www.erskine-systems.co.uk
Telephone: +44 (0) 1723 583511
Fax: +44 (0) 1723 581231
Email: sales@erskine-systems.co.uk
Erskine Systems Limited
Eastfiald, Scarborough Y011 3DU, UK
S9077THL4 Rev 0
Erskine Systems Limited reserve the right to alter
this specification at any time without notice.
The Erskine SMS1200 utilises high frequency switchmode
technology to deliver a compact, efficient and reliable source of
DC power. The system provides 1200A output at a nominal -48v
DC in a single cabinet. The system comes complete with two
400A battery isolators and 6 outgoing distribution ways, each
rated 100A. These can be linked to the Erskine End of Suite
distribution board to provide expandable distributed power.
Real time monitoring and control is included in the form of the
Erskine PMU (Power Management System) and PowerSentinel
software.
19” rack style cabinet
600W x 800D footprint
2090H (42U internal)
Max weight approx 550kg
Finish - Light Grey RAL7035
Ventilation - fan blown front to rear
-48V/1200A DC Output
Takes up to 12 x 100A rectifiers
Can be supplied part populated
to allow future expansion
Hot plug rectifier replacement
Passive current sharing across
all rectifiers
Voltage trim facility
Battery current limit facility
Over-temperature shutdown and
automatic reset
Real time monitoring and control
Rectifier input MCB’s
Optional door front
Battery monitoring and
programmable discharge testing
Battery low volts disconnect
facility
RS232 port and (optional)
modem
2 x 400A battery isolators
6 x 100A single pole distribution
mcb’s
High Power Density
12 x TSC5648A
rectifiers
Real time Monitoring
& Control
2 x Battery Isolators
6 x 100A distribution
Product
Description
Mechanical
Features
SMS1200
-48V/1200A DC POWER SYSTEM
www.erskine-systems.co.uk
Telephone: +44 (0) 1723 583511
Fax: +44 (0) 1723 581231
Email: sales@erskine-systems.co.uk
Erskine Systems Limited
Eastfiald, Scarborough Y011 3DU, UK
S9077THL4 Rev 0
Erskine Systems Limited reserve the right to alter
this specification at any time without notice.
Electrical
DC Output
Float Voltage
Equalise Voltage
System Input 380V to 415V, Frequency 50Hz/60Hz, 3 phase, 4 wire
Note: rectifiers are single phase AC input, connected Ph - N with the load spread evenly across all
three phases.
Rectifier Input voltage range 176V to 264V (230V+15% to 220V -20%)
LCD Display includes:
Load Volts/Amps
Battery Volts/Amps
Ambient Temperature
Humidity
Altitude
0˚C to +45˚C operating, -40˚C to +85˚C storage, -20˚C to +65˚C transportation
Up to 90% relative humidity, non-condensing
Up to 2000m operating, up to 3000m storage
AC Output
Alarm and Control
Environmental
Key pad enables set-up of system parameters, local control, and viewing event log
Individual rectifier output currents
Battery temperature (if optional probe is fitted)
LED Indicators
Rectifier PMU
Function
Input Healthy
Output Healthy
Current Output
High Output Volts
Over Temperature
Current Limit
Colour
Yellow
Green
Green
Red
Red
Red
Function
AC Supply Fail
Float
Equalise
Low DC Voltage
Low Volts Disconnect
High DC Voltage
Single Rectifier Fail
Multiple Rectifier Fail
Battery On Discharge
Colour
Yellow
Green
Green
Yellow
Yellow
Red
Yellow
Yellow
Yellow
EMC Compliance
Emission
Immunity
Harmonics EN 61000-3-2, 0-2Khz
Conducted EN 55022-B, 0.15-30Mhz
Radiated EN 55022-B (10m), 30Mhz - 1GHz
Fast Transients En 61000-4-4
ESD EN 61000-4-2
Radiated Immunity EN 61000-4-3 (10V/m)
Conducted Immunity EN 61000-4-6
Surge Immunity EN 61000-4-5
Other Features
Floating or Positive DC earthed
EN 60950
Rectifier MTBF >40 years as defined by HRD5
Optional battery probe for temperature compensated
battery charging voltage
DC Earthing
Safety
Reliability
NTC
54.48V (2.27V/Pb cell) (can be adjusted to suit other battery configurations)
57.6V (2.4V/Pb cell). (can be adjusted to suit other battery configurations)