Current Transducer LA 100-TP
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
IPN Primary nominal r.m.s. current 100 A
IPPrimary current, measuring range 0 .. ± 150 A
R M Measuring resistance @ TA = 70°C TA = 85°C
RM min RM max RM min RM max
with ± 12 V @ ± 100 A max 050 042
@ ± 120 A max 022 014
with ± 15 V @ ± 100 A max 0110 20 102
@ ± 150 A max 033 20 25
ISN Secondary nominal r.m.s. current 50 mA
K N Conversion ratio 1 : 2000
VCSupply voltage (± 5 %) ± 12 .. 15 V
ICCurrent consumption 10 (@ ± 15 V) + ISmA
VdR.m.s. voltage for AC isolation test, 50 Hz, 1 mn 2.5 kV
VbR.m.s. rated voltage 610 V
Accuracy - Dynamic performance data
XAccuracy @ IPN , TA = 25°C @ ± 15 V (± 5 %) ± 0.45 %
@ ± 12 .. 15 V (± 5 %) ± 0.70 %
εLLinearity < 0.15 %
Typ Max
IOOffset current @ IP = 0, TA = 25°C ± 0.10 mA
IOM Residual current 1) @ IP = 0, after an overload of 3 x IPN ± 0.15 mA
IOT Thermal drift of IO- 25°C .. + 85°C ± 0.05 ± 0.25 mA
- 40°C .. - 25°C ± 0.10 ± 0.50 mA
traReaction time @ 10 % of IP max < 500 ns
trResponse time 2) @ 90 % of IP max < 1 µs
di/dt di/dt accurately followed > 200 A/µs
fFrequency bandwidth (- 1 dB) DC .. 200 kHz
General data
TAAmbient operating temperature - 40 .. + 85 °C
TSAmbient storage temperature - 50 .. + 95 °C
R S Secondary coil resistance @ TA = 70°C 120
TA = 85°C 128
mMass 24 g
Standards 3) EN 50178
Notes : 1) The result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs
3) A list of corresponding tests is available
Features
Closed loop (compensated) current
transducer using the Hall effect
Printed circuit board mounting
Insulated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
IPN =100 A
981120/5
LEM Components www.lem.com
Remarks
IS is positive when IP flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
100°C.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Mechanical characteristics
General tolerance ± 0.2 mm
Fastening & connection of primary bus bar
6.4 x 1.6 mm
Recommended PCB hole 3.8 mm
Fastening & connection of secondary 3 pins
0.6 x 0.7 mm
Recommended PCB hole 0.9 mm
Dimensions LA 100-TP (in mm. 1 mm = 0.0394 inch)
Bottom view
Front view
Left view
Secondary terminals
Terminal +:supply voltage +12 .. 15 V
Terminal -:supply voltage -12 .. 15 V
Terminal M:measure
Connection
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Standard 00 Year Week
or N° SP..