status indication Green LED
Ambient temperature range °C –40…+70
Terminals for 24 V control logic
Type of connector 14 pole, according to IEC 60603-13
Terminals for 24 V power supply
Wire strip length mm 9.5
Screw torque Nm 0.5
Max. wire size
solid wire mm2 1 x 4/2 x 1.5
AWG 1 x 12/2 x 16
stranded wire mm2 1 x 2.5/2 x 1.5
AWG 1 x 14/2 x 16
093.68.14.1
Connected MasterADAPTER
Wiring diagram
Approvals
(according to type):
I-2015, www.findernet.com
26
39
SERIE S 39 Series - Relay interface modules 0.1 - 2 - 6 A