https://www.phoenixcontact.com/us/products/2801256
09/10/2014Page2/5
Surge protection device-PT-IQ-1X2+F-24DC-PT-2801256
Technical data
General
Type DIN rail module, two-section, divisible
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN4 V DC
Maximum continuous operating voltage UC30 V DC
21 V AC
Nominal current IN1000 mA (up to 40 °C)
Operating effective current IC at UC≤ 1 mA (per system)
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (Core-Core) 10 kA
Nominal discharge current In (8/20) µs (Core-Earth) 10 kA
Impulse discharge current (10/350)˽µs, peak value limp 2.5 kA
Voltage protection level UP (Core-Core) ≤ 80 V (C1 - 1 kV/500 A)
≤ 130 V (C2 - 10 kV / 5 kA)
≤ 55 V (C3 - 25 A)
Voltage protection level UP (Core-Earth) ≤ 900 V (C1 - 1 kV/500 A)
≤ 1300 V (C2 - 10 kV / 5 kA)
≤ 1000 V (C3 - 25 A)
Voltage protection level UP (Core-GND) ≤ 600 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
Voltage protection level UP static (core-core) ≤ 65 V (C1 - 1 kV/500 A)
Voltage protection level UP static (core-ground) ≤ 130 V (C2 - 10 kV / 5 kA)
≤ 60 V (C3 - 25 A)
Voltage protection level UP static (core-GND) ≤ 60 V (C2 - 10 kV / 5 kA)
≤ 40 V (C3 - 25 A)
Response time tA (Core-Core) ≤ 1 ns
Response time tA (Core-Earth) ≤ 100 ns
≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 270 kHz/150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system typ. 1.1 MHz