ACDC 150500 Watts LCL Series xppower.com * Single Output Industrial Supplies * High Efficiency * Low Cost * 150 W Convection Cooled * 300 W & 500 W with Internal Fans * Outputs from 12 V to 48 V * 3 Year Warranty Specification Input General * 85-264 VAC (127-370 VDC) (see note 1) * 47-63 Hz * 2.1 A max for LCL150, 4.5 A max for LCL300, 6.6 A max for LCL500 Inrush Current * 40 A max for LCL150, 60 A max for LCL300 & 500 cold start at 25 C, 230 VAC Power Factor * >0.9 Earth Leakage Current * <2 mA at 264 VAC, 60 Hz Input Protection * LCL150: T3.15 A/250 V, LCL300: T6.3A/250 V, LCL500: T10A/250 V, internal fuse fitted in line Input Voltage Input Frequency Input Current Efficiency Isolation Switching Frequency Power Density MTBF * 88% typical at full load & 230 VAC * 3000 VAC Input to Output 1500 VAC Input to Ground 500 VAC Output to Ground * 90-110 kHz main converter & 45-190 kHz PFC for LCL150, 80-190 kHz main converter & 62-65 kHz PFC for LCL300 & 500 * 2.7 W/in3 LCL150, 4.4 W/in3 LCL300, 4.9 W/in3 LCL500 * LCL150: >489 kHrs, LCL300: >235 kHrs, LCL500: >211 kHrs to MIL-HBK-217F at 25 C, GB Environmental Output Output Voltage Output Voltage Trim Initial Set Accuracy Minimum Load Start Up Delay * * * * * Start Up Rise Time * Hold Up Time Line Regulation * * Load Regulation Transient Response * * Ripple & Noise Overvoltage Protection Overtemperature Protection Overload Protection * * * * Short Circuit Protection * Remote Sense * Remote On/Off * See tables See tables 100 mV at 50% load None required 2 s max for LCL150, 1.5 s max for LCL300, 0.8 s max for LCL500 50 ms max for LCL150, 35 ms max for LCL300 & LCL500 10 ms min at 115 VAC and full load 0.5% max for LCL150, 0.3% for LCL300 & LCL500 1% max 4% max deviation recovery to within 1% in 500 s for a 50% load change See tables 110-140%, recycle input to reset Output turns off when OTP triggered, measured internally, auto recovery 110-150% of rated output power. Delayed by 1 s min to allow for peak loads. Trip and restart (hiccup mode), auto recovery Fitted to LCL500 only, compensates for 0.25 V max each line Fitted on LCL500 only, On = logic low or open circuit, Off = logic high Operating Temperature * -10 C to +70 C, derate from 100% load at 50 C to 50% load at 70 C Cooling * LCL150 convection cooled, LCL300 & LCL500 have internal fans Operating Humidity * 5% to 90% non condensing Storage Temperature * -40 C to +85 C Operating Altitude * 3000 m Vibration * 10-500 Hz, 2 g, 10 mins per cycle on 3 axes EMC & Safety Emissions Harmonic Currents Voltage Flicker ESD Immunity Radiated Immunity EFT/Burst Surge Conducted Immunity Magnetic Field Dips & Interruptions Safety Approvals * EN55022 level B conducted, level A radiated * EN61000-3-2 class A LCL150: EN61000-3-2 class C for loads 40% LCL300 & LCL500: EN61000-3-2 class C for loads 20% * EN61000-3-3 * EN61000-4-2, 4 kV contact, 8 kV air discharge, Performance Criteria A * EN61000-4-3, level 2 Perf Criteria A * EN61000-4-4, level 2 Perf Criteria A * EN61000-4-5, installation class 3, Perf Criteria A * EN61000-4-6, level 2 Perf Criteria A * EN61000-4-8, 1 A/m Perf Criteria A * EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms, Perf Criteria A, B, B * EN60950-1, UL60950-1, CSA60950 No 22.2 Output Power(1) Output Voltage 12.0 V 13.5 V 15.0 V 24.0 V 27.0 V 48.0 V 150 W Trim Range 11.0-13.0 V 12.5-14.5 V 14.0-16.0 V 23.0-25.0 V 26.0-28.0 V 47.0-49.0 V Output Current 12.5 A 11.1 A 10.0 A 6.3 A 5.6 A 3.1 A Ripple & Noise(2) 100 mV pk-pk 100 mV pk-pk 100 mV pk-pk 150 mV pk-pk 150 mV pk-pk 250 mV pk-pk Model Number LCL150PS12 LCL150PS13 LCL150PS15 LCL150PS24 LCL150PS27 LCL150PS48 Notes 1. Output power derates linearly from 100% at 90 VAC to 90% at 85 VAC. 2. Measured with 20 MHz bandwidth. Mechanical Details 1.02 (26.0) 1.97 (50.0) 0.90 (23.0) 0.57 (14.5) 4.64 (118.0) 4 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration Terminal Block, M4 Screw 7 pins 0.37 (9.5) centre 2.44 (62.0) 1 3.74 (95.0) 2.83 (72.0) 2 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration 7 J1 7.55 (192.0) 1.02 (26.0) 4.64 (118.0) 4 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration 0.57 (14.5) 0.90 (23.0) Notes 3. Tolerance is 0.05 (0.2) maximum. 100 100 80 90 60 40 20 -10 Function +Vout +Vout -Vout -Vout Ground Neutral Line Output Power (%) Output Power (%) 1. All dimensions shown in inches (mm). 2. Weight: 1.39 lbs (630 g) approx. Pin 1 2 3 4 5 6 7 0 10 20 30 40 50 Ambient Temperature (C) 60 70 85 90 100 110 120 230 Input Voltage (VAC) 240 250 264 ACDC LCL150 Model and Ratings Output Power(1) Output Voltage 12.0 V 13.5 V 15.0 V 24.0 V 27.0 V 48.0 V 300 W 310 W 315 W 320 W Trim Range 11.0-13.0 V 12.5-14.5 V 14.0-16.0 V 23.0-25.0 V 26.0-28.0 V 47.0-49.0 V Output Current 25.0 A 22.0 A 20.0 A 13.0 A 11.7 A 6.70 A Ripple & Noise(2) 150 mV pk-pk 150 mV pk-pk 150 mV pk-pk 150 mV pk-pk 200 mV pk-pk 240 mV pk-pk Model Number LCL300PS12 LCL300PS13 LCL300PS15 LCL300PS24 LCL300PS27 LCL300PS48 Notes 1. Output power derates linearly from 100% at 90 VAC to 90% at 85 VAC. 2. Measured with 20 MHz bandwidth. Mechanical Details 8.07 (205.0) 3 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration 1.97 (50.0) 0.94 (24.0) 0.63 (16.0) Terminal Block, M4 Screw 9 pins 0.37 (9.5) centre 4 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration 1 4.33 (110.0) 1.97 (50.0) 9 J1 0.63 7.44 (189.0) (16.0) 3 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration 6.81 (173.0) 0.98 (25.0) 0.50 (12.5) 1.97 (50.0) 6.81 (173.0) Notes 1. All dimensions shown in inches (mm 2. Weight: 1.94 lbs (880 g) approx. 3. Tolerance is 0.05 (0.2) maximum. 4. Airflow direction is out of the unit at fan. Pin 1 2 3 4 5 6 7 8 9 J1 Pin Connections Function +Vout +Vout +Vout -Vout -Vout -Vout Ground Neutral Line Derating Curves 100 80 90 Output Power (%) 100 Output Power (%) ACDC LCL300 Model and Ratings 60 40 20 -10 0 10 20 30 40 50 Ambient Temperature (C) 60 70 85 90 100 110 120 230 Input Voltage (VAC) 240 250 264 Output Power(1) Output Voltage 12.0 V 13.5 V 15.0 V 24.0 V 27.0 V 48.0 V 500 W Trim Range 11.0-13.0 V 12.5-14.5 V 14.0-16.0 V 23.0-25.0 V 26.0-28.0 V 47.0-49.0 V Output Current 42.0 A 37.0 A 34.0 A 21.0 A 18.5 A 10.5 A Ripple & Noise(2) 120 mV pk-pk 150 mV pk-pk 150 mV pk-pk 150 mV pk-pk 150 mV pk-pk 240 mV pk-pk Model Number LCL500PS12 LCL500PS13 LCL500PS15 LCL500PS24 LCL500PS27 LCL500PS48 Notes 1. Output power derates linearly from 100% at 90 VAC to 90% at 85 VAC. 2. Measured with 20 MHz bandwidth. Mechanical Details 4 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration 1.41 (36.0) 1.00 (25.5) 2.08 (53.0) 0.60 (15.0) 4 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration Terminal Block, M4 Screw 9 pins 0.37 (9.5) centre 1 J2 4 AIRFLOW 1 3.54 (90.0) 5.00 (127.0) 9 9.21 (234.0) J1 1.41 (36.0) 7.75 (197.0) 9.84 (250.0) 1.41 (0.36) 0.60 (15.0) 7.75 (197.0) Notes 1.Dimensions shown in inches (mm). 2. Weight: 3.2 lbs (1.45 kg) approx. Pin 1 2 1.00 (25.5) 3 4 4 x M4 x 0.7 THD 0.15 (3.8) Max Screw Penetration 5 6 7 8 9 3. Tolerance is 0.05 (0.2) maximum. J1 Pin Connections Function +Vout +Vout +Vout -Vout -Vout -Vout Ground Neutral Line Pin 1 2 3 4 J2 Pin Connections Function Remote On/Off Remote On/Off + Sense Sense + Applying >4.5 V to Pin 2 with respect to Pin 1 turns output off. Applying <0.8 V to Pin 2 with respect to Pin 1 or open circuit turns output on. Mating Connectors (J2): WST P4-I25002 housing WST I25002BS contacts 100 100 80 90 Output Power (%) Output Power (%) Derating Curves 60 40 20 -10 0 10 20 30 40 50 Ambient Temperature (C) 60 70 85 90 100 110 120 230 Input Voltage (VAC) 240 250 264 03-July-14 ACDC LCL500 Model and Ratings