POWR-GARD® Fuse Datasheet
© 2013 Littelfuse POWR-GARD® ProductsLittelfuse.com
Rev: 040913
2 of 3
30 A 60 A 100 A 200 A 400 A 600 A
5,000 1,060 1,600 2,100 2,600 4,100 --
10,000 1,350 2,000 2,800 3,400 5,250 8,000
15,000 1,600 2,300 3,200 3,900 6,000 9,000
20,000 1,700 2,600 3,600 4,500 6,700 10,000
25,000 1,900 2,800 3,800 4,800 7,500 11,000
30,000 2,000 3,000 4,100 5,200 8,000 12,000
35,000 2,100 3,100 4,400 5,700 8,500 12,500
40,000 2,200 3,300 4,600 6,000 9,000 13,000
50,000 2,400 3,500 4,900 6,500 9,500 14,000
60,000 2,500 3,800 5,200 7,000 10,000 15,000
80,000 2,700 4,000 5,700 7,75 0 11,000 17,000
100,000 2,900 4,200 6,200 8,500 12,000 18,000
150,000 3,200 4,600 7, 30 0 10,000 14,000 21,000
200,000 3,300 4,700 8,000 11,000 16,000 23,000
Visit www.littelfuse.com/llsrk for 600 V Current-Limiting effects
Current-Limiting Effects of LLSRK and LLSRK_ID (600 V) Fuses
30 A 60 A 100 A 200 A 400 A 600 A
5,000 900 1,400 2,000 2,700 4,800 5,000
10,000 1,100 1,900 2,700 3,500 6,200 8,500
15,000 1,250 2,100 3,100 4,200 7,000 9,500
20,000 1,400 2,400 3,500 4,600 8,000 10,800
25,000 1,500 2,600 3,900 5,000 8,300 11,500
30,000 1,600 2,800 4,000 5,250 9,000 12,000
35,000 1,700 2,850 4,300 5,500 9,500 12,500
40,000 1,800 3,000 4,600 5,800 9,800 13,500
50,000 1,900 3,200 4,800 6,300 10,200 14,000
60,000 2,000 3,500 5,200 6,700 11,000 15,000
80,000 2,200 3,900 5,700 7,2 00 12,200 16,000
100,000 2,300 4,000 6,000 8,100 12,700 17,000
150,000 2,500 4,500 6,700 9,100 14,000 19,000
200,000 2,600 4,800 7,000 9,700 15,000 20,000
*Prospective RMS Symmetrical Amperes Short-Circuit Current Visit www.littelfuse.com/llnrk for 250 V Current-Limiting effects
Note: Data derived from Peak Let-Thru Curves
Current-Limiting Effects of LLNRK (250 V) Fuses
Blown Fuse Indicator Assembly
Granular Quartz Filling
Precision Formed Short Circuit Element
Fiberglass Reinforced Pultruded Body
Elastomeric Silicone Overload Section
Plated End Caps
LLSRK_ID Fuses—Quality Construction
for performance you can rely on…
Littelfuse LLSRK_ID Fuses feature true dual-element
construction. This robust design withstands
repeated surges within rated time delay
without opening needlessly, eliminating
downtime caused by power surges
or equipment demands.