DENSEI-LAMBDA
HWS50/ME
SPECIFICATIONS
A226-01-01/ME
MODEL
ITEMS
1
Nominal Output Voltage
2
Maximum Output Current
3
Maximum Output Power
W
4
Efficiency (Typ) (*1)
100VAC
%
200VAC
%
5
Input Voltage Range
(*2)
-
85 - 265VAC (47 - 63Hz) or 120 - 370VDC
6
Input Current (100/200VAC)(Typ) (*1)
0.7/0.35
7
Inrush Current(Typ)
(*3)
-
14A at 100VAC, 28A at 200VAC, Ta=25°C, Cold Start
8
PFHC
-
Designed to meet IEC61000-3-2
9
Voltage Fluctuations / Flicker Emissions
-
Designed to meet IEC61000-3-3
10
Power Factor (100/200VAC)(Typ) (*1)
-
11
Output Voltage Range
12
Maximum Ripple & Noise
0<Ta<70°C
mV
(*4)
-10<Ta<0°C
mV
13
Maximum Line Regulation
(*5)
mV
14
Maximum Load Regulation
(*6)
mV
15
Temperature Coefficient
-
Less than 0.02% / °C
16
Over Current Protection
(*7)
17
Over Voltage Protection
(*8)
18
Hold-up Time (Typ)
(*9)
-
20ms
19
Leakage Current
(*10)
-
Less than 0.5mA. 0.2mA(Typ) at 100VAC / 0.4mA(Typ) at 230VAC
20
Remote Sensing
-
-
21
Parallel Operation
-
-
22
Series Operation
-
Possible
23
Operating Temperature
(*11)
-
-10 to +70°C (-10 to +50°C:100%,+60°C:60%,+70°C:20%)
24
Operating Humidity
-
30 to 90%RH (No dewdrop)
25
Storage Temperature
-
-30 to +85°C
26
Storage Humidity
-
10 to 95%RH (No dewdrop)
27
Cooling
-
Convection cooling
28
Withstand Voltage
-
Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA)
Output - FG : 500VAC (100mA) for 1min
29
Isolation Resistance
-
More than 100M
at 25°C and 70%RH Output - FG : 500VDC
30
Vibration
-
At no operating, 10 - 55Hz (Sweep for 1min)
19.6m/s
2
Constant, X,Y,Z 1hour each.
31
Shock (In package)
-
Less than 196.1m/s
2
32
Safety
(*12)
-
Approved by UL60601-1, EN60601-1, CSA-C22.2 No.601.1-M90
33
Line DIP
-
Designed to meet SEMI-F47 (200VAC Line only)
34
Conducted Emission
-
Designed to meet EN55011/EN55022-B, FCC-B, VCCI-B
35
Radiated Emission
-
Designed to meet EN55011/EN55022-B, FCC-B, VCCI-B
36
Immunity
-
Designed to meet IEC61000-4-2(Level 3), -3(Level 3), -4(Level 3),
-5(Level 3,4), -6(Level 3), -8(Level 4), -11
37
Weight(Typ.)
-
280g
38
Size (W x H x D)
mm
26.5 x 82 x 120 ( Refer to Outline Drawing )
*Read instruction manual carefully, before using the power supply unit.
=NOTES=
*1.
At 100/200VAC, Ta=25°C and maximum output power.
*2.
For cases where conformance to various safety specs (UL, EN, CSA) are required,
to be described as 100 - 230VAC(50/60Hz).
*3.
Not applicable for the in-rush current to Noise Filter for less than 0.2ms.
*4.
Measure with JEITA RC-9131A probe, Bandwidth of scope :100MHz.
*5.
85 - 265VAC , constant load.
*6.
No load-Full load, constant input voltage.
*7.
Constant current limit and Hiccup with automatic recovery.
Not operate at over load or dead short condition for more than 30seconds.
*8.
OVP circuit will shutdown output, manual reset (Re power on).
*9.
At 100/200VAC , nominal output voltage and maximum output current.
*10.
Measured by the each measuring method of UL,EN and CSA(at 60Hz).
When using it as a patient care equipment, all outer surfaces of the equipment shall be constructed of
nonconductive material. See clause 19.5DV.2 of UL60601-1.
*11.
Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
- As for other mountings, refer to derating curve (A226-01-02_).
*12.
As for UL60601-1, EN60601-1 and CSA-C22.2 No.601.1-M90, basic insulation.
83
84
85
50
82
52.8
82
51.6
81
84
83
5
10
HWS50
-5/ME
4.3
HWS50
-12/ME
12
HWS50
-15/ME
15
3.5
52.5
81
52.8
83
HWS50
-24/ME
HWS50
-48/ME
48
1.1
24
2.2
40
9.6 - 14.4
150
0.99/0.95
4.0 - 6.0
120
160
20
180
96
96
12.0 - 18.0
150
180
60
120
180
48
10.5
<
6.25 - 7.25
192
38.4 - 52.8
200
240
192
384
19.2 - 28.8
150
4.51
<
15.0 - 17.4
3.67
<
18.8 - 21.8
2.31
<
30.0 - 34.8
1.15
<
55.2 - 64.8